OPERATING PROCEDURE
PHOTOS
98
6. Removing the thermistor <Ambient> (TH7)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Disconnect the connector TH7/6 (RED) on the controller
circuit board in the electrical parts box. (See Photo 4)
(4) Loosen the fastener for the lead wire in the electrical parts
box.
(5) Loosen the clamps for the lead wire on top of the electrical
parts box.
(6) Pull out the thermistor <Ambient> (TH7) from thermistor holder.
Photo 11
Lead wire of thermistor <Ambient> (TH7)
Sensor holder
Photo 12
Valve bed
Thermistor
<Comp. Surface>
(TH32)
Compressor
Note: When replacing thermistor <Ambient> (TH7),
replace it together with thermistor <2-phase pipe>
(TH6), since they are combined together. Refer to
procedure No.4 in the previous page to remove the
thermistor <2-phase pipe>(TH6).
Damper
Thermistor
<Liquid>
(TH3)
7. Removing the thermistor <Liquid> (TH3), and thermistor
<Comp. surface> (TH32).
(1) Remove the service panel. (See Photo 1)
(2) Disconnect the connector, TH3 (WHT) and TH32 (BLK) on
the controller circuit board in the electrical parts box. (See
Photo 4)
(3) Loosen the fastener, cable strap and band for the lead wire
on the controller circuit board in the electrical parts box.
(4) Loosen the clamp for the lead wire on separator.
(5) Pull out the thermistor <Liquid> (TH3) from thermistor clip.
(6) Remove the top damper, then pull out the thermistor
<Comp. surface> (TH32) from thermistor holder.
OCH582B
Содержание PUHZ-P200YKA.UK
Страница 101: ...101 OCH582B ...