 3. System Configuration

Warning: Thermostat should be configured for use with a conventional system 

(not heat pump).
Note: When either Y2 or W2 is left unconnected, it is recommended to set 

SW2-6 to the OFF position. 

 1.  All wiring shown should be performed with 18 AWG thermostat wire. 
 2.  Terminals on the PAC-US444CN-1 support 20-30VAC.
 3.  High/medium/low fan signals are optional, and may not be available on all 

thermostat models.

 4.  W2 and Y2 signals are optional, and may be omitted for single-stage thermostats.

Example 1: Two-stage Cooling and Heating

Note: When both Y2 and W2 are connected, it is recommended to set SW2-6 to 

the ON position. 

Thermostat Interface

sandium.com

Содержание PAC-US444CN-1

Страница 1: ...ety precautions before use Hazards that can occur from incorrect handling are classified by the symbols below Warning Incorrect handling can result in death serious injury etc Caution Incorrect handling can result in bodily injury and or structure damage After reading this manual keep this manual for future reference When the device is reinstalled or repaired give this manual to those who provide ...

Страница 2: ...e internal parts cause device performance to be reduced and cause electrical shock Do not install the device in a bathroom kitchen or any room where steam could form Condensation may develop and cause electrical shock and or the device to malfunction Use standard wires with the proper current capacity to avoid the possibility of current leak excessive heat and or fire Do not touch the main circuit...

Страница 3: ...sition 1 All wiring shown should be performed with 18 AWG thermostat wire 2 Terminals on the PAC US444CN 1 support 20 30VAC 3 High medium low fan signals are optional and may not be available on all thermostat models 4 W2 and Y2 signals are optional and may be omitted for single stage thermostats Example 1 Two stage Cooling and Heating Note When both Y2 and W2 are connected it is recommended to se...

Страница 4: ...e When either Y2 or W2 is left unconnected it is recommended to set SW2 6 to the OFF position Example 3 Single stage Cooling and Heating with Dedicated Fan Speed Relays Note When connecting only first stage signals Y1 W1 it is recommended to set SW2 6 to the OFF position sandium com ...

Страница 5: ... Heating G G Fan 4 How to Install 1 Choose a place where to install the PAC US444CN 1 The device provides two mounting holes that can be used to mechanically affix the case to a solid surface Double sided tape may be used to affix the device When using tape ensure that the tape is approved for use within the anticipated operating temperature ranges 2 Install the transformer as necessary per buildi...

Страница 6: ...ollowing settings SW1 3 SW1 4 Result OFF OFF Auto Default ON OFF Medium OFF ON High ON ON Custom Auto Note Custom Auto provides more comfortable fan speed operation vs the more efficient Auto default Two Stage Thermostat Operation SW2 6 Adjusts indoor unit operation during stage 1 heating and stage 1 cooling according to the following table SW2 6 Operation during stage 1 OFF Full capacity ON The c...

Страница 7: ... Set by SW2 4 2 ON ON OFF 3 1 Set by SW2 4 2 ON ON ON 3 2 Set by SW2 4 2 Refer to the appropriate Indoor Unit Installation Manual for Mode 8 and Mode 10 function setting definitions CN24 Operation During Defrost SW2 4 Adjusts Mode 23 function settings according to the following table SW2 4 Result Fan and CN24 OFF Setting 2 Default ON ON Setting 1 OFF Refer to the appropriate Indoor Unit Installati...

Страница 8: ...e thermostat s temperature sensing is used to set the room temperature The indoor unit thermistor is used when calculating cooling and heating rates of change 5 Usage Operate the third party thermostat per the manufacturer s instructions During normal operation the connection of Mitsubishi remote controllers e g MA ME is not supported as they will interfere with the correct operation of the PAC US...

Отзывы: