![Mitsubishi Electric NZ2EX2B-60DA4 Скачать руководство пользователя страница 171](http://html.mh-extra.com/html/mitsubishi-electric/nz2ex2b-60da4/nz2ex2b-60da4_user-manual_1811812171.webp)
169
APPX
A
Appendix
1 Det
ails of
Rem
ot
e I
/O
S
ignals
Appendix
1.
1 Rem
ot
e
input
signals
APPENDICES
Appendix 1
Details of Remote I/O Signals
This section describes the details of the remote I/O signals for a master/local module.
The described assignment of device numbers assumes that the remote I/O signals of D/A converter modules are
assigned as follows:
Appendix 1.1
Remote input signals
(1) Warning flag
At the occurrence of a minor error, Warning flag (RX7) turns on.
Eliminating the cause of the minor error occurred and waiting for five seconds results in Latest warning code
(RWr1) turning to 0000H and Warning flag (RX7) turning off.
(a) Device number
The device number of this input signal is as follows:
Signal name
Main D/A converter module
Extension D/A converter module
Remote input signal
RX0 to RX1F
RX20 to RX2F
Remote output signal
RY0 to RY1F
RY20 to RY2F
Signal name
Main D/A converter module
Extension D/A converter module
Warning flag
RX7
Warning flag (RX7)
Latest warning code (RWr1)
Minor error removed
OFF
ON
ON
OFF
0000H
Error code or alarm code
Controlled by the D/A converter module
Minor error occurred
Remote READY (RXB)
0000H
5 seconds
5 seconds elapsed