6.8 Error Time Output Mode Setting
(1) Definition
This function determines the output mode (clear or hold) from the CPU module to the Q series-compatible output
modules, I/O combined modules, intelligent function modules, and/or interrupt module when a stop error occurs in
the CPU module.
(2) Error time output mode setting
Set the error time output mode in the I/O assignment tab of the PLC parameter dialog box.
1) Make I/O assignment for the target module.
2) Click the
button.
3) On the screen opened, select "Clear" or "Hold". (Default: "Clear")
(3) Precautions
The error time output setting will be enabled when:
• the CPU module is powered off and then on, or
• the CPU module is reset.
Failure to perform either of the operations above after changing the error time output mode setting will result in
"PARAMETER ERROR" (error code: 3000).
Figure 6.23 Error time output mode setting
Detailed setting
3) Select "Clear" or "Hold" for
the error time output mode.
1) Make I/O assignment.
2) Click the Detailed setting button.