13
- 13 -
HWE10170
GB
[8] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 50°F (10°C) - 86°F (30°C))
1) Thermistor characteristic graph
(2) Fan motor
Refer to the page on "DC fan motor (fan motor/INV board)."(page 47)
(3) Linear expansion valve
Refer to the page on "LEV". ([8] 4)(page 51)
Normal
Abnormal
4.3k
Ω
- 9.6k
Ω
Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Thermistor R
0
= 15 k
Ω
3%
Multiplier of B = 3480 k
Ω
2%
32°F (0°C) 15k
Ω
50°F (10°C) 9.6k
Ω
68°F (20°C) 6.3k
Ω
77°F (25°C) 5.2k
Ω
86°F (30°C) 4.3k
Ω
104°F (40°C) 3.0k
Ω
(A) Temperature °F
(°C)
(B) Resistance
(k
Ω
)
Rt = 15 exp { 3480(
) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)