CHAPTER 7 VARIOUS SETTINGS
7
7.3 Offset/Gain Setting
7.3
Offset/Gain Setting
If the user range is necessary, set up the offset/gain setting by following the instructions as illustrated below.
Note that using the factory default range does not require the offset/gain setting.
1.
Turn off the module power supply.
2.
Set x10 of the station number setting switch to O/G.
3.
Turn on the module power supply and check that
the LEDs are in the following state:
RUN LED: Off
O/G LED: On
4.
Select the setting target using SET/SEL button.
5.
Apply the offset value or gain value to the selected
channel for one second or more.
: OFF
: ON
[User range setting 1 (-10 to 10V)]
CH1: Offset
CH1: Gain
CH2: Offset
CH2: Gain
CH3: Offset
CH3: Gain
CH4: Offset
CH4: Gain
[User range setting 2 (-5 to 5V, -20 to 20mA)]
CH1: Offset
CH1: Gain
CH2: Offset
CH2: Gain
CH3: Offset
CH3: Gain
CH4: Offset
CH4: Gain
button
button