(5) Warning flag assignment
Warning flag (RX7) is assigned to the remote output (RY) of the extension output module using the external
signal assignment function. When a minor error occurs, the assigned Remote output (RY) turns on.
(a) Setting range
With the head of Remote output (RY) of the main D/A converter module as a starting point (0000H), set the
device number for Remote output (RY) of the connected extension output module.
Ex.
When Warning flag (RX7) is assigned to Remote output (RY) numbered 6H as counted from the head
(0H) of the extension output module
Remote output (RY) numbered 6H as counted from the head of the extension output module corresponds to
Remote output (RY) numbered 26H as counted from the head of the main D/A converter module.
Thus, set 26H for Warning flag assignment (address: 0006H).
(b) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(c) Default value
The default value is No assignment (FFFFH).
(d) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Setting a value out of the range results in the error code (0174H) being stored in Latest error code (RWr0), Error flag (RXA)
turning on, and the ERR. LED lighting up, with the previously set operation.
Remote buffer memory name
Main D/A converter module
Extension D/A converter module
Warning status flag assignment
0006H
0H
to
to
to
1FH 20H
26H
2FH
to
to
0H
6H
FH
Main D/A converter module
Extension output module