286
(4) Remote READY (RXB)
This signal is used as an interlock condition when the master station reads/writes data from/to the remote register
or remote buffer memory areas of the temperature control module.
The signal turns on when the module power supply is turned on.
When Error flag (RXA) turns on, the signal turns off.
(5) During operation setting change completion flag (RX10)
If parameters are changed during operation of the temperature control module and During operation setting
change instruction (RY10) is turned on, this signal turns on at the normal completion of the setting change.
The signal turns off when During operation setting change instruction (RY10) is turned off.
For parameters that can be changed during operation, refer to the following.
• Lists of Remote Buffer Memory Areas (
Common
Common
ON
OFF
OFF
OFF
OFF
ON
500ms
500ms
500ms
500ms
During operation setting
change instruction (RY10)
Remote buffer memory
Setting value B
During operation setting
change completion flag
(RX10)
Sampling cycle (500ms)
Reflection of a setting value
Setting value A
Setting value B
Controlled by the program
Controlled by the temperature control module
Setting value A
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......