Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be the
cause of Mitsubishi; machine damage or lost profits caused by faults in the Mitsubishi
products; damage, secondary damage, accident compensation caused by special
factors unpredictable by Mitsubishi; damages to products other than Mitsubishi
products; and to other duties.
For safe use
• This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in a
device or system used in purposes related to human life.
• Before using the product for special purposes such as nuclear power, electric power,
aerospace, medicine or passenger movement vehicles, consult with Mitsubishi.
• This product has been manufactured under strict quality control. However when
installing the product where major accidents or losses could occur if the product
fails, install appropriate backup or failsafe functions in the system.
Country/Region Sates office/Tel
U.S.A
Mitsubishi Electric Automation Inc.
500 Corporate Woods Parkway Vernon
Hills, IL 60061
Tel : +1-847-478-2100
Brazil
MELCO-TEC Rep. Com.e Assessoria
Tecnica Ltda.
Av. Rio Branco, 123-15 ,and S/1507,
Rio de Janeiro, RJ CEP 20040-005,
Brazil
Tel : +55-21-221-8343
Germany
Mitsubishi Electric Europe B.V. German
Branch
Gothaer Strasse 8 D-40880 Ratingen,
GERMANY
Tel : +49-2102-486-0
U.K
Mitsubishi Electric Europe B.V. UK
Branch
Travellers Lane, Hatfield, Herts., AL10
8XB, UK
Tel : +44-1707-276100
Italy
Mitsubishi Electric Europe B.V. Italian
Branch
Centro Dir. Colleoni, Pal. Perseo - Ingr.2
Via Paracelso 12, 20041 Agrate B.,
Milano, Italy
Tel:+39-039-60531
Spain
Mitsubishi Electric Europe B.V. Spanish
BranchCarretera de Rubi 76-80
08190 - Sant Cugat del Valles,
Barcelona, Spain
Tel:+34-935-653135
South Africa Circuit Breaker Industries LTD.
Private Bag 2016, Isando 1600,
Johannesburg, South Africa
Tel : +27-11-928-2000
Hong Kong Ryoden Automation Ltd.
10th Floor, Manulife Tower, 169 Electric
Road, North Point, HongKong
Tel : +852-2887-8870
Specifications are subject to change without notice
HEAD OFFICE
:
MITSUBISHI DENKI BLDG MARUNOUTI TOKYO 100-8310
TELEX:J24532 CABLE MELCO TOKYO
HIMEJI WORKS
:
840, CHIYODA CHO, HIMEJI, JAPAN
When exported from Japan, this manual does not require application to the Ministry of Economy,
Trade and Industry for service transaction permission.
Country/Region Sates office/Tel
China
Ryoden International Shanghai Ltd.
3F Block5 Building Automation
Instrumentation Plaza 103 Cao Bao Rd.
Shanghai 200233 China
Tel : +86-21-6475-3228
Taiwan
Setsuyo Enterprise Co., Ltd.
6F., No.105 Wu-Kung 3rd.RD, Wu-Ku
Hsiang, Taipei Hsine, Taiwan
Tel : +886-2-2299-2499
Korea
HAN NEUNG TECHNO CO.,LTD.
1F Dong Seo Game Channel Bldg.,
660-11, Deungchon-dong Kangsec-ku,
Seoul, Korea
Tel : +82-2-3660-9552
Singapore Mitsubishi Electric Asia Pte, Ltd.
307 ALEXANDRA ROAD #05-01/02,
MITSUBISHI ELECTRIC BUILDING
SINGAPORE159943
Tel : +65-473-2480
Thailand
F. A. Tech Co.,Ltd.
898/28,29,30 S.V.City Building,Office
Tower 2,Floor 17-18 Rama 3 Road,
Bangkpongpang, Yannawa,
Bangkok 10120
Tel : +66-2-682-6522
Indonesia
P.T. Autoteknindo SUMBER MAKMUR
Jl. Muara Karang Selatan BlockA Utara
No.1 Kav. No.11 KawasanIndustri/
PergudanganJakarta - Utara 14440
Tel : +62-21-663-0833
India
Messung Systems Put,Ltd.
Electronic Sadan NO:111 Unit No15,
M.I.D.C BHOSARI,PUNE-411026
Tel : +91-20-7128927
Australia
Mitsubishi Electric Australia Pty. Ltd.
348 Victoria Road, PostalBag, No 2,
Rydalmere, N.S.W 2116, Australia
Tel : +61-2-9684-7777
Side
A
Side
B
JAPANESE
ENGLISH
Side
B
●
●
●
●
SAFETY PRECAUTIONS
●
●
●
●
(Read these precautions before using)
Please read this manual carefully and pay special attention to safely in order
to handle this product properly. Also pay careful attention to safely and handle
the module properly.
These precautions apply only to Mitsubishi equipment. Refer to the user’s
manual of the CPU module to use for a description of the PLC system safety
precautions.
These
●
SAFETY PRECAUTIONS
●
classify the safety precautions into two
categories: "DANGER" and "CAUTION".
Depending on circumstances, procedures indicated by
may also be linked to serious results.
In any case, it is important to follow the directions for usage.
Store this manual in a safe place so that you can take it out and read it
whenever necessary. Always forward it to the end user.
[DESIGN PRECAUTIONS]
[INSTALLATION PRECAUTIONS]
[WIRING PRECAUTIONS]
Procedures which may lead to a dangerous condition
and cause death or serious injury if not carried out
properly.
Procedures which may lead to a dangerous condition
and cause superficial to medium injury, or physical
damage only, if not carried out properly.
DANGER
CAUTION
CAUTION
• Configure an interlock circuit in a sequence program so that the system
operates on the safety side using the communication status information
in the event the data link falls into a communication problem.
Otherwise, erroneous output and malfunction may result in accidents.
• Remote input and output can not be switched ON or OFF when a
problem occurs in the remote I/O modules. Therefore build an external
monitoring circuit that will monitor any input signals that could cause a
serious accident.
• Do not have control cables and communication cables bundled with or
placed near by the main circuit and/or power cables. Wire those cables
at least 100mm(3.94 inch) away from the main circuit and/or power
cables. It may cause malfunction due to noise interference.
• Use the module in the status in which any force is not applied on the
module, flat cables dedicated to CC-Link/LT and flat cables for I/O.
If a force is applied, wire breakage or failure may be caused.
DANGER
CAUTION
• Use the module in an environment that meets the general specifications
contained in this manual. Using this module in an environment outside
the range of the general specifications could result in electric shock, fire,
erroneous operation, and damage to or deterioration of the product.
• Do not directly touch the module's conductive parts.Doing so could
cause malfunction or trouble in the module.
CAUTION
• Perform installation and wiring after disconnecting the power supply at
all phases externally. If the power is not disconnected at all phases an
electric shock or product damage may result.
DANGER
[STARTING AND MAINTENANCE PRECAUTIONS]
[DISPOSAL PRECAUTIONS]
[TRANSPORTATION AND MAINTENANCE PRECAUTIONS]
●
●
●
●
Notification of CE marking
●
●
●
●
This notification does not guarantee that an entire mechanical module produced
in accordance with the contents of the notification comply with the following
standards. Compliance to EMC standards of the entire mechanical module
should be checked by the user / manufacturer.
Standards with which this product complies
Type : Programmable Controller (Open Type Equipment) Remote I/O module
Models : Products manufactured from November 1st, 2002.
For more details please contact the local Mitsubishi Electric sales site.
- Notes For compliance to EMC regulation.
It is necessary to install the CL1 series module in a shielded metal control panel.
• Perform correct wiring for the module according to the product’s rated voltage
and terminal arrangement. Connecting to a power supply different from rating
or miss-wiring may cause fire, product failure or malfunction.
• Make sure foreign objects do not get inside the module, such as dirt and wire
chips. It may cause fire, product failure or malfunction.
• Attach a warning label (hazard symbol 417-IEC-5036) concerning the electric
shock to the location.
• Do not touch the terminals when the power is ON. It may cause an electric
shock or malfunction.
• Perform cleaning the module after turning OFF the all external power supply
for sure. Failure to do so may cause failure or malfunction of the modules.
• Do not disassemble or modify the module. Doing so may cause failure,
malfunction, injury, or fire.
• The module case is made of resin; do not drop it or subject it to strong shock.
A module damage may result.
• Make sure to switch all phases of the external power supply OFF before
installing or removing the module to/from the panel. Failure to do so may
cause failure or malfunction of the modules.
CAUTION
DANGER
CAUTION
• When disposing of this product, treat it as industrial waste.
• During transportation avoid any impact as the module is a precision
instrument. Doing so could cause trouble in the module.
• If is necessary to check the operation of module after transportation, in case
of any impact damage.
Electromagnetic Compatibility Standards
(EMC)
Remark
EN61000-6-4:2001
Electromagnetic compatibility
-Generic standards - Emission standard for
Industrial environment
Compliance with all relevant
aspects of the standard. (Radiated
Emissions and Mains Terminal
Voltage Emissions)
EN61131-2:1994 Programmable controllers
/A11: 1996 -Equipment requirements and
tests
/A12: 2000
Compliance with all relevant
aspects of the standard. (RF
Immunity, Fast transients, ESD and
Damped oscillatory wave)
DANGER
CAUTION
1.
Outline of Product
This product is a cable type composite I/O module connected to CC-Link/LT.
This product has one input point (24V DC) and one output point (transistor
output).
2.
Name and Setting of Each Part
Sensor
Connector dedicated
to CC-Link/LT
(sold separately)
Switches
Input/output is ON: Lit
Input/output is OFF: Extinguished
Attach it with
this area facing
upward.
Status indicator LEDs
LED name
PW
L RUN
Operation
Lit while the
power is supplied.
Lit while normal
operation is
executed.
Blue
40 20
10
8
4 2 1
HLD
DIP switch
(Remove the switch cover
when setting the DIP switch.)
DIP switch assignment
Switch cover
(Make sure to attach the
switch cover after setting
the DIP switch.)
Input
operation
indicator
LED
Output
operation
indicator
LED
Flat cable dedicated
to CC-Link/LT
Flat cable for I/O
ON
Black
White
Brown
Name
Description
Status indicator
LED
PW
ON while the power is supplied.
L RUN
ON while normal operation is executed.
I/O operation
indicator LED
ON while the input or output is ON.
Extinguished while the input or output is OFF.
Flat cable
dedicated to CC-
Link/LT
24G
Connector for CC-Link/LT communication line/
module power supply
DB
DA
+24V
Flat cable for I/O
Blue
24G
Black
X0
White
Y0
Brown
+24V
DIP switch
Set the 10's digit of the station No. using "STATION NO. 10",
"STATION NO. 20" and "STATION NO. 40". Set the 1's digit of
the station No. using "STATION NO. 1", "STATION NO. 2",
"STATION NO. 4" and "STATION NO. 8".
Factory default = All bits are OFF.
Make sure to set the station No. in the range from 1 to 64.
X0 input operation
indicator LED
Y0 output operation
indicator LED
0
0
40
20
10
8
4
2
1
10's digit
1's digit
Station
No.
32
ON
OFF
ON
OFF
ON
OFF
OFF
Example: When setting the station No. to "32", set the
DIP switch as follows.
3.
Cautions on Handling
3.1 Handling of flat cable for I/O
The cable length from the module to a sensor shall be within 3m(9'10").
Measure the cable outside the module, and confirm that the driving voltage
for the used sensor is assured.
• Input
• Output
If the diameter of the I/O equipment connection cable is equivalent to the
diameter of the flat cable for I/O of this module, connectors dedicated to
CC-Link/LT can be used for connection.
3.2 Handling of cable
Do not bend the cable within 30mm(1.19") from the module.
Use a crimp-style terminal in a status in which no force is applied on the
cable.
Name
Description
DIP switch
HLD
Holds the output (when an error has occurred).
ON: Holds the output.
OFF: Clears the output.
Crimp-style connection device with
insulator or closed end connection
device
Sensor,
switch, etc.
Crimp-style connection device with
insulator or closed end connection
device
Lamp,
solenoid, etc.
Input
equipment
Connector dedicated to CC-Link/LT
Output
equipment
Wire diameter: AWG18 (34/0.18)
30mm(1.19")
30mm(1.19")
4.
Connection to External Equipment
4.1 External wiring
The input and output terminals of the CL1XY2-DTE1D5S operate while
using the power supplied from the interface.
When connecting a sensor to the input terminal, use a sensor of the PNP
open collector transistor type.
The output wiring is fixed to the sink output.
I/O wiring
4.2 Connection to sensor
• When using a two-wire type sensor
!
When using a three-wire type sensor
Replace * in the figure with the used input No.
Notes:
*1 Bleeder resistor
When connecting a two-wire type sensor or input equipment containing a
parallel resistor, select a sensor or equipment whose leakage current is
1.7mA or less.
If the leakage current is more than 1.7mA, connect a bleeder resistor
obtained in the following calculation formula.
Circuit image
R(k
Ω
) < 1.7(mA) / Leakage current(mA) - 1.7(mA) x 5.6(k
Ω
)
The power capacity W of the bleeder resistor R is as follows:
W = (Input voltage)
2
/R
• Make sure that both the ON and OFF time of the input signal are 1.5ms or
more.
0.5A
0.5A
24G
DA
DB
+24V
DC DC
Isolation
Flat cable
dedicated
to CC-Link/LT
Y0
X0
+24V
24G
Flat cable
for I/O
Internal
circuit
R
R
R
CL1XY2-DTE1D5S
L
Detection
circuit
Sensor (PNP)
Sensor (PNP)
Bleeder
resistor *1
Connected to 24G cable
Connected to 24G cable
X *
+24
X *
+24
Detection
circuit
R
24V DC
Leakage
current
Input impedance
5.6 k
Ω
1.7 mA or less
R: Bleeder resistor
Sensor(PNP)
Unit
Detection
circuit
5.
Specifications
5.1 General specifications
Notes:
*1 The ambient operating/storage temperature satisfies the requirements beyond
the specification in the JIS B3502 and the IEC61131-2.
*2 The module cannot be used in an environment pressurized above the
atmospheric pressure which can be generated around the altitude of 0 m. If the
module is used in such an environment, it may fail.
*3 The module can be used in any environment even outside the control panel as
far as the requirements of the ambient operating temperature, the ambient
operating humidity, etc. are satisfied.
*4 This indicates the section of the power supply to which the equipment is
assumed to be connected between the public electrical power distribution
network and the machinery within premises. Category
II
applies to equipment
for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300V is 2500V.
*5 This index indicates the degree of conductive generating substances in the
environment in which the module is used. The degree of contamination 2
indicates that contamination is caused by generation of only non-conductive
substances.
In this degree, however, temporary conduction may be caused by accidental
condensation.
5.2 Input specifications
Item
Specification
Ambient
working
temperature
0 to 55
°
C (32 to 131
°
F) (*1)
Ambient storage
temperature
-25 to 75
°
C (-13 to 167
°
F) (*1)
Ambient
operating
humidity
Conforming to JIS B3502 and IEC61131-2, Level RH-2
(5 to 95%RH: Dew condensation shall not be considered.)
Ambient storage
humidity
Conforming to JIS B3502 and IEC61131-2, Level RH-2
(5 to 95%RH: Dew condensation shall not be considered.)
Vibration
resistance
Conforming
to JIS
B3502 and
IEC61131-2
When intermittent vibration is present
Number of
times of
sweep
Frequency Acceleration Half amplitude
10 times
in each of
X, Y and Z
directions
(for 80
min)
10 to 57Hz
−
0.075mm
57 to 150Hz 9.8m/s
2
−
When continuous vibration is present
Frequency Acceleration Half amplitude
10 to 57Hz
−
0.035mm
57 to 150Hz 4.9m/s
2
−
Impact
resistance
Conforming to JIS B3502 and IEC61131-2
(147 m/s
2
, 3 times in each of X, Y and Z directions)
Operating
atmosphere
Corrosive gas shall not be present.
Operating
altitude
Conforming to JIS B3502 and IEC61131-2
(2,000m(6561'8") or less)(*2)
Installation
place
Inside control panel (*3)
Over-voltage
category
Conforming to JIS B3502 and IEC61131-2
(Category
ΙΙ
or less)(*4)
Degree of
contamination
Conforming to JIS B3502 and IEC61131-2, Degree of
contamination 2 or less (*5)
Item
Specification
Input method
DC input (using module power supply in common)
EN61131-2, Section3.3.1.2-Type1
Number of input
1 point
Isolation method
Isolation with photocoupler
Rated input voltage
24V DC
Rated input current
Approx. 4 mA
Operating voltage range
Same as module power supply
Max. simultaneous ON
input points
100% (at 24V DC)
ON voltage/ON current
19 V or more/3 mA or more
OFF voltage/OFF current
11 V or less/1.7 mA or less
Input resistance
5.6 k
Ω
Response
time
OFF
→
→
→
→
ON
1.5 ms or less (at 24V DC)
ON
→
→
→
→
OFF
1.5 ms or less (at 24V DC)
Common wiring method
1 point/1 common (Mutually exclusive output)
5.3 Output specifications
5.4 Performance specifications
Item
Specification
Output method
Transistor output
(using module power supply in common) (source)
Number of output
1 point
Isolation method
Isolation with photocoupler
Rated load voltage
24V DC
Operating load voltage
range
Same as module power supply
Max. load current
0.1A/point 0.2 A/1 common
Max. inrush current
0.4A/10 ms
Leakage current at OFF
0.1mA or less/30V DC
Max. voltage drop at ON
1V or less (max.)/0.1A
Response
time
OFF
→
→
→
→
ON
1.0ms or less
ON
→
→
→
→
OFF
1.0ms or less
Surge suppression
Zener diode
Common wiring method
1 point/1 common (Mutually exclusive output)
Internal protection for
outputs
Internal protection circuit none
Please connect the fuse in the connected load
outside.
Item
Specification
Module
power
supply
Voltage
20.4 to 28.8V DC (24V DC -15% to +20%)
Ripple ratio: Within 5%
Current
consumption
40mA (when all points are ON)
(Current consumption contains neither the input
current nor the load current.)
Initial current
70mA
Max. allowable
momentary power
failure period
PS1:1ms
Number of stations
occupied
4-, 8- or 16-point mode: 1 station
Noise durability
500Vp-p
Noise width: 1
µ
s Cycle: 25 to 60 Hz
(by noise simulator)
Withstand voltage
500V AC for 1 min
Isolation resistance
10 M
Ω
or more between primary area (external
DC terminal) and secondary area (internal circuit)
by 500V DC megger
Protection class
IP2X
I/O part connection method
Connection with cable
Module installation method
Can be installed in six directions
Flat cable for I/O (wire
diameter)
AWG18 (34/0.18)
Mass (weight)
0.07 kg (0.15 lbs)
(including 500mm (19.69") flat cable dedicated to
CC-Link/LT and 500mm (19.69") flat cable for I/O)
6.
Outside Dimensions
Unit: mm(inches)
24G X0 Y0
+24V
20(0.79")
65(2.56")
500(19.69")
12(0.48")
500(19.69")
CL1XY2-DTE1D5S
CC-Link/LT Remote I/O Module
Please read this manual thoroughly before starting to use the product and
handle the product properly.
User’s Manual
MODEL
CL1XY2-DTE1D5S
MANUAL Number
JY997D06301A
Date
NOVEMBER 2002