351
APPENDICES
A
Appendix
3 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
A
reas
(49)CH
Rate alarm alert detection cycle (address: 256H, 25FH, 268H, 271H)
Set the check cycle of the temperature process value (PV) for the rate alarm. Set the frequency of checks in the
unit of sampling cycles.
The check cycle can be calculated from the following formula.
• Rate alarm alert detection cycle = Set value of Rate alarm alert detection cycle
Sampling cycle
(a) Setting range
The setting range is 1 to 6000 (times).
(b) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(c) Default value
The default values are set to Every sampling cycle (1) in all channels.
(50)CH
Rate alarm upper limit value (address: 257H, 260H, 269H, 272H)
,
CH
Rate alarm lower limit value (address: 258H, 261H, 26AH, 273H)
Set the rate alarm upper limit value and lower limit value.
(a) Setting range
The setting is -32768 to 32767.
(b) Setting unit
The value to be set differs depending on the stored value in CH
Decimal point position (address: 620H,
621H, 622H, 623H). (
• No decimal place (0): Set a value in 1
(
or digit) unit.
• One decimal place (1): Set a value in 0.1
(
) unit (tenfold value).
(c) Enabling the setting
To enable the setting, turn off and on Initial data setting request flag (RY9) while the operations of all channels
are stopped.
(d) Default value
The default values are set to 0 in all channels.
Temperature
Input
Temperature
Input
Temperature
Input
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......