FX2N-64CL-M CC-Link/LT Master Block
Specifications 2
2-4
2.4
Performance specifications
*1 When connected to an FX
1N
Series PLC, up to two FX
2N
-64CL-M can be connected to each of the main and
extension units.
Item
Specification
Applicable PLC
FX
1N
/FX
2N
/FX
2NC
/FX
3U
/FX
3UC
Series PLC
(FX
2NC
-CNV-IF is required when FX
2NC
Series PLC is connected.)
(FX
2NC
-CNV-IF or FX
3UC
-1PS-5V is required when FX
3UC
Series PLC is
connected.)
Number of connectable master
blocks
FX
1N
Series: Up to 4
*1
FX
2N
Series: Up to 8
*2
FX
2NC
Series: Up to 3
*2
FX
3U
Series: Up to 8
*2
FX
3UC
Series: Up to 8
*2 *3
Applicable point mode
4-point mode and 16-point mode (selectable by DIP switch)
Cont
ro
l s
p
e
c
if
ic
ati
o
n
s
4-point mode
16-point mode
Maximum number of link points
Connected to FX
1N
Series PLC: 128 points
Connected to FX
2N
/FX
2NC
/FX
3U
/FX
3UC
Series PLC: 256 points
(including the number of I/O points in each PLC) (For the number of I/O
points in each PLC, refer to the manual of the PLC main unit.)
Number of link points per station
( ) shows the number of link
points when composite remote
module is used.
4 points (8 points)
16 points (32 points)
Li
nk
sc
an
ti
me
32 stations
Points
128 points
256 points
2.5Mbps
0.7ms
1.0ms
625kbps
2.2ms
3.8ms
156kbps
8.0ms
14.1ms
64 stations
Points
256 points
256 points
2.5Mbps
1.2ms
2.0ms
625kbps
4.3ms
7.4ms
156kbps
15.6ms
27.8ms
C
o
mmuni
ca
tio
n
s
pec
if
ic
ati
ons
Communication speed
2.5 Mbps, 625 kbps and 156 kbps (selectable by DIP switch)
Protocol
BITR method (Broadcastp Interval Timed Response)
Network topology
T-branch
Error control method
CRC
Number of connected stations
64 stations maximum
Remote station numbers
1 to 64
Master station connection
position
Connected at end of trunk line
RAS function
Communication error detection, automatic return to system, slave station
disconnection and internal loop back diagnosis
Connection cable
Dedicated flat cable (0.75 mm
2
×
4)
VCTF cable (0.75 mm
2
×
4 cable
specifications, refer to Section 2.3
)
High flexible cable (0.75 mm
2
×
4)
Number of occupied I/O points
8 points (fixed) + Number of connected remote I/O points (in multiples of eight)
Current consumption inside 5V DC 190 mA (Supplied by PLC via extension connector)
24V DC power
supply
Voltage
20.4V to 28.8V DC
Supplied from power adapter or
dedicated power supply via
connector.
Current
consumption
25 mA
Initial current
35 mA
Mass (weight)
0.15 kg (0.33 lbs)
Содержание FX2N-64CL-M
Страница 1: ...USER S MANUAL Detailed Volume FX2N 64CL M CC Link LT Master Block ...
Страница 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Страница 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Страница 12: ...FX2N 64CL M CC Link LT Master Block x ...
Страница 26: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 ...
Страница 48: ...FX2N 64CL M CC Link LT Master Block Connection of Cables Connectors and Terminating Resistors 6 6 10 ...
Страница 50: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 ...
Страница 74: ...FX2N 64CL M CC Link LT Master Block Model Assignment of Buffer Memory 10 10 14 ...
Страница 93: ......