7.4.3 Inverter FR-E800-E Communication Settings
Set the parameters of the communication settings with PU (operation panel or parameter unit).
An inverter reset after the setting is required for the parameters of the communication settings.
Item
Parameter
Set Value
Remarks
Operation mode selection
Pr.79
0 (Default value)
*2
Communication startup mode selection
Pr.340
10 (Default value)
*2
Communication EEPROM write selection
Pr.342
0 (Default value)
*2
PLC function operation selection
Pr.414
0 (Default value)
*2 *3
Stop mode selection at communication error
Pr.502
0 (Default value)
*2
Protocol selection
Pr.549
0 (Default value)
NET mode operation command source
selection
Pr.550
5
*2
Operation frequency during communication
error
Pr.779
9999 (Default value)
*2
Ethernet communication network number
Pr.1424
1 to 239
*1
Ethernet communication station number
Pr.1425
1 to 120
*1
Link speed and duplex mode selection
Pr.1426
0 (Default value)
*2
Ethernet function selection 1
Pr.1427
5000 to 5002,5006 to 5008 *1
Ethernet function selection 2
Pr.1428
9999
*2
Ethernet function selection 3
Pr.1429
9999
*2
Ethernet signal loss detection function
selection
Pr.1431
0
*2
Ethernet communication check time interval
Pr.1432
9999
*2
Ethernet IP address 1
Pr.1434
0 to 255
*1
Ethernet IP address 2
Pr.1435
Ethernet IP address 3
Pr.1436
Ethernet IP address 4
Pr.1437
Subnet mask 1
Pr.1438
255 (Default value)
*1 *2
Subnet mask 2
Pr.1439
255 (Default value)
*1 *2
Subnet mask 3
Pr.1440
255 (Default value)
*1 *2
Subnet mask 4
Pr.1441
0 (Default value)
*1 *2
Set the parameters of the communication settings with PU (operation panel or parameter unit).
An inverter reset after the setting is required for the parameters of the communication settings.
Do not change the parameters of the communication settings with the GOT. There are cases where the inverter
cannot communicate with the GOT when the parameters are changed with the GOT.
*1: Settings of the GOT can be changed. When changing the settings, also change the settings of the inverter.
*2: Change the settings depending on the operation environment.
*3: Because the default value of the inverter is "0: disabled", change the value to 1 or 2 when using PLC function.
[Additional Explanation]
When trying to monitor the devices of the PLC such as X and Y at the time when Pr.414 "PLC function operation
selection" is " 0: disabled ", the system alarm "322 Dedicated device is out of range. Confirm device range." is
output.
7.4.4 Settings of Sample Screen
Station Number Switching
In this sample screen, station No. can be switched between 1 and 16 in the default setting. When switching to the
number other than 1 to 16 such as station number 17, please refer to "7.7 C
hanging the Inverter Network No. and
Station No.
" and change the settings according to the system configuration.