5
6
6.1
When viewed from left side of unit
[Fig. 6.1.2]
When viewed from left side of unit
[Fig. 6.1.5]
When viewed from front of unit
[Fig. 6.1.6]
When viewed from front of unit
[Fig. 6.1.4]
When viewed from front of unit
[Fig. 6.1.3]
When viewed from left side of unit
[Fig. 6.1.1]
• P250·P300-F models
A
Service panel
B
Closed-end
pipe cap (gas)
C
Closed-end pipe
cap (liquid)
D
Maintenance
access hole
F
Unit
front
E
Closed-end
pipe cap (gas)
A
Service panel
B
L-shaped pipe
1
(gas)
C
Refrigerant pipe
2
(liquid)
G
Knockout holes for refrigerant
pipes
E
Maintenance
access hole
D
Connection to the
supplied pipe
<A> (Pipes routed
on the left of
the unit)
B
Connection to the
field-installed pipe
A
Field-installed pipe (liquid)
C
Field-installed pipe (gas)
<B> Caulk the gap between the pipe cover (field supplied)
and the access hole on the side panel.
<C> Insert at least 50 mm of the end of the pipe covers
(liquid/gas) into the access hole on the side panel.
<D> Caulk the gaps around the field-installed pipes and
pipe covers to keep condensation out.
* This also applies when routing the pipe on the left.
• P500·P600-F models
A
Cap pipe (Gas pipe)
B
Rubber cap (Liquid pipe)
A
Supplied pipe
connection parts
B
L bend pipe
2
(for liquid pipe)
C
L bend pipe
1
(for gas pipe)
D
Knockout holes for
refrigerant pipes
A
Connections for locally procured pipes
B
Locally procured pipes (gas and liquid)
<B> Caulk the side panel through holes and pipe covers (procured locally) to ensure
there is no gap.
<C> Insert the covers for the liquid pipe and gas pipe at least 50 mm into the side panel.
<D> Perform caulking or other measures to prevent dew condensation water from
entering the locally procured pipe covers.
* The same procedures apply when drawing out the pipes from the left.
<A> (When drawing
the pipe out from
the left)
F
Unit
front
<A> Viewed from the
direction of arrow A
00gb_WT05474X02_7.book Page 5 Wednesday, July 22, 2009 5:29 PM
Содержание PFAV-P250-500-750VM-E
Страница 119: ......