![Mitsubishi Electric NZ2EX2B-60AD4 Скачать руководство пользователя страница 207](http://html.mh-extra.com/html/mitsubishi-electric/nz2ex2b-60ad4/nz2ex2b-60ad4_user-manual_1811811207.webp)
205
APPX
A
Appendix 3 Details of Re
mote Buffer Me
mory
Appendix 3
Details of Remote Buffer Memory
This section describes the details of the remote buffer memory.
(1) Mode switch
Set the mode for all channels.
Setting a value other than the above results in the error code (0730H) being stored in Latest error code (RWr0),
Error flag (RXA) turning on, and the ERR. LED lighting up, with Automatical judgment mode (9H) set up.
(a) Enabling the setting
1.
Turn on and off Initial data setting request flag (RY9).
2.
Check that "0920H" is stored in Latest warning code (RWr1).
3.
Turn off and on the power supply.
(b) Default value
The default value is Automatical judgment mode (9H).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
(2) Conversion speed switch
Set the conversion speed for all channels.
In trigger conversion mode or synchronous communication mode, setting the conversion speed to 1ms/channel
(1H) results in operation at 400
μ
s/channel.
A value out of the range above results in the error code (0360H) being stored in Latest error code (RWr0), Error
flag (RXA) turning on, and the ERR. LED lighting up.
(a) Enabling the setting
Turn on and off Initial data setting request flag (RY9) to enable the setting.
(b) Default value
The default value is 400
μ
s/channel (0H).
(c) Remote buffer memory address
The remote buffer memory address of this area is as follows:
Mode
Setting value
Normal mode
0H
Trigger conversion mode
1H
Automatical judgment mode
9H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
Mode switch
0000H
Conversion speed
Setting value
400
μ
s/channel
0H
1ms/channel
1H
100
μ
s/channel
2H
Remote buffer memory name
Main A/D converter module
Extension A/D converter module
Conversion speed switch
0001H
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......