356
(58)CH
Self-tuning setting (address: 2C0H to 2C3H)
Perform operation setting of self-tuning with this remote buffer memory area.
For details on the self-tuning function, refer to the following.
(a) Setting range
• 0: Do not run the ST
• 1: Starting ST (PID constants only)
• 2: Starting ST (Simultaneous temperature rise parameter only
*1
)
• 3: Starting ST (PID constants and simultaneous temperature rise parameter
*1
)
• 4: Starting ST plus vibration ST (PID constants only)
*1
Indicates the values of CH
Simultaneous temperature rise gradient data (address: 2D1H, 2D5H, 2D9H, 2DDH) and
CH
Simultaneous temperature rise dead time (address: 2D2H, 2D6H, 2DAH, 2DEH) to be used in the simultaneous
temperature rise function.
For details on the simultaneous temperature rise function, refer to the following.
(b) Enabling the setting
Enable the setting contents by either of the following.
• Turning off and on Initial data setting request flag (RY9) while the operations of all channels are stopped
• Turning off and on During operation setting change instruction (RY10)
(c) Default value
The default values are set to Do not run the ST (0) in all channels.
This area is enabled only for the following channels.
• CH1 to CH4 when the standard control is used
• CH3 and CH4 when mix control (normal mode) or mix control (expanded mode) is used
Standard
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......