Mitsubishi Heavy Industries 100 VNX-W Скачать руководство пользователя страница 1

SAFETY PRECAUTIONS

PSC012D143B

1. HAULAGE AND INSTALLATION

 

(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)

Inverter driven split PAC

100, 125, 140 VNX-W

100, 125, 140 VSX-W

Designed for R32 refrigerant

Check before installation work

● 

Model name and power source

● 

Refrigerant piping length

● 

Piping, wiring and miscellaneous small parts

● 

Indoor unit installation manual

Notabilia as a unit designed for R32

Do not use any refrigerant other than R32.  R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or R407C).

  A cylinder containing R32 has a light blue indication mark on the top.

A unit designed for R32 has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.  The 
processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure.  Accordingly, you are required to arrange dedicated 
R32 tools listed in the table on the right before installing or servicing this unit.

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc.  (A wrong indoor unit, if connected into the system, will impair proper system operation)

When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity 

center  position.  

If not properly balanced, the unit can be thrown off-balance and fall.

a

b

c

d

e

f

g

h

Gauge manifold
Charge hose
Electronic scale for refrigerant charging
Torque wrench
Flare tool
Protrusion control copper pipe gauge
Vacuum pump adapter
Gas leak detector

Dedicated R32 and R410A tools

Deliver the unit as close as possible to the installation site before removing it from the packaging.

When some compelling reason necessitates the unpacking of the unit before it is carried in, use 

nylon slings or protective wood pieces so as not to damage the unit by ropes lifting it.

1) Delivery

2) Portage

The right hand side of the unit as viewed from the front (diffuser side) is heavier.  A person 

carrying the right hand side must take heed of this fact.  A person carrying the left hand side 

must hold with his right hand the handle provided on the front panel of the unit and with his left 

hand the corner column section.

We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full advantage of the functions of the unit and to 

avoid malfunction due to mishandling.

The precautions described below are divided into                   and                 . The matters with possibilities leading to serious consequences such as 

death or serious personal injury due to erroneous handling are listed in the                   and the matters with possibilities leading to personal injury or 
damage of the unit due to erroneous handling including probability leading to serious consequences in some cases are listed in                  . 

These are 

very important precautions for safety. Be sure to observe all of them without fail.

The meaning of "Marks" used here are as shown below.

For 3 phase power source outdoor unit, EN61000-3-2 is not applicable if consent by the utility company or nortification to the utility company is given before usage.

3phase power source unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a house-hold 

appliance it could cause electromagnetic interference.

In case of 125VNX and 140VNX, equipment complying with IEC 61000-3-12.

Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance 

methods of this equipment to the user according to the owner's manual. 

Keep the installation manual together with owner's manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user

Never do it under any circumstance.

Always do it according to the instruction

WARNING

WARNING

CAUTION

CAUTION

CAUTION

INSTALLATION MANUAL FOR OUTDOOR UNIT

This installation manual deals with outdoor units and general installation specifications only.  For indoor units, refer to the respective installation manuals supplied with the units.

When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height 

differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces

Installation must be carried out by the qualified installer.

If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system 

malfunction.

Install the system in full accordance with the instruction manual.

Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.

Use the original accessories and the specified components for installation.

If parts other than those prescribed by us are used, It may cause fall of the unit, water leaks, electric shocks, fire, refrigerant leak, substandard 

performance, control failure and personal injury.

When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant   in the event of leakage 

accordance with ISO5149.

Consult the expert about prevention measures. If the density of refrigerant exceeds the limit in the event of leakage, lack of oxygen can occur, which 

can cause serious accidents.

Ventilate the working area well in the event of refrigerant leakage during installation.

If the refrigerant comes into contact with naked flames, poisonous gas is produced.

After completed installation, check that no refrigerant leaks from the system.

If refrigerant leaks into the room and comes into contact with an oven or other hot surface, poisonous gas is produced.

Hang up the unit at the specified points with ropes which can support the weight in lifting for portage. And to avoid jolting out of alignment, 

be sure to hang up the unit at 4-point support.

An improper manner of portage such as 3-point support can cause death or serious personal injury due to falling of the unit

Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.

 

Ensure the unit is stable when installed, so that it can withstand earthquakes and strong winds.

Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.

 

The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work” and “national 

wiring regulation”, and the system must be connected to the dedicated circuit.

Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire,

Be sure to shut off the power before starting electrical work.

Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment. 

Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.

Unconformable cables can cause electric leak, anomalous heat production or fire. 

Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent 

overloading the terminal blocks.

Loose connections or cable mountings can cause anomalous heat production or fire.

Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.

Incorrect installation may result in overheating and fire. 

Do not perform brazing work in the airtight room

It can cause lack of oxygen.

Use the prescribed pipes, flare nuts and tools for R32 and R410A.

Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.

Tighten the flare nut by using double spanners and torque wrench according to prescribed method. Be sure not to 

tighten the flare nut too much.

Loose flare connection or damage on the flare part by tightening with excess torque can cause burst or refrigerant leaks which 

may result in lack of oxygen. 

Do not open the service valves for liquid line and gas line until completed refrigerant piping work, air tightness test 

and evacuation.

If the compressor is operated in state of opening service valves before completed connection of refrigerant piping work, you 

may incur frost bite or injury from an abrupt refrigerant outflow and air can be sucked into refrigerant circuit, which can cause 

burst or personal injury due to anomalously high pressure in the refrigerant

Only use prescribed optional parts. The installation must be carried out by the qualified installer.

 

If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire. 

Do not perform any change of protective device itself or its setup condition

The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non 

specified component can cause fire or burst.

Be sure to switch off the power supply in the event of installation, inspection or servicing.

If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.

Consult the dealer or an expert regarding removal of the unit.

 

Incorrect installation can cause water leaks, electric shocks or fire. 

Stop the compressor before closing valve and disconnecting refrigerant pipes in case of pump down operation.

If disconnecting refrigerant pipes in state of opening service valves before compressor stopping, you may incur frost bite or 

injury from an abrupt refrigerant outflow and air can be sucked, which can cause burst or personal injury due to anomalously 

high pressure in the refrigerant circuit

Be sure to wear protective goggles and gloves while at work.

This unit is designed specifically for R32.

Using any other refrigerant can cause unit failure and personal injury.

Ensure that no air enters in the refrigerant circuit when the unit is installed and removed. 

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit becomes too high, which can cause burst and 

personal injury. 

Do not run the unit with removed panels or protections

 

Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric 

shocks. 

Be sure to fix up the service panels.

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.

Do not perform any repairs or modifications by yourself. Consult the dealer if the unit requires repair.

If you repair or modify the unit, it can cause water leaks, electric shocks or fire.

Do not process or splice the power cord, or share the socket with other power plugs.

This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.

Do not bundle or wind or process the power cord. Do not deform the power cord by treading it.

This may cause fire or heating.

WARNING

CAUTION

2. REFRIGERANT PIPING WORK

CAUTION

CAUTION

The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.  Where an existing pipe system is 

utilized, different one-way pipe length restrictions should apply depending on its pipe size.  For more information, see “ 6. UTILIZATION OF EXISTING PIPING.”

With the triple pipe connection, the way of use is different when the difference of one-way pipe length after the first branching point is 3m to 10m.  For details, refer 

to the above table and right figure.

When the 50V or 60V model is connected as an indoor unit, always use a 

φ

9.52 liquid pipe for the branch (branching pipe – indoor unit) and a different 

diameter joint supplied with the branching pipe set for connection with the indoor unit (

φ

6.35 on the liquid pipe side).

If a 

φ

6.35 pipe is used for connection with a branching pipe, a refrigerant distribution disorder may occur, causing one of the indoor units to fall short of 

the rated capacity.

A riser pipe must be a part of the main.  A branching pipe set should be installed horizontally at a point as close to an indoor unit as possible.

A branching part must be dressed with a heat-insulation material supplied as an accessory.

For the details of installation work required at and near a branching area, see the installation manual supplied with your branching pipe set.

In the case of a triple type, branching pipe set shown in this table varies depending on the length difference of one way piping after the first branch. 

Please check the table above.

3) Refrigerant pipe wall thickness and material

Select refrigerant pipes of the table shown on the right wall thickness and material as 

specified for each pipe size.

This unit uses R32.  Always use 1/2H pipes having a 1.0mm or thicker wall for 

φ

19.05 or 

larger pipes, because O-type pipes do not meet the pressure resistance requirement.

Pipe diameter 

[mm]

Minimum pipe wall thickness 

[mm]

Pipe material*

6.35

0.8

O-type pipe

9.52

0.8

O-type pipe

12.7

0.8

O-type pipe

15.88

1.0

O-type pipe

22.22

1.0

1/2H-type pipe

25.4

1.0

1/2H-type pipe

28.58

1.0

1/2H-type pipe

NOTE

*Phosphorus deoxidized seamless copper pipe  C1220T, JIS 

3300

Intake

(

service

  space  

)

Intake

Outlet

5) Installation space

Walls surrounding the unit in the four sides are not acceptable.  

There must be a 1-meter or larger space in the above.

Where a danger of short-circuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.

Where piling snow can bury the outdoor unit, provide proper snow guards.

A barrier wall placed in front of the exhaust diffuser must not be higher than the unit.

L

3

L

2

L

4

L

1

Example installation

Size

L1
L2
L3
L4

Open

300
150

5

Open

5

300

5

500

Open

150

5

(mm)

1) Restrictions on unit installation and use

2) Determination of pipe size

 

Determine refrigerant pipe size pursuant to the following guidelines based on the indoor unit specifications.

② 

Notabilia for installation

Intake

Outlet

Fasten with bolts

 (M10-12)

Use a thicker block to

 

anchor deeper.

Use a long block to extend the width.

190

200

580

20

410

20

① 

Anchor bolt fixed position

In installing the unit, fix the unit’s legs with bolts specified on the left.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the left illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.)

Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.

6) Installation

Plug the end of the pipe with tape, or other 
material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Primary side Secondary side

0.5MPa

Hand

Relief valve

Nitrogen 

gas

Select pipes having a wall thickness larger 

than the specified minimum pipe thickness.

Brazing must be performed under a nitrogen gas flow.  

Without nitrogen gas, a large quantity of foreign matters (oxidized film) are 
created, causing a critical failure from capillary tube or expansion valve clogging.

About brazing

Outdoor unit connected

Refrigerant piping (Main pipe L)

Flare

Flare

Flare

Flare

Flare

Flare

Gas pipe

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Liquid pipe

Indoor unit connected
Capacity of indoor unit
Branching pipe set

Branching pipe set

Refrigerant piping (branch pipe L1,L2)
Indoor unit connected
Capacity of indoor unit

Indoor unit connected
Capacity of indoor unit

Refrigerant piping (branch pipe L1,L2,L3)
Indoor unit connected
Capacity of indoor unit
Branching pipe set
Refrigerant piping (branch pipe La)

Branching pipe set (After branch pipe La)
Refrigerant piping (branch pipe L2,L3)

In the case of a single type

In the case of a twin type

In the case of a triple type A

In the case of a triple type B

DIS-WA1G

DIS-WA1G

DIS-WA1G

DIS-TA1G

DIS-WA1G

DIS-WA1G

φ

15.88

φ

9.52

φ

9.52

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

12.7

φ

6.35

φ

12.7

Model 50V

×

2

Model 71V

×

2

Model 50Vx3

Model 50V

×

3

φ

15.88

φ

9.52

φ

9.52

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

15.88

φ

9.52

φ

15.88

φ

9.52

Refrigerant piping (branch pipe L1)

φ

12.7

φ

9.52

φ

15.88

φ

9.52

φ

9.52

φ

15.88

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

12.7

φ

6.35

φ

12.7

φ

9.52

φ

12.7

φ

6.35

φ

12.7

φ

9.52

φ

12.7

φ

6.35

φ

12.7

Model 60V

×

2

Model 100V

Model 125V

Model 140V

< Single type >

< Triple type A > 

In case L1, L2, L3 difference < 3m

< Triple type B > 

In case L1, L2, L3 difference >

= 3m

< Twin type >

Indoor unit

(The unit of which elevation difference from the outdoor unit is the largest.)

Indoor unit

(The unit of which elevation difference from the outdoor unit is the largest.)

L1

L2

L (riser)

Outdoor unit

Indoor unit

h

L

H

H

H

H

Outdoor unit

Indoor unit

L1

L2

L3

L (riser)

Outdoor unit

Indoor unit

Indoor unit

h3

h3

h1

h2

L (riser)

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

L1

L2

L3

La

h1

h2

7) To run the unit for a cooling operation, when the outdoor temperature 

is –5°C or lower.

When the outdoor air temperature is -5°C or lower, provide a snow hood to the outdoor unit on site,

so that strong wind will not blow against the outdoor heat exchanger directly.  Regarding outline of a snow hood, 

consult a dealer.

Be sure to select a suitable installation place in consideration of following conditions.

 A place where it is horizontal, stable and can endure the unit weight and will not allow vibration transmittance of the unit. 

 A place where it can be free from possibility of bothering neighbors due to noise or exhaust air from the unit 

 A place where the unit is not exposed to oil splashes.

 A place where it can be free from danger of flammable gas leakage. 

 A place where drain water can be disposed without any trouble.

 A place where the unit will not be affected by heat radiation from other heat source.

 A place where snow will not accumulate.

 A place where the unit can be kept away 5m or more from TV set and/or radio receiver in order to avoid any radio or TV interference.

 A place where good air circulation can be secured, and enough service space can be secured for maintenance and service of the unit safely.

 A place where the unit will not be affected by electromagnetic waves and/or high-harmonic waves generated by other equipment.

 A place where chemical substances like sulfuric gas, chloric gas, acid and alkali (including ammonia), which can harm the 

unit, will not be generated and not remain. 

 A place where strong wind will not blow against the outlet air blow of the unit. 

 Do not install the unit in places which exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g. snow melting agent), 

exposed to ammonia substance (e.g. organic fertilizer).

3)  Selection of installation location for the outdoor unit

1.Install the outlet air blow side of the 

unit to face a wall of building, or 

provide a fence or a windbreak screen.

3.The unit should be installed on 

the stable and level foundation.  

If the foundation is not level, 

tie down the unit with wires.

Over 500 mm

2.Install the outlet air blow side of

the unit in a position perpendicular

to the direction of wind.

(1) If the unit is installed in the area where the snow will accumulate, following measures are required.

The bottom plate of unit and intake, outlet may be blocked by snow. 

4) Caution about selection of installation location

1.Install the unit on the base so

that the bottom is higher than

snow cover surface.

2.Provide a snow hood to

the outdoor unit on site.

3.Install the unit under eaves

or providen the roof on site.

Since drain water generated by defrost control may freeze, following measures are required.

Don’t execute drain piping work by using a drain elbow and drain grommets (optional parts). [Refer to Drain piping work.]

Recommend setting Defrost Control (SW3-1) and Snow Guard Fan Control (SW3-2). [Refer to Setting SW3-1, SW3-2.]

Attach heater on a base plate on site, if there is possibility to freeze drain water.

In case that the product has a corrective drainage system, the drainage paths should have suitable measure against 

freezing but be sure not to melt the material of drainage paths with heat.

(2) If the unit can be affected by strong wind, following measures are required. 

Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger anomalous stop 

of the unit due to rising of high pressure.

Regarding outline of a snow 

hood, consult a dealer.

Model 100V

Model 125V

Model 140V

Wind direction

Wind direction

Note (1) Install the indoor units so that L + L1 becomes the longest one-way pipe.

Keep the pipe length difference between L1 and (La + L2) or (La + L3) within 10m.

(2) When the outdoor unit is installed at a position higher than the indoor unit by 30m or more, set SW5-2 on the control PCB to ON.

(3) Maximum piping length is limited up to 65m for SRK50 triple type combination, and 85m for FDE50 triple type and FDE60, FDE71 twin type.

Carry out the electrical work for ground lead with care

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line's ground lead. Incorrect grounding can cause unit faults such as 

electric shocks due to short-circuiting. Never connect the grounding wire to a gas pipe because if gas leaks,it could cause explosion or ignition.

Use the circuit breaker for all pole with correct  capacity.

Using the incorrect circuit breaker, it can cause the unit malfunction and fire.

Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations. 

The isolator should be locked in accordanced with EN60204-1

Take care when carrying the unit by hand.

If the unit weights more than 20kg, it must be carried by two or more persons. Do not carry by the plastic straps, always use the carry handle when carrying the 

unit by hand. Use gloves to minimize the risk of cuts by the aluminum fins.

Dispose of any packing materials correctly. 

Any remaining packing materials can cause personal injury as it contains nails and wood. And to avoid danger of suffocation, be sure to keep the plastic 

wrapper away from children and to dispose after tear it up.

 

Pay attention not to damage the drain pan by weld spatter when welding work is done near the indoor unit.

If weld spatter entered into the indoor unit during welding work, it can cause pin-hole in drain pan and result in water leakage. To prevent such damage, keep the indoor unit in its packing or cover it.

Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.

Insufficient insulation can cause condensation, which can lead to moisture damage on the ceiling, floor, furniture and any other valuables.

 

Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can occur, which can cause serious accidents.

Perform installation work properly according to this installation manual. 

Improper installation can cause abnormal vibrations or increased noise generation.

After maintenance, all wiring, wiring ties and the like, should be returned to their original state and wiring route, and the necessary clearance from 

all metal parts should be secured.

Earth leakage breaker must be installed

If the earth leakage breaker is not installed, it can cause fire or electric shocks.

Do not use any materials other than a fuse with the correct rating in the location where fuses are to be used.

Connecting the circuit with copper wire or other metal thread can cause unit failure and fire.

Do not install the unit near the location where leakage of combustible gases can occur.

If leaked gases accumulate around the unit, it can cause fire.

Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can 

accumulate or collect, or where volatile combustible substances are handled.

Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts and etc. And combustible gas can cause fire.

Secure a space for installation, inspection and maintenance specified in the manual.

Insufficient space can result in accident such as personal injury due to falling from the installation place.

When the outdoor unit is installed on a roof or a high place, provide permanent ladders and handrails along the access route and fences and handrails around the outdoor unit.

If safety facilities are not provided, it can cause personal injury due to falling from the installation place.

Do not install nor use the system close to the equipment that generates electromagnetic fields or high frequency harmonics

Equipment such as inverters, standby generators, medical high frequency equipments and telecommunication equipments can affect the system, and cause 

malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.

Do not install the outdoor unit in a location where insects and small animals can inhabit.

Insects and small animals can enter the electric parts and cause damage or fire. Instruct the user to keep the surroundings clean.

Do not use the base flame for outdoor unit which is corroded or damaged due to long periods of operation.

Using an old and damage base flame can cause the unit falling down and cause personal injury. 

Do not install the unit in the locations listed below

Locations where carbon fiber, metal powder or any powder is floating.

Locations where any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur. 

Vehicles and ships

Locations where cosmetic or special sprays are often used.

Locations with direct exposure of oil mist and steam such as kitchen and machine plant.

Locations where any machines which generate high frequency harmonics are used.

Locations with salty atmospheres such as coastlines 

Locations with heavy snow (If installed, be sure to provide base flame and snow hood mentioned in the manual)

Locations where the unit is exposed to chimney smoke

Locations at high altitude (more than 1000m high)

Locations with ammonic atmospheres (e.g. organic fertilizer).

Locations with calcium chloride (e.g. snow melting agent).

Locations where heat radiation from other heat source can affect the unit

Locations without good air circulation.

Locations with any obstacles which can prevent inlet and outlet air of the unit

Locations where short circuit of air can occur (in case of multiple units installation)

Locations where strong air blows against the air outlet of outdoor unit

Locations where something located above the unit could fall.

It can cause remarkable decrease in performance, corrosion and damage of components, malfunction and fire.

Do not install the outdoor unit in the locations listed below.

Locations where discharged hot air or operating sound of the outdoor unit can bother neighborhood.

Locations where outlet air of the outdoor unit blows directly to an animal or plants. The outlet air can affect adversely to the plant etc.

Locations where vibration can be amplified and transmitted due to insufficient strength of structure.

Locations where vibration and operation sound generated by the outdoor unit can affect seriously. (on the wall or at the place near bed room)

Locations where an equipment affected by high harmonics is placed. (TV set or radio receiver is placed within 5m)

Locations where drainage cannot run off safely.

It can affect surrounding environment and cause a claim

Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.

It can cause the damage of the items.

Do not touch any buttons with wet hands

It can cause electric shocks

Do not touch any refrigerant pipes with your hands when the system is in operation.

During operation the refrigerant pipes become extremely hot or extremely cold depending the operating condition, and it can cause burn injury or frost injury.

Do not clean up the unit with water

It can cause electric shocks

Do not operate the outdoor unit with any article placed on it.

You may incur property damage or personal injure from a fall of the article.

Do not step onto the outdoor unit.

You may incur injury from a drop or fall.

Do not touch the suction or aluminum fin on the outdoor unit.

This may cause injury.

202002

Observe the following restrictions on unit installation and use.  Improper installation can result in a compressor failure or performance degradation.

L

L1,L2

L1, L2, L3

 10m

 3m

|L1-L2|

| L1-L2 | , | L2-L3 | , | L3-L1 |

 10m

One way pipe length difference from the second
branch to the indoor unit

 10m

 50m

 

(2)

 15m

 0.5m

h

h1,h2,h3

One-way pipe length between the first branch
from to the second branch

One-way pipe length after the first branch

One-way pipe length from the first branch
to indoor units through the second branch

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX
140VNX, 140VSX
100VNX,125VNX,100VSX,125VSX

Resitrictions

L+L1
L+L2

L

L

One-way pipe length

Main pipe length

140VNX, 140VSX

Triple type A

– : Not applicable combination

Installation type

Twin type

Single type

Dimensional
restrictions

Model for outdoor units

L+L1+L2+L3

 30m

 5m

140VNX, 140VSX

 27m

Elevation difference between indoor units

H

H

H

Elevation difference between indoor and outdoor units

Outdoor unit is positioned lower,

Outdoor unit is positioned higher,

One-way pipe length difference from the first branch
to the indoor unit

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX

140VNX, 140VSX

3m 

 100m (3)

 100m (3)

Heavy

Pad

Wooden  pallet

L

L1 (1) 

L1-(La+L2),L1-(La+L3)  (1)

| L2-L3 |

h1,h2,h3

La

Triple type B

L+L1+L2+L3

H

La+L2, La+L3 (1) 

SAFETY PRECAUTIONS

PSC012D143B

1. HAULAGE AND INSTALLATION

 

(Take particular care in carrying in or moving the unit, and always perform such an operation with two or more persons.)

Inverter driven split PAC

100, 125, 140 VNX-W

100, 125, 140 VSX-W

Designed for R32 refrigerant

Check before installation work

● 

Model name and power source

● 

Refrigerant piping length

● 

Piping, wiring and miscellaneous small parts

● 

Indoor unit installation manual

Notabilia as a unit designed for R32

Do not use any refrigerant other than R32.  R32 will rise to pressure about 1.6 times higher than that of a conventional refrigerant (R22 or R407C).

  A cylinder containing R32 has a light blue indication mark on the top.

A unit designed for R32 has adopted a different size indoor unit operation valve charge port and a different size check joint provided in the unit to prevent the charging of a wrong refrigerant by mistake.  The 
processed dimension of the flared part of a refrigerant pipe and a flare nut's parallel side measurement have also been altered to raise strength against pressure.  Accordingly, you are required to arrange dedicated 
R32 tools listed in the table on the right before installing or servicing this unit.

All indoor units must be models designed exclusively for R32. Check connectable indoor unit models in a catalog, etc.  (A wrong indoor unit, if connected into the system, will impair proper system operation)

When a unit is hoisted with slings for haulage, take into consideration the offset of its gravity 

center  position.  

If not properly balanced, the unit can be thrown off-balance and fall.

a

b

c

d

e

f

g

h

Gauge manifold
Charge hose
Electronic scale for refrigerant charging
Torque wrench
Flare tool
Protrusion control copper pipe gauge
Vacuum pump adapter
Gas leak detector

Dedicated R32 and R410A tools

Deliver the unit as close as possible to the installation site before removing it from the packaging.

When some compelling reason necessitates the unpacking of the unit before it is carried in, use 

nylon slings or protective wood pieces so as not to damage the unit by ropes lifting it.

1) Delivery

2) Portage

The right hand side of the unit as viewed from the front (diffuser side) is heavier.  A person 

carrying the right hand side must take heed of this fact.  A person carrying the left hand side 

must hold with his right hand the handle provided on the front panel of the unit and with his left 

hand the corner column section.

We recommend you to read this “SAFETY PRECAUTIONS” carefully before the installation work in order to gain full advantage of the functions of the unit and to 

avoid malfunction due to mishandling.

The precautions described below are divided into                   and                 . The matters with possibilities leading to serious consequences such as 

death or serious personal injury due to erroneous handling are listed in the                   and the matters with possibilities leading to personal injury or 
damage of the unit due to erroneous handling including probability leading to serious consequences in some cases are listed in                  . 

These are 

very important precautions for safety. Be sure to observe all of them without fail.

The meaning of "Marks" used here are as shown below.

For 3 phase power source outdoor unit, EN61000-3-2 is not applicable if consent by the utility company or nortification to the utility company is given before usage.

3phase power source unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a house-hold 

appliance it could cause electromagnetic interference.

In case of 125VNX and 140VNX, equipment complying with IEC 61000-3-12.

Be sure to confirm no anomaly on the equipment by commissioning after completed installation and explain the operating methods as well as the maintenance 

methods of this equipment to the user according to the owner's manual. 

Keep the installation manual together with owner's manual at a place where any user can read at any time. Moreover if necessary, ask to hand them to a new user

Never do it under any circumstance.

Always do it according to the instruction

WARNING

WARNING

CAUTION

CAUTION

CAUTION

INSTALLATION MANUAL FOR OUTDOOR UNIT

This installation manual deals with outdoor units and general installation specifications only.  For indoor units, refer to the respective installation manuals supplied with the units.

When install the unit, be sure to check whether the selection of installation place, power supply specifications, usage limitation (piping length, height 

differences between indoor and outdoor units, power supply voltage and etc.) and installation spaces

Installation must be carried out by the qualified installer.

If you install the system by yourself, it may cause serious trouble such as water leaks, electric shocks, fire and personal injury, as a result of a system 

malfunction.

Install the system in full accordance with the instruction manual.

Incorrect installation may cause bursts, personal injury, water leaks, electric shocks and fire.

Use the original accessories and the specified components for installation.

If parts other than those prescribed by us are used, It may cause fall of the unit, water leaks, electric shocks, fire, refrigerant leak, substandard 

performance, control failure and personal injury.

When installing in small rooms, take prevention measures not to exceed the density limit of refrigerant   in the event of leakage 

accordance with ISO5149.

Consult the expert about prevention measures. If the density of refrigerant exceeds the limit in the event of leakage, lack of oxygen can occur, which 

can cause serious accidents.

Ventilate the working area well in the event of refrigerant leakage during installation.

If the refrigerant comes into contact with naked flames, poisonous gas is produced.

After completed installation, check that no refrigerant leaks from the system.

If refrigerant leaks into the room and comes into contact with an oven or other hot surface, poisonous gas is produced.

Hang up the unit at the specified points with ropes which can support the weight in lifting for portage. And to avoid jolting out of alignment, 

be sure to hang up the unit at 4-point support.

An improper manner of portage such as 3-point support can cause death or serious personal injury due to falling of the unit

Install the unit in a location with good support.

Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.

 

Ensure the unit is stable when installed, so that it can withstand earthquakes and strong winds.

Unsuitable installation locations can cause the unit to fall and cause material damage and personal injury.

 

The electrical installation must be carried out by the qualified electrician in accordance with “the norm for electrical work” and “national 

wiring regulation”, and the system must be connected to the dedicated circuit.

Power supply with insufficient capacity and incorrect function done by improper work can cause electric shocks and fire,

Be sure to shut off the power before starting electrical work.

Failure to shut off the power can cause electric shocks, unit failure or incorrect function of equipment. 

Be sure to use the cables conformed to safety standard and cable ampacity for power distribution work.

Unconformable cables can cause electric leak, anomalous heat production or fire. 

Use the prescribed cables for electrical connection, tighten the cables securely in terminal block and relieve the cables correctly to prevent 

overloading the terminal blocks.

Loose connections or cable mountings can cause anomalous heat production or fire.

Arrange the wiring in the control box so that it cannot be pushed up further into the box. Install the service panel correctly.

Incorrect installation may result in overheating and fire. 

Do not perform brazing work in the airtight room

It can cause lack of oxygen.

Use the prescribed pipes, flare nuts and tools for R32 and R410A.

Using existing parts (for R22 or R407C) can cause the unit failure and serious accidents due to burst of the refrigerant circuit.

Tighten the flare nut by using double spanners and torque wrench according to prescribed method. Be sure not to 

tighten the flare nut too much.

Loose flare connection or damage on the flare part by tightening with excess torque can cause burst or refrigerant leaks which 

may result in lack of oxygen. 

Do not open the service valves for liquid line and gas line until completed refrigerant piping work, air tightness test 

and evacuation.

If the compressor is operated in state of opening service valves before completed connection of refrigerant piping work, you 

may incur frost bite or injury from an abrupt refrigerant outflow and air can be sucked into refrigerant circuit, which can cause 

burst or personal injury due to anomalously high pressure in the refrigerant

Only use prescribed optional parts. The installation must be carried out by the qualified installer.

 

If you install the system by yourself, it can cause serious trouble such as water leaks, electric shocks, fire. 

Do not perform any change of protective device itself or its setup condition

The forced operation by short-circuiting protective device of pressure switch and temperature controller or the use of non 

specified component can cause fire or burst.

Be sure to switch off the power supply in the event of installation, inspection or servicing.

If the power supply is not shut off, there is a risk of electric shocks, unit failure or personal injury due to the unexpected start of fan.

Consult the dealer or an expert regarding removal of the unit.

 

Incorrect installation can cause water leaks, electric shocks or fire. 

Stop the compressor before closing valve and disconnecting refrigerant pipes in case of pump down operation.

If disconnecting refrigerant pipes in state of opening service valves before compressor stopping, you may incur frost bite or 

injury from an abrupt refrigerant outflow and air can be sucked, which can cause burst or personal injury due to anomalously 

high pressure in the refrigerant circuit

Be sure to wear protective goggles and gloves while at work.

This unit is designed specifically for R32.

Using any other refrigerant can cause unit failure and personal injury.

Ensure that no air enters in the refrigerant circuit when the unit is installed and removed. 

If air enters in the refrigerant circuit, the pressure in the refrigerant circuit becomes too high, which can cause burst and 

personal injury. 

Do not run the unit with removed panels or protections

 

Touching rotating equipments, hot surfaces or high voltage parts can cause personal injury due to entrapment, burn or electric 

shocks. 

Be sure to fix up the service panels.

Incorrect fixing can cause electric shocks or fire due to intrusion of dust or water.

Do not perform any repairs or modifications by yourself. Consult the dealer if the unit requires repair.

If you repair or modify the unit, it can cause water leaks, electric shocks or fire.

Do not process or splice the power cord, or share the socket with other power plugs.

This may cause fire or electric shock due to defecting contact, defecting insulation and over-current etc.

Do not bundle or wind or process the power cord. Do not deform the power cord by treading it.

This may cause fire or heating.

WARNING

CAUTION

2. REFRIGERANT PIPING WORK

CAUTION

CAUTION

The use restrictions appearing in the table above are applicable to the standard pipe size combinations shown in the table below.  Where an existing pipe system is 

utilized, different one-way pipe length restrictions should apply depending on its pipe size.  For more information, see “ 6. UTILIZATION OF EXISTING PIPING.”

With the triple pipe connection, the way of use is different when the difference of one-way pipe length after the first branching point is 3m to 10m.  For details, refer 

to the above table and right figure.

When the 50V or 60V model is connected as an indoor unit, always use a 

φ

9.52 liquid pipe for the branch (branching pipe – indoor unit) and a different 

diameter joint supplied with the branching pipe set for connection with the indoor unit (

φ

6.35 on the liquid pipe side).

If a 

φ

6.35 pipe is used for connection with a branching pipe, a refrigerant distribution disorder may occur, causing one of the indoor units to fall short of 

the rated capacity.

A riser pipe must be a part of the main.  A branching pipe set should be installed horizontally at a point as close to an indoor unit as possible.

A branching part must be dressed with a heat-insulation material supplied as an accessory.

For the details of installation work required at and near a branching area, see the installation manual supplied with your branching pipe set.

In the case of a triple type, branching pipe set shown in this table varies depending on the length difference of one way piping after the first branch. 

Please check the table above.

3) Refrigerant pipe wall thickness and material

Select refrigerant pipes of the table shown on the right wall thickness and material as 

specified for each pipe size.

This unit uses R32.  Always use 1/2H pipes having a 1.0mm or thicker wall for 

φ

19.05 or 

larger pipes, because O-type pipes do not meet the pressure resistance requirement.

Pipe diameter 

[mm]

Minimum pipe wall thickness 

[mm]

Pipe material*

6.35

0.8

O-type pipe

9.52

0.8

O-type pipe

12.7

0.8

O-type pipe

15.88

1.0

O-type pipe

22.22

1.0

1/2H-type pipe

25.4

1.0

1/2H-type pipe

28.58

1.0

1/2H-type pipe

NOTE

*Phosphorus deoxidized seamless copper pipe  C1220T, JIS 

3300

Intake

(

service

  space  

)

Intake

Outlet

5) Installation space

Walls surrounding the unit in the four sides are not acceptable.  

There must be a 1-meter or larger space in the above.

Where a danger of short-circuiting exists, install guide louvers.

When more than one unit are installed, provide sufficient intake space consciously so that short-circuiting may not occur.

Where piling snow can bury the outdoor unit, provide proper snow guards.

A barrier wall placed in front of the exhaust diffuser must not be higher than the unit.

L

3

L

2

L

4

L

1

Example installation

Size

L1
L2
L3
L4

Open

300
150

5

Open

5

300

5

500

Open

150

5

(mm)

1) Restrictions on unit installation and use

2) Determination of pipe size

 

Determine refrigerant pipe size pursuant to the following guidelines based on the indoor unit specifications.

② 

Notabilia for installation

Intake

Outlet

Fasten with bolts

 (M10-12)

Use a thicker block to

 

anchor deeper.

Use a long block to extend the width.

190

200

580

20

410

20

① 

Anchor bolt fixed position

In installing the unit, fix the unit’s legs with bolts specified on the left.

The protrusion of an anchor bolt on the front side must be kept within 15 mm.

Securely install the unit so that it does not fall over during earthquakes or strong winds, etc.

Refer to the left illustrations for information regarding concrete foundations.

Install the unit in a level area. (With a gradient of 5 mm or less.)

Improper installation can result in a compressor failure, broken piping within the unit and abnormal noise generation.

6) Installation

Plug the end of the pipe with tape, or other 
material, and fill the pipe with nitrogen gas.

Only use nitrogen gas (N

2

)

Taping

N

2

Nitrogen

Brazing

Station valve

Primary side Secondary side

0.5MPa

Hand

Relief valve

Nitrogen 

gas

Select pipes having a wall thickness larger 

than the specified minimum pipe thickness.

Brazing must be performed under a nitrogen gas flow.  

Without nitrogen gas, a large quantity of foreign matters (oxidized film) are 
created, causing a critical failure from capillary tube or expansion valve clogging.

About brazing

Outdoor unit connected

Refrigerant piping (Main pipe L)

Flare

Flare

Flare

Flare

Flare

Flare

Gas pipe

Liquid pipe

Gas pipe

Liquid pipe

Gas pipe

Liquid pipe

Indoor unit connected
Capacity of indoor unit
Branching pipe set

Branching pipe set

Refrigerant piping (branch pipe L1,L2)
Indoor unit connected
Capacity of indoor unit

Indoor unit connected
Capacity of indoor unit

Refrigerant piping (branch pipe L1,L2,L3)
Indoor unit connected
Capacity of indoor unit
Branching pipe set
Refrigerant piping (branch pipe La)

Branching pipe set (After branch pipe La)
Refrigerant piping (branch pipe L2,L3)

In the case of a single type

In the case of a twin type

In the case of a triple type A

In the case of a triple type B

DIS-WA1G

DIS-WA1G

DIS-WA1G

DIS-TA1G

DIS-WA1G

DIS-WA1G

φ

15.88

φ

9.52

φ

9.52

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

12.7

φ

6.35

φ

12.7

Model 50V

×

2

Model 71V

×

2

Model 50Vx3

Model 50V

×

3

φ

15.88

φ

9.52

φ

9.52

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

15.88

φ

9.52

φ

15.88

φ

9.52

Refrigerant piping (branch pipe L1)

φ

12.7

φ

9.52

φ

15.88

φ

9.52

φ

9.52

φ

15.88

φ

9.52

φ

15.88

φ

15.88

φ

9.52

φ

12.7

φ

6.35

φ

12.7

φ

9.52

φ

12.7

φ

6.35

φ

12.7

φ

9.52

φ

12.7

φ

6.35

φ

12.7

Model 60V

×

2

Model 100V

Model 125V

Model 140V

< Single type >

< Triple type A > 

In case L1, L2, L3 difference < 3m

< Triple type B > 

In case L1, L2, L3 difference >

= 3m

< Twin type >

Indoor unit

(The unit of which elevation difference from the outdoor unit is the largest.)

Indoor unit

(The unit of which elevation difference from the outdoor unit is the largest.)

L1

L2

L (riser)

Outdoor unit

Indoor unit

h

L

H

H

H

H

Outdoor unit

Indoor unit

L1

L2

L3

L (riser)

Outdoor unit

Indoor unit

Indoor unit

h3

h3

h1

h2

L (riser)

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

L1

L2

L3

La

h1

h2

7) To run the unit for a cooling operation, when the outdoor temperature 

is –5°C or lower.

When the outdoor air temperature is -5°C or lower, provide a snow hood to the outdoor unit on site,

so that strong wind will not blow against the outdoor heat exchanger directly.  Regarding outline of a snow hood, 

consult a dealer.

Be sure to select a suitable installation place in consideration of following conditions.

 A place where it is horizontal, stable and can endure the unit weight and will not allow vibration transmittance of the unit. 

 A place where it can be free from possibility of bothering neighbors due to noise or exhaust air from the unit 

 A place where the unit is not exposed to oil splashes.

 A place where it can be free from danger of flammable gas leakage. 

 A place where drain water can be disposed without any trouble.

 A place where the unit will not be affected by heat radiation from other heat source.

 A place where snow will not accumulate.

 A place where the unit can be kept away 5m or more from TV set and/or radio receiver in order to avoid any radio or TV interference.

 A place where good air circulation can be secured, and enough service space can be secured for maintenance and service of the unit safely.

 A place where the unit will not be affected by electromagnetic waves and/or high-harmonic waves generated by other equipment.

 A place where chemical substances like sulfuric gas, chloric gas, acid and alkali (including ammonia), which can harm the 

unit, will not be generated and not remain. 

 A place where strong wind will not blow against the outlet air blow of the unit. 

 Do not install the unit in places which exposed to sea breeze (e.g. coastal area) or calcium chloride (e.g. snow melting agent), 

exposed to ammonia substance (e.g. organic fertilizer).

3)  Selection of installation location for the outdoor unit

1.Install the outlet air blow side of the 

unit to face a wall of building, or 

provide a fence or a windbreak screen.

3.The unit should be installed on 

the stable and level foundation.  

If the foundation is not level, 

tie down the unit with wires.

Over 500 mm

2.Install the outlet air blow side of

the unit in a position perpendicular

to the direction of wind.

(1) If the unit is installed in the area where the snow will accumulate, following measures are required.

The bottom plate of unit and intake, outlet may be blocked by snow. 

4) Caution about selection of installation location

1.Install the unit on the base so

that the bottom is higher than

snow cover surface.

2.Provide a snow hood to

the outdoor unit on site.

3.Install the unit under eaves

or providen the roof on site.

Since drain water generated by defrost control may freeze, following measures are required.

Don’t execute drain piping work by using a drain elbow and drain grommets (optional parts). [Refer to Drain piping work.]

Recommend setting Defrost Control (SW3-1) and Snow Guard Fan Control (SW3-2). [Refer to Setting SW3-1, SW3-2.]

Attach heater on a base plate on site, if there is possibility to freeze drain water.

In case that the product has a corrective drainage system, the drainage paths should have suitable measure against 

freezing but be sure not to melt the material of drainage paths with heat.

(2) If the unit can be affected by strong wind, following measures are required. 

Strong wind can cause damage of fan (fan motor), or can cause performance degradation, or can trigger anomalous stop 

of the unit due to rising of high pressure.

Regarding outline of a snow 

hood, consult a dealer.

Model 100V

Model 125V

Model 140V

Wind direction

Wind direction

Note (1) Install the indoor units so that L + L1 becomes the longest one-way pipe.

Keep the pipe length difference between L1 and (La + L2) or (La + L3) within 10m.

(2) When the outdoor unit is installed at a position higher than the indoor unit by 30m or more, set SW5-2 on the control PCB to ON.

(3) Maximum piping length is limited up to 65m for SRK50 triple type combination, and 85m for FDE50 triple type and FDE60, FDE71 twin type.

Carry out the electrical work for ground lead with care

Do not connect the ground lead to the gas line, water line, lightning conductor or telephone line's ground lead. Incorrect grounding can cause unit faults such as 

electric shocks due to short-circuiting. Never connect the grounding wire to a gas pipe because if gas leaks,it could cause explosion or ignition.

Use the circuit breaker for all pole with correct  capacity.

Using the incorrect circuit breaker, it can cause the unit malfunction and fire.

Install isolator or disconnect switch on the power supply wiring in accordance with the local codes and regulations. 

The isolator should be locked in accordanced with EN60204-1

Take care when carrying the unit by hand.

If the unit weights more than 20kg, it must be carried by two or more persons. Do not carry by the plastic straps, always use the carry handle when carrying the 

unit by hand. Use gloves to minimize the risk of cuts by the aluminum fins.

Dispose of any packing materials correctly. 

Any remaining packing materials can cause personal injury as it contains nails and wood. And to avoid danger of suffocation, be sure to keep the plastic 

wrapper away from children and to dispose after tear it up.

 

Pay attention not to damage the drain pan by weld spatter when welding work is done near the indoor unit.

If weld spatter entered into the indoor unit during welding work, it can cause pin-hole in drain pan and result in water leakage. To prevent such damage, keep the indoor unit in its packing or cover it.

Be sure to insulate the refrigerant pipes so as not to condense the ambient air moisture on them.

Insufficient insulation can cause condensation, which can lead to moisture damage on the ceiling, floor, furniture and any other valuables.

 

Be sure to perform air tightness test by pressurizing with nitrogen gas after completed refrigerant piping work.

If the density of refrigerant exceeds the limit in the event of refrigerant leakage in the small room, lack of oxygen can occur, which can cause serious accidents.

Perform installation work properly according to this installation manual. 

Improper installation can cause abnormal vibrations or increased noise generation.

After maintenance, all wiring, wiring ties and the like, should be returned to their original state and wiring route, and the necessary clearance from 

all metal parts should be secured.

Earth leakage breaker must be installed

If the earth leakage breaker is not installed, it can cause fire or electric shocks.

Do not use any materials other than a fuse with the correct rating in the location where fuses are to be used.

Connecting the circuit with copper wire or other metal thread can cause unit failure and fire.

Do not install the unit near the location where leakage of combustible gases can occur.

If leaked gases accumulate around the unit, it can cause fire.

Do not install the unit where corrosive gas (such as sulfurous acid gas etc.) or combustible gas (such as thinner and petroleum gases) can 

accumulate or collect, or where volatile combustible substances are handled.

Corrosive gas can cause corrosion of heat exchanger, breakage of plastic parts and etc. And combustible gas can cause fire.

Secure a space for installation, inspection and maintenance specified in the manual.

Insufficient space can result in accident such as personal injury due to falling from the installation place.

When the outdoor unit is installed on a roof or a high place, provide permanent ladders and handrails along the access route and fences and handrails around the outdoor unit.

If safety facilities are not provided, it can cause personal injury due to falling from the installation place.

Do not install nor use the system close to the equipment that generates electromagnetic fields or high frequency harmonics

Equipment such as inverters, standby generators, medical high frequency equipments and telecommunication equipments can affect the system, and cause 

malfunctions and breakdowns. The system can also affect medical equipment and telecommunication equipment, and obstruct its function or cause jamming.

Do not install the outdoor unit in a location where insects and small animals can inhabit.

Insects and small animals can enter the electric parts and cause damage or fire. Instruct the user to keep the surroundings clean.

Do not use the base flame for outdoor unit which is corroded or damaged due to long periods of operation.

Using an old and damage base flame can cause the unit falling down and cause personal injury. 

Do not install the unit in the locations listed below

Locations where carbon fiber, metal powder or any powder is floating.

Locations where any substances that can affect the unit such as sulphide gas, chloride gas, acid and alkaline can occur. 

Vehicles and ships

Locations where cosmetic or special sprays are often used.

Locations with direct exposure of oil mist and steam such as kitchen and machine plant.

Locations where any machines which generate high frequency harmonics are used.

Locations with salty atmospheres such as coastlines 

Locations with heavy snow (If installed, be sure to provide base flame and snow hood mentioned in the manual)

Locations where the unit is exposed to chimney smoke

Locations at high altitude (more than 1000m high)

Locations with ammonic atmospheres (e.g. organic fertilizer).

Locations with calcium chloride (e.g. snow melting agent).

Locations where heat radiation from other heat source can affect the unit

Locations without good air circulation.

Locations with any obstacles which can prevent inlet and outlet air of the unit

Locations where short circuit of air can occur (in case of multiple units installation)

Locations where strong air blows against the air outlet of outdoor unit

Locations where something located above the unit could fall.

It can cause remarkable decrease in performance, corrosion and damage of components, malfunction and fire.

Do not install the outdoor unit in the locations listed below.

Locations where discharged hot air or operating sound of the outdoor unit can bother neighborhood.

Locations where outlet air of the outdoor unit blows directly to an animal or plants. The outlet air can affect adversely to the plant etc.

Locations where vibration can be amplified and transmitted due to insufficient strength of structure.

Locations where vibration and operation sound generated by the outdoor unit can affect seriously. (on the wall or at the place near bed room)

Locations where an equipment affected by high harmonics is placed. (TV set or radio receiver is placed within 5m)

Locations where drainage cannot run off safely.

It can affect surrounding environment and cause a claim

Do not use the unit for special purposes such as storing foods, cooling precision instruments and preservation of animals, plants or art.

It can cause the damage of the items.

Do not touch any buttons with wet hands

It can cause electric shocks

Do not touch any refrigerant pipes with your hands when the system is in operation.

During operation the refrigerant pipes become extremely hot or extremely cold depending the operating condition, and it can cause burn injury or frost injury.

Do not clean up the unit with water

It can cause electric shocks

Do not operate the outdoor unit with any article placed on it.

You may incur property damage or personal injure from a fall of the article.

Do not step onto the outdoor unit.

You may incur injury from a drop or fall.

Do not touch the suction or aluminum fin on the outdoor unit.

This may cause injury.

202002

Observe the following restrictions on unit installation and use.  Improper installation can result in a compressor failure or performance degradation.

L

L1,L2

L1, L2, L3

 10m

 3m

|L1-L2|

| L1-L2 | , | L2-L3 | , | L3-L1 |

 10m

One way pipe length difference from the second
branch to the indoor unit

 10m

 50m

 

(2)

 15m

 0.5m

h

h1,h2,h3

One-way pipe length between the first branch
from to the second branch

One-way pipe length after the first branch

One-way pipe length from the first branch
to indoor units through the second branch

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX
140VNX, 140VSX
100VNX,125VNX,100VSX,125VSX

Resitrictions

L+L1
L+L2

L

L

One-way pipe length

Main pipe length

140VNX, 140VSX

Triple type A

– : Not applicable combination

Installation type

Twin type

Single type

Dimensional
restrictions

Model for outdoor units

L+L1+L2+L3

 30m

 5m

140VNX, 140VSX

 27m

Elevation difference between indoor units

H

H

H

Elevation difference between indoor and outdoor units

Outdoor unit is positioned lower,

Outdoor unit is positioned higher,

One-way pipe length difference from the first branch
to the indoor unit

140VNX, 140VSX

100VNX,125VNX,100VSX,125VSX

140VNX, 140VSX

3m 

 100m (3)

 100m (3)

Heavy

Pad

Wooden  pallet

L

L1 (1) 

L1-(La+L2),L1-(La+L3)  (1)

| L2-L3 |

h1,h2,h3

La

Triple type B

L+L1+L2+L3

H

La+L2, La+L3 (1) 

Отзывы: