2. Installation and Wiring
2.3 Installation of the inverter and enclosure design
1
2
3
4
5
6
7
8
9
10
When installing multiple inverters, fully take measures to prevent the surrounding air temperature of the inverter from being
higher than the permissible value by providing ventilation or increasing the enclosure size.
Arrangement of the ventilation fan and inverter
Heat generated in the inverter is blown up from the bottom of the unit as warm air by the cooling fan. When installing a
ventilation fan for that heat, determine the place of ventilation fan installation after fully considering an air flow. (Air passes
through areas of low resistance. Make an airway and airflow plates to expose the inverter to cool air.)
2.3.4
Protruding the heat sink through a panel
When encasing the inverter to an enclosure (inverter capacity: 3.7 kW or lower), protrude the heat sink of the inverter using the
panel through attachment (FR-E7CN). Doing so can greatly reduce the heat generated in the enclosure. For a panel cut
dimension drawing and an installation procedure of the FR-E7CN to the inverter, refer to the Instruction Manual of the FR-
E7CN.
When installing the inverter in a compact enclosure, etc., this installation method is recommended.
Arrangement of multiple inverters
Arrangement of the ventilation fan and inverter
Guide
Guide
Enclosure
Enclosure
Guide
(a) Horizontal arrangement
(b) Vertical arrangement
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
Inverter
<Good example>
<Bad example>