FX1S Series Programmable Controllers
Installation Notes 3
3-3
3.2
FX
1S
RUN/STOP Control
RUN or STOP of the FX
1S
can be controlled by:
n
The RUN/STOP switch mounted next to the programming port.
o
A standard input (X0 to X17) defined by the system parameters.
p
Remotely from a personal computer or other programming peripheral.
Note:The FX
1S
RUN/STOP switch works in parallel with the RUN input terminal. Please
refer to Table 3.2.
During remote operation the FX
1S
RUN/STOP status is determined by the most recently
operated control.
E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal
computer, the PLC can only be restarted with the RUN/STOP switch by first moving the
switch to STOP and then back to RUN.
Figure 3.2: RUN/STOP Input Wiring Diagram
Table 3.2: Run Status Table
n
RUN/STOP
SWITCH
o
RUN INPUT
TERMINAL
FX
1S
MPU
STATUS
9
9
RUN
9
RUN
STOP
9
RUN
X2
S/S 0V 24V X0 X1
RUN
➁
Содержание FX1S-10MR-DS
Страница 1: ...HARDWARE MANUAL FX1S SERIES PROGRAMMABLE CONTROLLERS ...
Страница 12: ...Introduction 1 FX1S Series Programmable Controller ...
Страница 22: ...FX1S Series Programmable Controllers ...
Страница 26: ...FX1S Series Programmable Controllers Terminal Layouts 2 2 4 ...
Страница 28: ...FX1S Series Programmable Controllers ...
Страница 38: ...FX1S Series Programmable Controllers ...
Страница 44: ...FX1S Series Programmable Controllers Power Supply 4 4 6 ...
Страница 46: ...FX1S Series Programmable Controllers ...
Страница 52: ...FX1S Series Programmable Controllers ...
Страница 60: ...FX1S Series Programmable Controllers ...
Страница 73: ...FX1S Series Programmable Controllers ...