![Mitsubishi Electric RD77MS16 Скачать руководство пользователя страница 156](http://html.mh-extra.com/html/mitsubishi-electric/rd77ms16/rd77ms16_user-manual_1811857156.webp)
154
4 HIGH-LEVEL POSITIONING CONTROL
4.3 Setting the Block Start Data
Repeated start (FOR condition)
In a "repeated start (FOR condition)", the data between the "block start data" in which "5: FOR condition" is set in "[Da.13]
Special start instruction" and the "block start data" in which "6: NEXT start" is set in "[Da.13] Special start instruction" is
repeatedly executed until the establishment of the conditions set in the "condition data".
Conditional judgment is carried out as soon as switching to the point of "6: NEXT start" (before positioning of NEXT start
point).
(The "condition data" designation is set in "[Da.14] Parameter" of the "block start data" in which "5: FOR condition" is set in
"[Da.13] Special start instruction".)
The control examples are shown when the "block start data" and "positioning data" are set as shown in the setting examples.
Setting examples
■
Block start data setting example
The "condition data Nos." have been set in "[Da.14] Parameter".
■
Positioning data setting example
Control examples
The following shows the control executed when the "block start data" of the 1st point of axis 1 is set as shown in the setting
examples and started.
1.
Execute the axis 1 "positioning data No.1, 2, 3, 10, and 11".
2.
Carry out the conditional judgment set in axis 1 "condition data No.5".
*1
Conditions not established
Execute "Positioning data No.50, 51". Go to the above 1.
Conditions established
Execute "Positioning data No.50, 51" and complete the positioning.
*1
Conditional judgment is carried out as soon as switching to NEXT start point (before positioning of NEXT start point).
Axis 1 block start data
[Da.11] Shape
[Da.12] Start data No.
[Da.13] Special start
instruction
[Da.14] Parameter
1st point
1: Continue
1
5: FOR condition
5
2nd point
1: Continue
10
0: Block start
3rd point
0: End
50
6: NEXT start
Axis 1 positioning data
No.
[Da.1] Operation pattern
1
01: Continuous positioning
control
2
01: Continuous positioning
control
3
00: Positioning complete
10
11: Continuous path control
11
00: Positioning complete
50
01: Continuous positioning
control
51
00: Positioning complete
Содержание RD77MS16
Страница 1: ...MELSEC iQ R Simple Motion Module User s Manual Application RD77MS2 RD77MS4 RD77MS8 RD77MS16 ...
Страница 2: ......
Страница 316: ...314 9 COMMON FUNCTIONS 9 4 External Input Signal Select Function Program example ...
Страница 317: ...9 COMMON FUNCTIONS 9 4 External Input Signal Select Function 315 9 ...
Страница 574: ...572 13 PROGRAMMING 13 4 Positioning Program Examples Parameter initialization program Flash ROM write program ...
Страница 575: ...13 PROGRAMMING 13 4 Positioning Program Examples 573 13 Error reset program Axis stop program ...
Страница 643: ......