FX2N-64CL-M CC-Link/LT Master Block Model
Assignment of Buffer Memory 10
10-9
10.2.11 Detailed error information [BFM #29 (1Dh)]
Each type of error is assigned to a bit of the buffer memory [BFM #29 (1Dh)]. The status is
indicated by the 0 (OFF)/1 (ON) status of each bit.
Bit
Function
Description
Error flag restoration
operation
b0
Link error in
some stations
Turns ON when link error has occurred in
some stations. [Turns ON when any bit in
BFM #4 (4h) to 7 (7h) have turned ON.]
For the station number in which error has
occurred, refer to the link error station
information [BFM #4 (4h) to 7 (7h)].
When the cause of the error is
eliminated, the error flag is
automatically restored.
b1
Link error in all
stations
Turns ON when data link error has
occurred in all stations.
b2
Remote I/O
error
Turns ON when remote I/O error has
occurred. [Turns ON when any bit in BFM
#8 (8h) to 11 (Bh) have turned ON.]
For the station number, refer to the remote
I/O error information [BFM #8 (8h) to 11
(Bh)].
For type of error, refer to the instruction
manual of each remote station.
b3
Out-of-control-
range station
error
Turns ON when a remote station not
registered in the detailed remote station
information [BFM #32 (20h) to #95 (5Fh)]
is connected to the network.
When the station number of
the connected remote station
is smaller than the final station
number, the error flag is
automatically restored when
the cause of the error is
eliminated.
When the station number of
the connected remote station
is larger than the final station
number, the error flag is
restored when the cause of
the error is eliminated and is
followed by a power reset.
b4
Transmission
speed setting
error
Turns ON when the transmission speed
setting DIP switch is set to a incompatible
position.
When the cause of the error is
eliminated, and power is reset,
the error flag is automatically
restored.
b5
Communication
power down
Turns ON at communication power down.
When the cause of the error is
eliminated, the error flag is
automatically restored.
b6
RD station
setting error
•
Turns ON when the RD station is
connected to a station number outside
the range No. 49 to No. 64.
•
Turns ON when the RD station is used
in the 4-point mode.
When the cause of the error is
eliminated and the power is
reset, the error flag is
automatically restored.
Содержание FX2N-64CL-M
Страница 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block x ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Страница 48: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 10 ...
Страница 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Страница 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Страница 93: ......