56
Check of LEV
No
Yes
No
Yes
Turn ON the power supply to the outdoor unit after checking LEV
coil is mounted to the LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of LEV coil with your hand?
Disconnect the connectors.
CN724: LEV A, CN725: LEV B
(MXZ-2HA)
CN791: LEV A, CN792: LEV B,
CN793: LEV C
(MXZ-3HA)
,
CN797: LEV R
(MXZ-3HA)
Is there normal resistance to LEV coil?
(Refer to 12-5.)
Normal
Replace the outdoor control P.C. board.
Replace LEV coil.
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit gets warm.
Connector
MXZ-2HA
MXZ-3HA
CN724
CN725
Inverter P.C. board
Outdoor control
P.C. board
CN791
CN792
CN793
CN794
CN795
CN796
―
OBH828B