28
- 28 -
HWE10170
GB
1. Error
Code
Heatsink temperature sensor (THHS) fault (Indoor unit)
2. Error
definition and error detection method
When a short or an open of THHS is detected just before or during the inverter operation.
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
1. Error
Code
ACCT sensor circuit fault (Indoor unit)
2. Error
definition and error detection method
When abnormal value is detected by the ACCT detection circuit immediately before the inverter starts
3. Cause, check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
5110
Cause
Check method and remedy
(1)
Loose connector
Check the CNTH on the INV board for proper connection.
(2)
THHS sensor fault
If the problem persists after resuming operation, replace the THHS sensor.
(3)
INV board failure
If no problems were found with items (1) and (2) above and the problem per-
sists after resuming operation, replace the INV board.
5305
Cause
Check method and remedy
(1)
INV board failure
Refer to [8] 3.2.[1].(page 48)
(2)
Fan motor error
Refer to [8] 3.2.[4].(page 49)