UNIT: mm (inch)
Piping length each indoor unit (a, b)
20 m
Total piping length (a+b)
30 m
Bending point for each unit
20
Total bending point
30
MXZ-2HJ40VA
MAX REFRIGERANT PIPING LENGTH
a
b
Outdoor
unit
Indoor
units
15 m
10 m
15 m
Refrigerant piping length (one way, 2 unit total)
Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 20)
Outdoor unit
precharged
(g)
30 m
200
20 m
0
950
Max.
Height
difference
Outdoor unit union diameter
For
Indoor unit A
Liquid
6.35(1/4)
Gas
9.52(3/8)
Indoor unit B
Liquid
6.35(1/4)
Gas
9.52(3/8)
Stop valve
(with strainer #100)
LEV A
LEV B
Compressor
Muffler
4-way valve
Indoor unit
B
Indoor unit
A
Indoor unit
A
Indoor unit
B
Capillary tube
Capillary tube
Stop valve
(with strainer #100)
Refrigerant flow in cooling
Refrigerant flow in heating
Discharge
temperature
thermistor RT62
Stop valve
(with service port)
Stop valve
(with service port)
Strainer
#100
Sub muffler
Defrost
thermistor
RT61
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor
RT68
FAN-OUT
HEX-OUT
It is irrelevant which unit is higher.
ADDITIONAL REFRIGERANT CHARGE
UNIT: mm
REFRIGERANT SYSTEM DIAGRAM
7
Refrigerant pipe diameter is different according to indoor unit to be
connected. When using extension pipes, refer to the right table.
When diameter of refrigerant pipe is different from that of outdoor
unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS
CATALOG".