en
7
3. Installing the outdoor unit
(mm)
600
600
210
210
1020
25
330
370
Min. 10
Min. 430
B
D
A
C
E
Max. 30
A
M10 (3/8”) bolt
B
Base
C
As long as possible.
D
Vent
E
Set deep in the ground
Fig. 3-1
•
Be sure to install the unit in a sturdy, level surface to prevent rattling noises during
operation. (Fig. 3-1)
<Foundation specifications>
Foundation bolt
M10 (3/8")
Thickness of concrete
120 mm
Length of bolt
70 mm
Weight-bearing capacity
320 kg
•
Make sure that the length of the foundation bolt is within 30 mm of the bottom
surface of the base.
• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca
-
tions.
Installing the outdoor unit
•
Do not block the vent. If the vent is blocked, operation will be hindered and break-
down may result.
•
In addition to the unit base, use the installation holes on the back of the unit to
attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15
mm or less) and install on site.
Warning:
• The unit must be securely installed on a structure that can sustain its
weight. If the unit is mounted on an unstable structure, it may fall down and
cause damage or injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor
-
rectly installed unit may fall down and cause damage or injuries.
Caution:
• Install be unit on a rigid structure to prevent excessive operation sound or
vibration.
RH79D007H02_01en.indd 7
2020/09/25 17:18:58
009