26
- 26 -
HWE10170
GB
1. Error
Code
Position detection error at startup (Indoor unit)
2. Error
definition and error detection method
Position error is detected by the hall sensor at inverter startup.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
1. Error
Code
Position detection error during operation (Indoor unit)
2. Error
definition and error detection method
Position error is detected by the hall sensor during operation.
3. Cause, Check method and remedy
Refer to section [8] Troubleshooting, item 3. DC fan motor (fan motor/INV board) for error codes related to the inverter.
(page 47)
4255
Cause
Check method and remedy
(1)
Loose connector
Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2)
Inverter failure or fan motor error
1)
Refer to [8] 3.2.[2].(page 48)
2)
Refer to [8] 3.2.[3].(page 49)
4255
Cause
Check method and remedy
(1)
Loose connector
Check the CNCT1 and CNINV connectors on the
INV board for proper connection.
(2)
Inverter failure or fan motor error
1)
Refer to [8] 3.2.[2].(page 48)
2)
Refer to [8] 3.2.[3].(page 49)
HWE10170.book 26 ページ 2011年7月19日 火曜日 午後2時57分