51
Check of power supply
Outdoor unit does not operate.
MXZ-3HA50VF
12-6. TROUBLESHOOTING FLOW
Turn ON the power supply.
No
Yes
Yes
No
No
Yes
Check the main power supply circuit for proper connections.
Is there voltage of 220 - 230 - 240 V AC
in the power supply terminal block?
Is the output voltage from the outdoor
power P.C. board 311 - 339 V DC?
Check the power supply cable.
Replace the outdoor power P.C. board.
Turn OFF the power supply and recconnect the reactor.
Is the reactor short-circuited?
Replace the reactor.
Replace the outdoor control P.C. board.
Turn ON the power supply.
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
+
-
Check the main power supply circuit for proper connections.
Is there voltage of 220 - 230 - 240 V AC
in the power supply terminal block?
Is there voltage of 220 - 230 - 240 V AC
between LD66B and X64 on
the inverter P.C. board?
Check the power supply and correct them.
Replace the outdoor display P.C. board.
Replace the inverter P.C. board.
Is there voltage of 220 - 230 - 240 V AC
between LD66A and LD70 on the
inverter P.C. board?
Replace the reactor.
Is there voltage of 311 - 339 V DC
between DB61 and DB61 on the
inverter P.C. board?
Replace the inverter P.C. board.
Is there voltage of 5 V DC between
CN936 and CN936 on the
outdoor display P.C. board?
Check the connected wire between
the inverter P.C. board and outdoor
display P.C. board and correct it.
Replace the inverter P.C. board.
MXZ-2HA40VF/2HA50VF
OBH828B