291
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
11
Hi
gh
-Speed
Counters
12
O
utput W
iri
ng
13
W
iri
ng for
V
ari
ous
Us
es
14
Te
st R
un,
Mai
nten
ance,
T
roubl
es
hooti
ng
15
IInput/Output
Pow
ered
Exte
nsi
on U
nit
s
16
Input/O
utput
Extens
ion
Bl
ock
s
17
Extension
Power Suppl
y
Un
it
18
Other Extens
ion
Uni
ts an
d
Opti
ons
19
D
isplay M
od
ule
20
Te
rminal
Bl
oc
k
15. FX
2N
-32/48E*-* (Input/Output Powered Extension Units)
DESIGN PRECAUTIONS
• Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during
external power supply problems or PLC failure.
Otherwise, malfunctions may cause serious accidents.
1) Most importantly, have the following: an emergency stop circuit, a protection circuit, an interlock circuit for
opposite movements (such as normal vs. reverse rotation), and an interlock circuit (to prevent damage to the
equipment at the upper and lower positioning limits).
2) Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all
outputs are turned off. Also, when an error that cannot be detected by the PLC CPU occurs in an input/output
control block, output control may be disabled.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
3) Note that the output current of the 24V DC service power supply varies depending on the model and the
absence/presence of extension blocks. If an overload occurs, the voltage automatically drops, inputs in the
PLC are disabled, and all outputs are turned off.
External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
4) Note that when an error occurs in a relay, triac or transistor output device, the output could be held either on
or off.
For output signals that may lead to serious accidents, external circuits and mechanisms should be designed
to ensure safe machinery operation in such a case.
DESIGN PRECAUTIONS
• Do not bundle the control line together with or lay it close to the main circuit or power line. As a guideline, lay the
control line at least 100mm (3.94") or more away from the main circuit or power line.
Noise may cause malfunctions.
WIRING PRECAUTIONS
• Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
• Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating
operation after installation or wiring work.
Failure to do so may cause electric shock.
Содержание FX2-16E series
Страница 2: ......
Страница 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Страница 508: ...FX3U Series Programmable Controllers User s Manual Hardware Edition 500 C Character code C 1 ASCII Code Table MEMO ...
Страница 510: ...502 FX3U Series Programmable Controllers User s Manual Hardware Edition D Discontinued models MEMO ...
Страница 519: ......