10.3. External input/output function
Preset temperature input (external analog input: 4mA-20mA)
External input is input through CN421, CN422 on the circuit board. (Fig. 10.3.1)
Use the supplied connector.
If no temperature settings are made via the MA remote controller, the temperature
changes with the current.
Refer to the instructions manual that came with the MA remote controller for how
to make the settings.
4 mA
→
10
°
C
20 mA
→
70
°
C
External output terminal
External output terminal (refer to Fig. 10.3.2) is ineffective when the circuit is open.
Refer to Table 10.3.2 for information about each contact.
The current in the circuit to be connected to the external output terminal must be
0.6A or less.
Table10.3.2
External input terminal
The piping length must be within 100 m.
External input terminal (refer to Fig. 10.3.3) is ineffective when the circuit is open.
Refer to Table 10.3.3 through Table 10.3.5 for information about each contact.
Only the “pump interlock” function is ineffective when the circuit is short-circuited.
Connect a relay circuit to the external output terminal as shown in Fig. 7.4.1.
The specifications of the relay circuit to be connected must meet the following
conditions.
Contact rating voltage = DC15V
Contact rating current
=
0.1A
Minimum applicable load
=
1mA at DC
Table10.3.3
TB142A
Table10.3.4
TB142B
Table10.3.5
TB142C
*1 PWFY-P100VM-E-BU
Hot Water
PWFY-P100/200VM-E-AU
Heating
*2 Effective when SW 4-3 is set to ON.
*3 Effective when SW 4-4 is set to ON.
[Fig. 10.1.1] (P. 4)
A
Breaker for current leakage
B
Local switch or breakers for wiring
C
PWFY-P100VM-E-BU
D
PWFY-P100/200VM-E-AU
E
Pull box
Caution:
Do not use anything other than the correct capacity breaker and fuse. Us-
ing fuse, wire or copper wire with too large capacity may cause a risk of
malfunction or fire.
10.2. Connecting remote controller, indoor
and outdoor transmission cables
(Remote contoroller is optionally available.)
•
Connect unit TB5 and outdoor unit TB3. (Non-polarized 2-wire (shield))
The “S” on unit TB5 is a shielding wire connection. For specifications about
the connecting cables, refer to the outdoor unit installation manual.
•
Install a remote controller following the manual supplied with the remote con-
troller.
•
Connect the “1” and “2” on unit TB15 to a MA remote controller. (Non-polar-
ized 2-wire)
[Fig. 10.2.1]
(P.4) MA Remote controller
•
DC 10 to 13 V between 1 and 2 (MA remote controller)
[Fig. 10.2.2]
(P.4) MA Remote controller
•
The MA remote controller cannot be used at the same time or interchange-
ably.
A
Non-polarized
B
TB15 (MA remote controller cables)
C
MA remote Controller
D
TB5 (Transmission cables)
E
TB2 (Power supply wiring)
Note:
Ensure that the wiring is not pinched when fitting the terminal box cover.
Pinching the wiring may cut it.
Caution:
•
Use wire with supplemental insulation.
•
Input to TB142A, TB142B, and TB142C should not carry voltage.
•
Cables from equipment connected to external input/output should have sup-
plemental insulation.
•
Use a single multiple-core cable for external input/output to allow for connec-
tion to the PG screw.
Caution:
Wire the power supply so that no tension is imparted. Otherwise discon-
nection, heating or fire result.
OUT1
OUT2
OUT3
OUT4
Operation ON/OFF
Defrost
Compressor
Error signal
IN1
Pump interlock
IN3
IN4
Connection demand
Operation ON/OFF
COM+
IN5*1
IN6*2
IN7*3
Common
Hot Water/Heating
Heating ECO
Anti-freeze
10.1. Power supply wiring
•
Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
•
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
ELECTRICAL WORK
1. Electrical characteristics
Model
PWFY-P100VM-E-BU
Minimum wire thickness (mm
2
)
Main cable
2.5
Ground
2.5
30 A 30 mA 0.1 sec or less
Local swich (A)
fuse
25
branch
-
Breaker for
current leakage
capacity
25
30
Breaker for wiring (NFB) (A)
Model
Minimum wire thickness (mm
2
)
Local swich (A)
Breaker for
current leakage
capacity
Breaker for wiring (NFB) (A)
Main cable
1.5
2.5
4.0
branch
1.5
2.5
4.0
Ground
1.5
2.5
4.0
fuse
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Total
operating
current
16 A or less
25 A or less
32 A or less
20 A 30 mA 0.1 sec. or less
30 A 30 mA 0.1 sec. or less
40 A 30 mA 0.1 sec. or less
20
30
40
16
25
32
16
25
32
2. Power cable specifications
Model
PWFY-P100VM-E-BU
Hz
50/60
Volts
220-230-240 V
Voltage range
Max. 264 V
Min. 198 V
MCA (A)
15.71
Output (kW)
1.0
SC (A)
1.25
RLA (A)
Heating
11.63-11.12-10.66
PWFY-P100VM-E-AU
PWFY-P200VM-E-AU
Hz
50/60
Volts
220-230-240 V
Voltage range
Max. 264 V
Min. 198 V
MCA (A)
0.085
Cooling
Heating
Model
0.068-0.065-0.063
Power supply
Compressor
RLA (A)
Power supply
WT05377X01_en
08.6.19, 9:27 AM
11
Содержание PWFY-P100VM-E-AU