FX

2N

-232IF RS232C INTERFACE BLOCK

HARDWARE MANUAL

JY992D73501B

This manual contains text, diagrams and explanations which will guide the reader in the correct installation
and operation of the FX

2N

-232IF RS232C Interface Block. It should be read and understood before

attempting to install or use the unit. Further information can be found in the FX PROGRAMMING MAN-
UAL, FX series hardware manuals.

If in doubt at any stage during the installation of the FX

2N

-232IF RS232C Interface Block always consult a

professional electrical engineer who is qualified and trained to the local and national standards. 

1. INTRODUCTION

The RS232C interface block FX

2N

-232IF (hereinafter referred to as "232IF") is connected to the FX

2N

/

FX

2NC

/FX

3U

/FX

3UC

 series PLC to realize full duplex serial data communication with another RS232C

interface such as a personal computer, bar code reader, printer, etc.

1) Two or more devices with RS232C interfaces can be connected to an FX

2N

/FX

2NC

/FX

3U

/FX

3UC

 series

PLC by using the RS232C special function block. Up to 8 special function block can be connected to

the FX

2N

/FX

3U

/FX

3UC*1

 series PLC. Up to 4 special function block can be connected to the FX

2NC

PLC. (Refer to section 2.1)

2) Communication requires no protocol

Full-duplex asynchronous communication between RS232C devices is specified through buffer mem-
ory (BFM). The FROM/TO instruction is used for the buffer memory.

3) The send/receive buffer can accommodate 512 bytes/256 words.

When the RS232C interlink connection mode is used, data exceeding 512 bytes/256 words can also
can be received.

4) ASCII/HEX conversion function

The function to convert and send and a hexadecimal numeric (0 to F) saved in the send data buffer as
well as the function to convert a received ASCII code into a hexadecimal numeric (0 to F) and save it
to the receive buffer are provided.

*1 Up to 7 special function block can be connected to the FX

3UC

-32MT-LT PLC

2. Specifications

2.1 External Dimensions and Part Names

Dimensions:mm(inches)

Weight: Approx. 0.3 kg 

Accessory:Special block No. label

POWER

RD

SD

24

+
24

-

80(3.15")

mounting 

hole 

pitch

55(2.17")

4(0.16")

85(3.35")

POWER

RD

SD

FX  -232IF

2N

90(3.54")

➂ ➃ ➄

c

Extension cable

d

Mounting hole (2-

φ

4.5(0.18"))

e

POWER LED :Lit when both the 5V DC power supplied from the main unit and the 24V DC power

supplied from the external terminal are supplied.

f

SD LED:Lit while data is sent to the RS232C equipment connected to the 232IF.

g

RD LED:Lit while data is received from the RS232C equipment connected to the 232IF.

h

Terminal screws (M3 (0.12"))

i

Next step extension connector

j

RS232C connector (9-pin D-SUB connector: #4-40unc inch screw thread)

k

DIN rail clip

l

DIN rail groove (35(1.38"))

2.2 Connector Pin Layout

1

2

3

4

5

9
8
7
6

*

<  > 

At selection of interlink connection mode

Pin No.

Signal name

Meaning

Function

1

CD(DCD)

Carrier detection

This signal indicates only status.

2

RD(RXD)

Receive data

Receive data (RS232C device to 232IF)

3

SD(TXD)

Send data

Send data (232IF to RS232C device)

4

ER(DTR)

Data terminal ready

ON when Send/Receive enable is ON

5

SG

Signal ground

Signal ground

6

DR(DSR)

Data set ready

This signal indicates only status.

7

RS(RTS)

Request to send
<Clear to receive>*

ON when Send command is ON
<ON when 232IF is Receive enabled>*

8

CS(CTS)

Clear to send

ON when RS232C device is ready to receive

9

CI(RI)

Calling indication

This signal indicates only status.

2.3 System Configuration

RS-232C device

Personal computer

Bar code reader

Printer

FX

2N

-232IF

RS-232C:max 15m

PLC

FX

2N

/FX

3U 

PLC

FX

2NC

/FX

3UC 

P

LC

To connect this block to the FX

2NC

 Series

PLC, the FX

2NC

-CNV-IF is required

or

FX

2NC

-CNV-IF

To connect this block to the FX

3UC

 Series

PLC, either the FX

2NC

-CNV-IF or FX

3UC

-

-1PS-5V is required.

FX

3UC

-1PS-5V

or

3. WIRING AND CONNECTION

3.1 Connection with the programmable controller

The 232IF can be connected to the FX

2N

/FX

2NC

/FX

3U

/FX

3UC

 programmable controller or connected on

the right side of another extension block/unit. A number is assigned to each special unit/block counting
from the one nearest the main unit in the way of No.0, No.1. . . No.7". Up to 8 FX

2N

-232IF units can be

connected to the FX

2N

/FX

3U

/FX

3UC*1

 Series PLC. Up to 4 FX

2N

-232IF units can be connected to the

FX

2NC

 Series PLC. However, the capacity of the 5V DC power supplied from the programmable controller

is limited. The current consumption of the 5V DC power in the 232IF is 40 mA. Make sure that the total
current consumption of the 5V DC power supply including other special blocks is equivalent to or less than
that available.

*1 Up to 7 units can be connected to an FX

3UC

-32MT-LT PLC

  

FX    -48MR-ES/UL

  

Block No.1 

  

FX    -232IF

  

FX    -16EX-ES/UL

  

Block No.0 

X000-X027

Y000-Y027

X030-X047

2N

  

FX    -232IF

2N

2N

2N

FX -48MR

2N

MELSEC

7

6

27

20

22 23 24 25 26

21

16 17

14

17

15

10

12 13

7

2

4 5 6

1

3

0

27

20

22 23 24 25 26

21

16

11

IN

L

X5

X7

X13

X15

X17

X21

X23

X25

X4

X6

X10

X14

X16

X20

X22

X24

24+

N

COM

X0

X1

X2

COM4

Y24

Y25

COM5

Y27

COM2

Y4

Y5

Y6

Y7

COM3

Y10

Y13

COM1

Y0

Y2

Y3

Y14

Y15

Y20

Y21

Y22

Y23

Y26

P

OWER

T.V

C

P

U.E

P

ROG.E

P

OWER

R

D

S

D

P

OWER

R

D

S

D

1

IN 0

7

2

3

4

5

6

P

OWER

1

IN 0

7

2

3

4

5

6

1

IN 0

7

2

3

4

5

6

P

OWER

1

IN 0

7

2

3

4

5

6

3.2 Power Supply Wiring

Handling of the crimp-style terminal

Use the crimp-style terminals of the dimensions shown on the fig-
ure on the left. Make sure that the tightening torque of the terminal
is 0.5 to 0.8 N

y

m.

Tighten each terminal securely to avoid malfunction.

FX

2N

programmable

controller

Extension

cable

FX

2N

-232IF

DC service supply of

programmable controller

may be used.

DC service supply

Class D 

grounding

100 

 or less

24V DC

±

10%

80mA

24+

24-

0V 24V

6.2mm

(0.24")

6.2mm

(0.24")

3.3 Connection Example

The signal wiring of the RS232C equipment varies depending on the RS232C specifications connected.
Check the specifications of the RS232C equipment used, then connect the signals correctly. Representa-
tive wiring examples are shown below.

1) Connection with counterpart equipment of terminal specifications (when control line is not used)

BFM #0 communication format: b9 = 0, b8 = 0, without control line

Communication is performed in accordance
with the condition determined by the soft-
ware in the 232IF and the counterpart equip-
ment.

232IF side

Signal

name

Pin
No.

SD(TXD)

3

RD(RXD)

2

SG(GND)

5

RS232C device side

Signal

name

9-pin

D-SUB

25-pin

D-SUB

SD(TXD)

3

2

RD(RXD)

2

3

SG(GND)

5

7

2) Connection with counterpart equipment of terminal specifications (when control line is used)

Cross cable used, BFM #0 communication format: b9 = 0, b8 = 1, standard RS232C mode

Because the carrier to send (CS) signal pin
of the 232IF itself receives the request to
send (RS) signal, signal transfer is per-
formed as if the counterpart equipment is
functioning.

*1 When the CD signal is not monitored, the

CD signal pin is not required to be con-
nected. The 232IF only monitors the sig-
nal status (ON/OFF).

*2  The 232IF only monitors the signal status

(ON/OFF).

232IF side

Signal

name

Pin
No.

SD(TXD)

3

RD(RXD)

2

RS(RTS)

7

CS(CTS)

8

CD(DCD)

1

ER(DTR)

4

DR(DSR)

6

SG(GND)

5

RS232C device side

Signal

name

9-pin

D-SUB

25-pin

D-SUB

SD(TXD)

3

2

RD(RXD)

2

3

RS(RTS)

7

4

CS(CTS)

8

5

CD(DCD)

1

8

ER(DTR)

4

20

DR(DSR)

6

6

SG(GND)

5

7

*1

*2

3) Interlink serial cross cable used, 

BFM #0 communication format: b9 = 1, b8 = 1, RS232C interlink connection mode

In the interlink connection mo de, data
exceeding 512 bytes (upper limit of the
receive buffer in the 232IF) can be received.

*1 In this mode, the Request to Send signal

(RS) functions as the receive enable sig-
nal in the 232IF. When receiving data that
exceeds 512 bytes (the upper limit of the
232IF receive buffer), the 232IF sets the
Request to Send signal (RS) to “OFF”
and requests the counterpart equipment
to suspend the data transmission. Once
the data saved in the receive buffer is
r ea d   by  th e   s e q u en c e   p r o gra m ,   th e
remaining data can be received.

*2 The 232IF only monitors the signal status

(ON/OFF).

232IF side

Signal

name

Pin
No.

SD(TXD)

3

RD(RXD)

2

RS(RTS)

7

CS(CTS)

8

ER(DTR)

4

DR(DSR)

6

SG(GND)

5

RS232C device side

Signal

name

9-pin

D-SUB

25-pin

D-SUB

SD(TXD)

3

2

RD(RXD)

2

3

RS(RTS)

7

4

CS(CTS)

8

5

ER(DTR)

4

20

DR(DSR)

6

6

SG(GND)

5

7

*1

*2

4) Connection with counterpart equipment of modem specifications (Control line is essential.)

Straight cable used, BFM #0 communication format: b9 = 0, b8 = 1, standard RS232C mode

232IF side

Signal

name

Pin
No.

SD(TXD)

3

RD(RXD)

2

RS(RTS)

7

CS(CTS)

8

CD(DCD)

1

ER(DTR)

4

DR(DSR)

6

SG(GND)

5

CI(RI)

9

RS232C device side

Signal

name

9-pin

D-SUB

25-pin

D-SUB

SD(TXD)

3

2

RD(RXD)

2

3

RS(RTS)

7

4

CS(CTS)

8

5

CD(DCD)

1

8

ER(DTR)

4

20

DR(DSR)

6

6

SG(GND)

5

7

CI(RI)

9

22

*1 When the CD signal is not being moni-

tored, the CD signal pin is not required
to be connected. The 232IF only moni-
tors the signal status (ON/OFF).

*2 The 232IF only monitors the signal sta-

tus (ON/OFF).

*3 When the CI signal is not required, the

CI signal pin is not required to be con-
nected. The 232IF only monitors the
signal status (ON/OFF).

*1

*2

*3

Содержание FX2N-232IF

Страница 1: ...consumption of the 5V DC power in the 232IF is 40 mA Make sure that the total current consumption of the 5V DC power supply including other special blocks is equivalent to or less than that available 1 Up to 7 units can be connected to an FX3UC 32MT LT PLC FX 48MR ES UL Block No 1 FX 232IF FX 16EX ES UL Block No 0 X000 X027 Y000 Y027 X030 X047 2N FX 232IF 2N 2N 2N FX 48MR 2N MELSEC 7 6 27 20 22 23...

Страница 2: ...consumption of the 5V DC power in the 232IF is 40 mA Make sure that the total current consumption of the 5V DC power supply including other special blocks is equivalent to or less than that available 1 Up to 7 units can be connected to an FX3UC 32MT LT PLC FX 48MR ES UL Block No 1 FX 232IF FX 16EX ES UL Block No 0 X000 X027 Y000 Y027 X030 X047 2N FX 232IF 2N 2N 2N FX 48MR 2N MELSEC 7 6 27 20 22 23...

Страница 3: ...consumption of the 5V DC power in the 232IF is 40 mA Make sure that the total current consumption of the 5V DC power supply including other special blocks is equivalent to or less than that available 1 Up to 7 units can be connected to an FX3UC 32MT LT PLC FX 48MR ES UL Block No 1 FX 232IF FX 16EX ES UL Block No 0 X000 X027 Y000 Y027 X030 X047 2N FX 232IF 2N 2N 2N FX 48MR 2N MELSEC 7 6 27 20 22 23...

Страница 4: ...ng When the RD LED is lit while data is received or the SD LED is lit while data is sent the installa tion and the wiring are correct 3 Make sure that the communication setting BFM 0 of the 232IF is equivalent to that of the external equipment If they are not equivalent each other correct as required 4 Verify the status of the data send receive device For example make sure that the counterpart equ...

Страница 5: ...ng When the RD LED is lit while data is received or the SD LED is lit while data is sent the installa tion and the wiring are correct 3 Make sure that the communication setting BFM 0 of the 232IF is equivalent to that of the external equipment If they are not equivalent each other correct as required 4 Verify the status of the data send receive device For example make sure that the counterpart equ...

Страница 6: ...consumption of the 5V DC power in the 232IF is 40 mA Make sure that the total current consumption of the 5V DC power supply including other special blocks is equivalent to or less than that available 1 Up to 7 units can be connected to an FX3UC 32MT LT PLC FX 48MR ES UL Block No 1 FX 232IF FX 16EX ES UL Block No 0 X000 X027 Y000 Y027 X030 X047 2N FX 232IF 2N 2N 2N FX 48MR 2N MELSEC 7 6 27 20 22 23...

Страница 7: ...ng When the RD LED is lit while data is received or the SD LED is lit while data is sent the installa tion and the wiring are correct 3 Make sure that the communication setting BFM 0 of the 232IF is equivalent to that of the external equipment If they are not equivalent each other correct as required 4 Verify the status of the data send receive device For example make sure that the counterpart equ...

Отзывы: