16.3 Actions to be Taken When the ERR. LED is On or Flashing
16
TROUBLESHOOTING
(3) Detailed error information and corrective actions by error code
The error codes and respective detailed information and corrective actions are shown
below.
If an error code not found in the error code list is detected, please consult your local
Mitsubishi service center or representative, explaining the details of the problem.
(a) Error code list (1000 to 1999)
Table 16.3 Error codes
Error code
Error message
Error information
LED status
CPU operation status
RUN
ERR.
1000
MAIN CPU DOWN
Off
Flashing
Stop
1009
MAIN CPU DOWN
Off
Flashing
Stop
1106
RAM ERROR
Off
Flashing
Stop
1300
FUSE BREAK OFF
Module No.
*1
Off/On
Flashing/On
Stop/Continue
*2
1310
I/O INT.ERROR
Off
Flashing
Stop
* 1 The error information (module No.) in "Event information" in the <<Event history>> tab of C Controller setting utility is displayed as follows:
"Error information: XX - YYY"
XX (DEC.): Slot No.(0 to 63), CPU No.(1 to 4)
YYY (HEX.): Start I/O No. 16 (000 to 0FF, 3E0 to 3E3)