6.12
Error Status Register [BFM #29 Bit0 to Bit13]
BFM Access : Read / Write
This BFM shows the 32DP’s error status. In the General Error (BFM#29 Bit0 = ON), the 32DP sends the data
from BFM#28 and #29 as diagnostic data to the DP-Master, while suspending the normal data exchange.
When turning the PLC from STOP to RUN, all BFM#29 Bits turn OFF except Bit3, 4, 12 and 13.
The 32DP maps this BFM to BFM#1308.
*1.
BFM#37 shows the error reason.
→
For details on BFM#37, refer to Section 6.18
*2.
BFM#38 shows the error reason.
→
For details on BFM#38, refer to Section 6.19
*3.
BFM#35 shows the error reason.
→
For details on BFM#35, refer to Section 6.16
*4.
BFM#27 includes additional information.
→
For details on BFM#27, refer to Section 6.10
6.13
Module ID Code [BFM #30]
BFM Access : Read Only
This BFM shows " 7150 " as the Module ID Code of the 32DP, given by its vendor.
6.14
Master Address [BFM #33]
BFM Access : Read Only
This BFM shows the DP-Master address on the DP network, where the 32DP exists. When the DP-Master
does not recognize the 32DP, this BFM value is 00FFh.
Bit No.
Name
Description
Bit 0
General Error
ON when any one or more of BFM#29’s Bit1, 8 to 13 is ON
Bit 1
PLC in STOP mode
ON when the connected PLC is in STOP mode, and turns OFF
when the PLC switches into RUN
Bit 2
Extended-user Alarm/Diagnostic
Data Not Yet Sent Flag
ON when BFM#25 Bit2 is not 0
Bit 3
Hardware Error
ON when the 32DP detects an internal hardware error
Bit 4
EEPROM Error
ON when the slave address data in the EEPROM is corrupt
Bit 5
Consistency Handling Error Flags ON when the 32DP detects a consistency error
*1
Bit 6
Setting Error Flag
ON when the 32DP detects an incorrect BFM setting
*2
Bit 7
Not Available
−
Bit 8
Watchdog DP Timeout
ON when the 32DP detects no reply from the DP-Master within the
preset watchdog time
Bit 9
Acyclic Communication Error
ON when an error occurs in acyclic communication
*3
Bit 10
Configuration Error
ON when the 32DP receives incorrect Config Data
Bit 11
Parameter Error
ON when the 32DP receives incorrect Parameter Data
Bit 12
Slave Address Change Error
ON when the 32DP detects an incorrect address or the address
outside the range : 0 to 126
*4
Bit 13
Slave "Reset No Address
Change" Error
ON when the 32DP detects an error due to resetting the Address
Change Impossible Flag (BFM#25 Bit8)" in Data Exchange mode,
or resetting this flag while the access to BFM#25 Bit8 is disabled
Bit 14 to 15 Not Available
−