63
CHAPTER 6 INSTALLATION AND WIRING
6
6.6 Wiring of Te
rminal Bl
ock and
E
xter
nal D
evices
6.6
Wiring of Terminal Block and External Devices
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range.
Tightening the screws too much may damage the module case.
The following table shows applicable solderless terminals to be connected to the terminal block. For wiring, use
the wire and tightening torque as specified in the table below. Use UL-listed solderless terminals, and for
processing, use the tool recommended by their manufacturers. Note that a solderless terminal with an insulation
sleeve cannot be used.
Screw type
Tightening torque range
Terminal screw (M3)
0.43 to 0.57N
⋅
m
Terminal block mounting screw (M3.5)
0.68 to 0.92N
⋅
m
Solderless terminal
Wire
Model
Applicable tightening torque
Diameter
Type
Material
Temperature rating
R1.25-3
0.43 to 0.57N
⋅
m
22 to 14 AWG
Stranded
Copper
75
or higher
V2-MS3
RAP2-3SL
TGV2-3N