WIRING SPECIFICATIONS
8-1. FIELD ELECTRICAL WIRING (power wiring specifications)
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Cylinder or
Hydrobox unit/outdoor
unit connection cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
B
N
1
2
S1
S2
S3
S1
S2
S3
Remote
controller
B
Earth leakage breaker
C
wiring circuit breaker or
isolating switch
C
Cylinder or
Hydrobox unit
B
B
Earth leakage breaker
C
wiring circuit breaker or
isolating switch
C
L
N
1
2
1
2
S1
Indoor
unit
S2
S3
S1
S2
S3
S1
S2
S3
Unit
power
supply
Indoor/outdoor
unit connection
cable
Indoor
unit
Outdoor
unit
Remote
controller
Cylinder or
Hydrobox unit/outdoor
unit connection cable
1
2
S1
S2
S3
S1
S2
S3
Remote
controller
Cylinder or
Hydrobox unit
1:1 system electrical wiring
Synchronized twin system electrical wiring
• Synchronized twin
Notes: 1. Wiring size must comply with the applicable local and national code..
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
3. Install an earth line longer than power cables.
Warning:
In the case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
(Design 60245 IEC 57)
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
Power supply
Isolator
A-Control
Indoor Unit
Outdoor unit power supply
~/N (single), 50 Hz, 230 V
Outdoor unit input capacity Main switch (Breaker)
*1
25 A
Wiring
Wire No. ×
size (mm²)
Outdoor unit power supply
3 × Min. 2.5
Indoor unit – Outdoor unit
Cylinder– or Hydrobox – Outdoor unit
*2
3 × 1.5 (Polar)
Indoor unit – Outdoor unit earth
Cylinder– or Hydrobox – Outdoor unit earth
*2
1 × Min. 1.5
Remote controller – Indoor unit *3
Cylinder– or Hydrobox-side remote controller – its unit
2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L – N (single)
Outdoor unit L1 – N, L2 – N, L3 – N (3 phase)
*4
230 V AC
Indoor unit – Outdoor unit S1-S2
Cylinder– or Hydrobox – Outdoor unit S1-S2
*4
230 V AC
Indoor unit – Outdoor unit S2-S3
Cylinder– or Hydrobox – Outdoor unit S2-S3
*4
24 V DC
Remote controller – Indoor unit
Cylinder– or Hydrobox-side remote controller – its unit
*4
12 V DC
*1
A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
*2
Maximum 45 m
If 2.5 mm² used, maximum 50 m
If 2.5 mm² used and S3 separated, maximum 80 m
*3
Maximum 500 m (When using 2 remote controllers, the maximum wiring length for the remote controller cables is 200 m.)
*4
The figures are NOT always against the ground.
S3 terminal has 24 V DC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.