This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
Side
B
Side
A
Side
B
JAPANESE
ENGLISH
JY997D13801F
Safety Precaution
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and
.
Depending on the circumstances, procedures indicated by
may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
IIndicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name
Manual No.
Description
FX
3G
Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains the FX
3G
Series PLC
s p e c i f i c a t i o n s f o r I / O , w i r i n g ,
installation, and maintenance.
FX
3U
Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains the FX
3U
Series PLC
s p e c i f i c a t i o n s f o r I / O , w i r i n g ,
installation, and maintenance.
FX
3UC
Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains the FX
3UC
Series PLC
s p e c i f i c a t i o n s f o r I / O , w i r i n g ,
installation, and maintenance.
F X
3 G
/ F X
3 U
/ F X
3 U C
Series
Programming Manual
- B a s i c & A p p l i e d
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming for
basic /applied ins tructions and
devices.
FX Series User’s
Manual
- Data Communication
Edition
JY997D16901
MODEL CODE:
09R715
Explains N:N network, Parallel Link,
C o m p u t e r L i n k , N o n - P r o t o c o l
communication by RS and RS2
instructions/FX
2N
-232IF.
Applicable standards
FX
3U
-485ADP
units made in June, 2005 or later comply with the EC Directive (EMC
Directive) and UL standards (UL, cUL). Further information can be found in the
following manual.
→
Refer to the FX
3G
Series Hardware Manual (Manual No. JY997D33401)
→
Refer to the FX
3U
Series Hardware Manual (Manual No. JY997D18801)
→
Refer to the FX
3UC
(D, DSS) Series Hardware Manual (Manual No.
JY997D28601)
→
Refer to the FX
3UC
-32MT-LT-2 Hardware Manual (Manual No. JY997D31601)
Regarding the standards that relate to the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
1. Outline
The FX
3U
-485ADP communication special adapter (hereinafter called 485ADP) is a
special adapter for RS-485 communication with a terminal block (European type).
The 485ADP is an isolated signal exchange unit of RS-485 serial data communication
between the PLC and an RS-485 device.
1.1 Communication Function
1.2 Incorporated Items
Verify that the following product and items are included in the package:
The label should be applied on the front of 485ADP for checking station numbers in
N:N network, computer link, etc.
1.3 External Dimensions, Part Names and Terminal Layout
Communication type
Function
N:N network
Data transfer connecting up to eight FX Series PLCs.
Parallel link
Data transfer between two FX Series PLCs relationship
specifying master/slave station.
Computer link
Data transfer between the PLC and computer (specified as
the master station) via dedicated protocol.
Non-protocol
communication
Serial communication between the PLC and an RS-485
device via non-protocol.
Inverter
communication
Controlling Mitsubishi's FREQROL inverter using inverter
communication instructions.
[1] DIN rail mounting groove (DIN rail: DIN46277)
[2] Name plate
Station 15
Station 12
Station 11
Station 10
Station 9
Station 8
Station 7
Station 6
Station 5
Station 4
Station 3
Station 2
Station 1
Station 0
Station 14
Station 13
JY818D61301A
Netwrork Station No.
Station 16
Station
Station
Manual
This
manual
Product
Label
POWER
RD
SD
FX
3U
-485ADP
74(2.92")
[6]
[5]
[7]
[8]
[9]
[10]
[3]
[12]
[14]
[11]
Weight: Approx. 80g (0.18 lbs)
Special adapter
connector cover
is removed
7(0.28")
15.5
(0.65")
90(3.55")
98(3.86")
106(4.18")
17.6
(0.7")
15.1
(0.6")
[13]
[2]
[4]
[1]
RDA
RDB
SDA
SDB
SG
1.4 Terminal Configuration
The terminal configuration of the RS-485 terminal on the 485ADP is shown below.
1.5 Terminal Resistor Selector Switch
485ADP has a built-in terminal resistor.
A terminal resistor may be required depending on the communication type. Refer to the
following manual for the terminal resistor setting.
→
Refer to the FX Series User's Manual - Data Communication Edition
2. Channel Allocation
Up to two communication ports can be added to the main unit.
FX
3U
/
FX
3UC
-32MT-LT(-2) Series PLC
Communication port channels are automatically allocated. The communication special
adapter closer to the main unit is ch1.
•
Using one communication special a communication expansion board
•
Using two communication special adapters
[3] Special adapter slide lock:
Used to connect additional special adapters onto left side of this special adapter.
[4] Special adapter connector cover:
Remove this cover to connect additional special adapters on the left side.
[5] Direct mounting hole:2 holes of
φ
4.5 (0.18") (mounting screw: M4 screw)
Not used when connecting to FX
3UC
Series PLC.
[6] POWER LED (green): Lit while 5V DC power is supplied from main unit.
[7] RD LED (red):
Lit while receiving data from connected RS-485 device.
[8] SD LED (red):
Lit while sending data to connected RS-485 device.
[9] Terminal resistor selector switch (330
Ω
/OPEN/110
Ω
)
[10] Special adapter connector:
Used to connect this special adapter to PLC main unit or special adapter.
[11] Terminal block (European type) for connecting RS-485 device
Use to connect RS-485 device to 485ADP.
[12] DIN rail mounting hook
[13] Special adapter fixing hook
[14] Special adapter connector:
Used to connect communication or analog special adapter to the left side of the
485ADP.
Signal
name
Function
Signal direction
485ADP
RS-485
equipment
RDA(RXD+)
Receive data
←
RDB(RXD-)
SDA(TXD+)
Send data
→
SDB(TXD-)
SG(GND)
Signal ground
−
Terminal screws
RDA
RDB
SDA
SD
B
SG
Setting terminal
resistor to 330
Ω
330
Ω
OPEN
110
Ω
Setting no
terminal resistor
330
Ω
OPEN
110
Ω
Setting terminal
resistor to 110
Ω
330
Ω
OPEN
110
Ω
Analog
special
function
adapter
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
Analog
special
function
adapter
Main unit
Communication function
extension board (ch1)
(ch2)
Analog
special
function
adapter
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
Analog
special
function
adapter
FX
3U
-
485ADP Main unit
FX
3U
-CNV-BD
(ch1)
(ch2)
FX
3UC
(
D, DSS
) Series PLC
Communication port channels are automatically allocated. The communication
special adapter closer to the main unit is ch1.
FX
3G
Series PLC
Communication port channels are automatically allocated.
•
40-point, 60-point type
•
14-point, 24-point type
3. Installation
For installation/uninstallation details, refer to the following manuals:
→
Refer to the FX
3G
Series User's Manual - Hardware Edition.
→
Refer to the FX
3U
Series User's Manual - Hardware Edition.
→
Refer to the FX
3UC
Series User's Manual - Hardware Edition.
INSTALLATION
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•
Use the product within the generic environment specifications described in
PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive
dusts, corrosive gas (salt air, Cl
2
, H
2
S, SO
2
, or NO
2
), flammable gas,
vibration or impacts, or expose it to high temperature, condensation, or rain
and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•
When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•
Connect special adapter securely to their designated connectors.
Loose connections may cause malfunctions.
Analog
special
function
adapter
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
Analog
special
function
adapter
FX
3U
-
485ADP Main unit
(ch1)
(ch2)
FX
3U
-
485ADP
Analog
special
function
adapter
FX
3U
-
485ADP
Main unit
(ch1)
Analog
special
function
adapter
Connector conversion adapter
(ch2)
Analog
special
function
adapter
Analog
special
function
adapter
FX
3U
-
485ADP
Main unit
Communication
expansion board (ch2)
(ch1)
Connector conversion adapter
Analog
special
function
adapter
FX
3U
-
485ADP
Main unit
(ch1)
Connector conversion adapter
3.1 Connection to the FX
3U
Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter,
and demount the main unit and special adapter mounted on DIN rail or
mounted directly using screws.
2) Install an expansion board to the main unit.
For the expansion board installation procedure, refer to the following manual:
→
Refer to the FX
3U
Series User's Manual - Hardware Edition
3) Remove the special adapter connector cover
on the expansion board (fig.A).
When connecting this product to another
special adapter, please replace the
'expansion board' in the above description
with a 'special adapter' and perform the
procedure as indicated.
4) Slide the special adapter slide lock
(fig.B) of the main unit.
When connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated.
5) Connect the
special adapter
(fig.C) to the
main unit as
shown on the
right.
6) Slide back the
special adapter
slide lock (fig.B)
of the main unit
to fix the special
adapter (fig.C).
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
3.2 Connection to the FX
3UC
(D, DSS) Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Remove the special adapter connector
cover (fig.A).
3) Slide the special adapter slide lock (fig.B)
of the main unit.
when connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a
'special adapter' and perform the
procedure as indicated.
4) Connect the
special
adapter (fig.C)
to the main
unit as shown
on the right.
5) Slide back the
special
adapter slide
lock (fig.B) of
the main unit
to fix the
special
adapter (fig.C)
3.3 Connection to the FX
3UC
-32MT-LT(-2) Series PLC
→
For details, refer to the FX
3UC
Series User's Manual - Hardware Edition.
RUN
STOP
FX
3U
-48MR/ES
FX
3U-48M
3)
4)
B
B
A
4)
RUN
STOP
FX
3U
-48MR/ES
FX
3U
-48M
0
IN
10
1
POWER
RD
SD
FX
3U-485ADP
FX
3U-48M
6)
C
B
B
5)
5)
5)
6)
4)
3)
B
A
B
3)
2)
POWER
RD
SD
FX
3U-485ADP
5)
C
B
B
4)
4)
4)
5)
3.4 Connection to the FX
3G
Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from the DIN
rail.
2) Install a connector conversion adapter to the main unit.
For the connector conversion adapter installation procedure, refer to the following
manual:
→
Refer to the FX
3G
Series User's Manual - Hardware Edition
3) Remove the special adapter connector cover
when connecting this product to another
special adapter.
Removal of the special adapter connector
cover is not required when connecting this
product to the connector conversion adapter.
4) Slide the special adapter slide lock (fig.A) of the
connector conversion adapter.
When connecting this product to another special
adapter, please replace the 'connector
conversion adapter' in the above description
with a 'special adapter' and perform the
procedure as indicated.
5) Connect the special
adapter (fig.B) to the
connector conversion
adapter as shown on
the right.
6) Slide back the special
adapter slide lock
(fig.A) of the
connector conversion
adapter to fix the
special adapter (fig.B).
4. Wiring
For wiring details, refer to the FX Series User's Manual - Data Communication Edition.
Wiring precaution
•
Do not attach the terminal block (replacement European terminal block) for
connecting RS-485 device which is already wired to FX
3U
-485-BD.
If attached as its left and right are confused, the terminal configuration becomes
upside down and no communication is performed.
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•
Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
•
Make sure to observe the following precautions in order to prevent any damage to
the machinery or accidents due to abnormal data written to the PLC under the
influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
Otherwise, noise disturbance and/or surge induction are likely to take place. As
a guideline, lay the control line at least 100mm (3.94") or more away from the
main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the PLC.
However, do not use common grounding with heavy electrical systems.
•
Make sure to properly wire to the European terminal board in accordance with the
following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should follow the dimensions described by
the above manual.
- Tightening torque should follow the specifications by the above manual.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires of
unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
A
4)
4)
A
3)
POWER
RD
SD
FX
3U-485ADP
A
6)
A
B
6)
5)
5)
5)
5. Specifications
5.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
5.2 General Specifications
For the general specifications, refer to the manual of the PLC main unit.
The items other than the following are equivalent to those of the PLC main unit.
5.3 Power Supply Specifications
5.4 Performance Specification
*1 Only the FX
3G
PLC supports 38400 bps.
STARTUP AND
MAINTENANCE
PRECAUTIONS
•
Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
•
Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•
Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•
The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name
Applicability
FX
3U
Series PLC
Ver.2.20 or later (from first production)
FX
3UC
Series PLC Ver.1.00 or later (from first production)
FX
3G
Series PLC
Ver.1.00 or later (from first production)
Item
Specification
Dielectric withstand
voltage
500 V AC, 1 min
Conforming to JEM-1021
Between terminal block
and ground terminal of
PLC main unit
Insulation resistance
5 M
Ω
o r m o r e , 5 0 0 V D C b y
Megger
Item
Specification
Current
consumption
20mA
5V DC power is supplied from the internal power supply of
main unit.
Item
Specification
Transmission
standard
Conforming to RS-485/RS-422
Type of isolation
Photocoupler isolation
Transmission
distance
Total extension distance: 500m (1640' 5") or less
[50m (164' 0") or less if FX
2N
-485-BD, FX
1N
-485-BD or
FX
3U
-485-BD, FX
3G
-485-BD is installed to connected
equipment]
Connection method
European type terminal block, AWG 22-20 (when inserting
one twisted pair cable), AWG 22 (when inserting two twisted
pair cables)
Tightening torque: 0.22 to 0.25 N
•
m
Number of occupied
I/O points
0 point (This number is not related to the maximum number
of input/output points of the PLC.)
Communication
method
Half-duplex
Baud rate
Computer Link, Non-Protocol Communication:
300/600/1200/2400/4800/9600/19200/38400
*1
bps
Communication
format
N:N network, Parallel Link
Computer Link (dedicated protocol: format 1/format 4), Non-
Protocol
LED display:
LED color
Power: green, RD: red, SD: red
6. Operation of Terminal Resistor Selector Switch
Use the tip of tweezers, tip of mechanical pencil, minute screwdriver, or the tool
whose tip width is about 0.8mm (0.03") when operating the terminal resistor
selector switch.
Either 'push down' or 'push up' the switch to change the setting as indicated in
the figure above.
Confirm the clicking noise when setting the switch.
330
Ω
OPEN
110
Ω
Pushing down
direction
Pushing up direction
Tool
Switch
330
Ω
OPEN
110
Ω
330
Ω
OPEN
110
Ω
Tool
FX
3U
-485ADP
Installation Manual
This manual describes the part names, dimensions, mounting, and
specifications of the product. Before use, read this manual and the manuals of
all relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective September 2008
Specifications are subject to change without notice.
©
2005 Mitsubishi Electric Corporation
Manual Number
JY997D13801
Revision
F
Date
September 2008