background image

HEAD OFFICE

: MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310

TELEX : J24532 CABLE MELCO TOKYO

HIMEJI WORKS : 840, CHIYODA CHO, HIMEJI, JAPAN

Specifications are subject to change without notice

2.2.2 Two-pair Wiring

*1 R is the terminating resistor. Connect the terminating resistor (330

) between terminals SDA and SDB, and terminals RDA

and RDB.

*2 The shield of the shielded twisted-pair cable must be connected to ground (100

 or less). When using parallel link, ground

both side. When using no protocol or dedicated protocol, ground one side.

*3 Connect terminal FG to each terminal of the programmable controller main body grounded with resistance of 100

 or less.

However, for the computer link unit of the A series programmable controller, see the manual of the computer link unit. 

2.2.3 One-pair Wiring

*1 R is the terminating resistor. Connect the terminating resistor (110

) between terminals RDA and RDB.

*2 The shield of the shielded twisted-pair cable must be connected to ground (100

 or less). 

*3 Connect terminal FG to each terminal of the programmable controller main body grounded with resistance of 100

 or less.

However, for the computer link unit of the A series programmable controller, see the manual of the computer link unit. 

3. Specifications

3.1 General Specifications

General specifications other than the those-mentioned below are the same as for the FX or FX

2N

 series programmable controller.

Items

Description

Dielectric withstand voltage

500 V AC > 1 min, tested between terminals in batch and case

Insulation Resistance

5 M

 > 500 V DC, tested between terminals in batch and case

G rounding  of resistance 100

 or less

R *1

R *1

S D A

S D B

R D A

R D B

S D A

S D B

R D A

R D B

S G

S D A

S D B

R D

A

R D

B

LIN K

S G

*3

F G

S D A

S D B

R D A

R D B

S G

*3

F G

R *1

R *1

485P C -IF

F X

2N

-485-B D

F X

(0N )

-485A D P

A  series pro gram m able

controllers c om puter link  unit

'

LIN K  S G

*2

G rounding  of resistance 100

 or less

R *1

S D A

S D B

R D A

R D B

S D A

S D B

R D A

R D B

S G

S D A

S D B

R D A

R D B

LIN K

S G

*3

F G

S D A

S D B

R D A

R D B

S G

*3

F G

R *1

LIN K  S G

*2

485P C -IF

F X

2N

-485-B D

F X

(0N )

-485A D P

A  series pro gram m able

controllers c om puter link  unit

3.2 Power Supply Specifications

Note

Use a plug with specifications as shown right.

3.3 Performance Specifications

4. Diagnostics

For diagnostics of computer link, please see FX Communication User’s Manual.

4.1 POWER LED Check

4.2 SD LED and RD LED Check

Check the status of the SD LED and the RD LED.

Items

Description

Power source

5 V DC ± 5%

Current consumption

Max. 260 mA

Items

Description

Transmis-
sion standard

RS232C

Conforming to RS232C

RS485/422

Conforming to RS485 and RS232C

Communication method

Full-duplex communication

transmission 
distance

RS232C

Max. 15 m

RS485/422

Max. 500 m

Supported baud rate

300 to 19,200 bps

Isolation

Photo coupler isolation and transformer isolation 
(between programmable controller and communication signal)

LED Status

Description

Lit

Power source is OK.

Otherwise

Check power supply unit and connection.

Location

LED Status

Check Point

Sending data form computer to 
programmable controller(s).

SD LED is lit

Wiring between computer and 485PC-IF is OK.

SD LED is not lit

Check wiring between computer and 485PC-IF. Check that data has been 
sent from computer.

Sending data form programma-
ble controller to computer.

RD LED is lit

Wiring between programmable controller and 485PC-IF is OK.

RD LED is not lit

Check wiring between programmable controller and 485PC-IF. Check set-
ting of programmable controller(s) for computer link.

D im ensions: m m  (inches)

 

φ

5.5(0.22")

 

φ

2.1(0.08")

9.5 (

0

.37")

Guidelines for the safety of the user and protection of the FX-485PC-IF RS485 Interface Unit

This manual has been written to be used by trained and competent personnel. This is defined by the European directives for
machinery, low voltage and EMC.

If in doubt at any stage during the installation of the FX-485PC-IF always consult a professional electrical engineer who is qualified
and trained to the local and national standards. If in doubt about the operation or use of the FX-485PC-IF please consult the near-
est Mitsubishi Electric distributor. 

Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of
the installation or use of this equipment. 

All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee opera-
tion. Mitsubishi Electric will accept no responsibility for actual use of the product based on these illustrative examples. 

Owing to the very great variety in possible application of this equipment, you must satisfy yourself as to its suitability for your spe-
cific application. 

Отзывы: