(3) Procedure for the self-tuning control
The following is the flow chart for the control.
Self-tuning start
Self-tuning completion
PID constants are calculated and changed by
self-tuning.
The module is controlled with the set PID constants.
PID constants are calculated by self-tuning.
The setting is changed to the PID constants calculated
by self-tuning.
Temperature is controlled with the set PID constants.
Has the response failed?
YES
NO
Has the
temperature control been started?
Or has the set value (SV) been
changed?
YES
NO
Has the
temperature process value (PV)
become out of the set value (SV)?
YES
YES
NO
NO
Is the response erratic?
CH□ Auto tuning status (RX20 to RX23) turns on.
(Starting ST)
CH□ Auto tuning status (RX20 to RX23) turns off.
CH□ PID auto-correction status (b0 of RWr14 to RWr17)
turns off.
CH□ PID auto-correction status (b0 of RWr14 to RWr17)
turns on.
CH□ Auto tuning status (RX20 to RX23) turns on.
(Vibration ST)
CH□ PID auto-correction status (b0 of RWr14 to RWr17)
turns off.
CH□ PID auto-correction status (b0 of RWr14 to RWr17)
turns on.