278
*1
represents the channel number where an error has occurred.
*2
The error details written here are for the case when Error history is A06H to A09H (for Error history 1 (address: A00H to
A0FH)). The following information of when an error has occurred are stored in this area.
• Error occurrence address
• Process value (PV)
• Manipulated value (MV)
• Set value (SV)
For details on Error history, refer to the following.
0A
AH
Minor error
A process alarm upper
limit alert has occurred.
• The ALM LED turns on.
• CH
Alert occurrence flag
(RX18 to RX1B) turns on.
• CH
Process alarm upper
limit (b2 of RWr4 to RWr7)
turns on.
• The process value of
the error channel is
stored in Process
value (PV).
• The manipulated value
of the error channel is
stored in Manipulated
value (MV).
• The set value of the
error channel is stored
in Set value (SV).
When the temperature process
value (PV) has returned within
the setting range, the
corresponding bit of CH
Alert
definition (RWr4 to RWr7) and
CH
Alert occurrence flag
(RX18 to RX1B) automatically
turns off. Latest warning code
(RWr2) is automatically cleared
when the temperature process
value (PV) has returned within
the setting range.
0B
AH
Minor error
A process alarm lower
limit alert has occurred.
• The ALM LED turns on.
• CH
Alert occurrence flag
(RX18 to RX1B) turns on.
• CH
Process alarm lower
limit (b3 of RWr4 to RWr7)
turns on.
0C
AH
Minor error
A rate alarm upper limit
alert has occurred.
• The ALM LED turns on.
• CH
Alert occurrence flag
(RX18 to RX1B) turns on.
• CH
Rate alarm upper
limit (b4 of RWr4 to RWr7)
turns on.
When the temperature process
value (PV) has returned within
the setting range, the
corresponding bit of CH
Alert
definition (RWr4 to RWr7) and
CH
Alert occurrence flag
(RX18 to RX1B) automatically
turns off. Latest warning code
(RWr2) is automatically cleared
when the temperature process
value (PV) has returned within
the setting range.
0D
AH
Minor error
A rate alarm lower limit
alert has occurred.
• The ALM LED turns on.
• CH
Alert occurrence flag
(RX18 to RX1B) turns on.
• CH
Rate alarm lower
limit (b5 of RWr4 to RWr7)
turns on.
Alarm code
(hexadecimal)
*1
Classification
Cause
Operation at alarm
occurrence
Alarm details
*2
Action
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......