5-5. STANDARD OPERATION DATA
PLA-RP125BAR4.UK
PLA-RP100BAR4.UK
PLA-RP125BAR4.UK
PLA-RP100BAR4.UK
1, 50
1, 50
230
230
0.15
0.14
1.00
0.94
PUHZ-P250YKA.UK
PUHZ-P250YKAR1.UK
PUHZ-P200YKA.UK
PUHZ-P200YKAR1.UK
3, 50
3, 50
400
400
Heating
Cooling
Heating
Cooling
11.78
10.57
8.63
7.77
19,000
22,400
22,000
27,000
5.92
6.36
7.83
8.41
79.2
74.5
68.8
66.8
50.2
50.3
45.0
48.8
−
2.0
5.6
−
2.1
7.6
7.5
7.5
7.5
7.5
20
27
20
27
15
19
15
19
45.3
12.4
41.6
13.3
7
35
7
35
6
24
6
24
0.71
0.74
0.18
0.21
—
—
—
—
2.99
3.03
2.97
2.81
0.63
0.83
0.89
0.63
0.13
0.87
0.14
0.94
Electrical circuit
Refrigerant circuit
Indoor side
Outdoor
side
Representative matching
SHF
BF
Mode
Capacity
Input
Total
Phase , Hz
Voltage
Input
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
V
kW
A
V
A
MPa
MPa
°C
°C
°C
m
°C
°C
°C
°C
°C
Indoor unit
D.B.
W.B.
D.B.
D.B.
W.B.
W
kW
OCH582B