BCN-P5999-1305-1c
7.3 RS-485 Connection
This sample screen can also be used for RS-485 connection of GOT2000 and FR-E800 inverter.
The setting example is as below.
System Configuration
*1: For more details on the cable, please refer to "GOT2000 Series Connection Manual (Mitsubishi Products)".
7.3.1 Controller Setting of GOT
(1) Controller Setting
Item
Set Value
Remarks
Manufacturer
MITSUBISHI ELECTRIC
Controller Type
FREQROL 800/E700NE (Batch monitor)
I/F
Standard I/F(RS422/RS485)
(2) Detail Setting
Item
Set Value
Remarks
Transmission Speed (BPS)
115200
Data Bit
8bit
Stop Bit
1bit
Parity
Odd
Retry (Times)
0
Timeout Time (Sec)
3
Host Address
0
Make sure to set the station
number of the inverter connected
to the GOT to [Host address] when
connecting the GOT to the inverter
in RS-485 connection.
Delay Time (ms)
10
Negotiation Time (Sec)
5
Initialization Wait Time (Sec)
3
Automatic Negotiation
Yes
RS485 cable*1
GOT2000
・
GT27**- V(640×480)
・
Interface:
Standard I/F (RS422/485)
Motor
・
FR-E800
・
Interface: PU port