![Mitsubishi Electric NZ2EX2B-60AD4 Скачать руководство пользователя страница 101](http://html.mh-extra.com/html/mitsubishi-electric/nz2ex2b-60ad4/nz2ex2b-60ad4_user-manual_1811811101.webp)
99
CHAPTER 8 FUNCTIONS
8
8.7 Ra
nge Switching F
unct
ion
8.7
Range Switching Function
The input range can be selected for each channel from the following ranges:
• Factory default range (4 to 20mA, 0 to 20mA, 1 to 5V, 0 to 5V, -10 to 10V)
• User range (user range setting 1, user range setting 2)
*1
*1
The main A/D converter module only permits the selection.
(1) Setting procedure
The setting procedure for the main A/D converter module is as follows:
1.
Set "Method selection" to "Parameter write".
"CC IE Field Configuration" window
Select the main A/D converter module from "List of stations"
[CC IE Field Configuration]
[Online]
[Parameter Processing of Slave Station]
2.
In "Basic module parameter", set "CH
A/D conversion enable/disable setting" to "0: Enable".
3.
In "Basic module parameter", set up "CH
Range setting".
For the extension A/D converter module, make the settings for each item of "Ext. module 1_Module parameter".
Содержание NZ2EX2B-60AD4
Страница 1: ...CC Link IE Field Network Analog Digital Converter Module User s Manual NZ2GF2BN 60AD4 NZ2EX2B 60AD4 ...
Страница 2: ......
Страница 49: ...47 CHAPTER 4 PROCEDURES BEFORE OPERATION 4 Memo ...
Страница 156: ...154 3 In the dialog box that appears shown below click button ...
Страница 169: ...167 CHAPTER 10 MAINTENANCE AND INSPECTION 10 Memo ...
Страница 253: ......