(2) List of error codes (D000H to DFFFH (D529H and D52BH excluded))
While any of these errors occurs, the ERR. LED does not turn on. Based on the behavior of the D LINK LED at
the occurrence of an error, the errors are classified into two types, each of which requires different
troubleshooting.
(a) Communication errors where the D LINK LED flashes or turns off
This type of communication error results in the D LINK LED flashing or being turned off. Troubleshoot the
problem with the CC-Link IE Field Network diagnostics. (
(b) Communication errors where the D LINK LED does not change
This type of communication error results in no change of the D LINK LED. These errors are not shown in CC-
Link IE Field Network diagnostics because they are automatically recovered after the occurrence.
Troubleshooting them requires the error history to be read out. (
When multiple errors have occurred, only the latest error code is stored in Latest error code (RWr0) or Latest warning code
(RWr2).
The errors that occurred in the past can be checked with the error history of the engineering tool.
For the error history, refer to the following.
• Checking with the command execution of slave station (
• Error history
(address: A00H to FFFH) (
Error code
(hexadecimal)
Error name
Description and cause
Action
D0E0H
Station type mismatch
The network parameter is invalid or
outside the range.
Change the station type of the module to the remote device station
in the network configuration settings of the master station.
D0E1H
Own station reserved
The network parameter is invalid or
outside the range.
• Cancel the reserved station specification in the network
configuration settings of the master station.
• Change the station number of the module to a station number
that is not reserved.
D0E2H
Station No. already in
use (own station)
The network parameter is invalid or
outside the range.
• Set a unique station number.
• After taking the above action, turn off and on or reset all the
stations where this error has been detected.
D0E3H
Own station No. out of
range
The network parameter is invalid or
outside the range.
Add the station information of the module in the network
configuration settings of the master station.
D72AH
Station number switch
out of range (a value
other than 1 to 120)
A value other than 1 to 120.is set as a
station number.
Set a station number in the range of 1 to 120.
Error code
(hexadecimal)
Error name
Description and cause
Action
D217H
Transient data
command error
The transient data request command is
invalid.
Correct the request command at the request source, and retry the
operation.
D2A0H
Receive buffer full
The transient transmission is overloaded
and the receive buffer of the own station
is full.
• Check the network status using the CC-Link IE Field Network
diagnostics of the engineering tool.
• Send transient data to the own station at intervals.
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......