166
8.3.9
Derivative action selection function
A derivative action appropriate for each of fixed value action and ramp action can be selected and the action
characteristic can be improved using this function.
(1) Action
Each type of derivative action operates as shown below.
(2) Setting method
1.
Set "Method selection" to "Param write" of the control mode to be used.
"CC IE Field Configuration" window
Select the temperature control module from "List of
stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
Set "CH
Differentiation operation selection".
CH
Derivative action
selection (address: 110H,
140H, 170H, 1A0H)
Action
Measured value derivation (0)
This setting effectively
prevents the temperature from
being affected by disturbance,
though the performance to
follow the set value can be
low.
Deviation derivation (1)
This setting allows the
temperature to follow the set
value well, though the
disturbance effect is great.
Standard
Heating-cooling
Ramp action
Fixed value action
Disturbance
Set value (SV)
Temperature
process value
(PV)
Temperature
process value
(PV)
Set value (SV)
Disturbance
Fixed value action
Ramp action
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......