FX2N-64CL-M CC-Link/LT Master Block
Troubleshooting 12
12-6
b6
• Turns ON when the RD station is
connected to a station number outside the
range from No. 49 to No. 64.
• Turns ON when the RD station is used in
the 4-point mode.
When the cause of the error is eliminated
and power is reset, the error flag is
automatically restored.
b7
Turns ON when EEPROM write error or read
error has occurred or when the request to
write EEPROM is given in any mode other
than the CONFIG mode.
• Set the FX
2N
-64CL-M to the CONFIG
mode, and write data to the EEPROM
again.
b8
Turns ON when the DIP switch setting is
changed during operation.
• Return the DIP switch setting to the status
at the time of power ON.
• If the DIP switch setting should be
changed, change the DIP switch setting,
reset power.
b9 to b14
--
--
b15
Turns ON when abnormality is detected in
the self-loop-back test. (When the FX
2N
-
64CL-M is connected to the FX
1N
Series
PLC, check for hardware errors in the status
indicator LEDs.)
• Refer to "12.4 Self-loop-back test".
Bit
Description
Countermeasures
Содержание FX2N-64CL-M
Страница 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block x ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Страница 48: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 10 ...
Страница 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Страница 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Страница 93: ......