14
SPECIFICATION
4
Outdoor model
MXZ-2HA40VF
Outdoor unit power supply
Single phase
220 - 230 - 240 V, 50 Hz
System
Indoor units number
2
Piping total length
m
Max. 30
Connecting pipe length
m
Max. 20
Height difference (Indoor ~ Outdoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function
Cooling
Heating
Capacity Rated (Min.-Max.) *2
kW
4.0 (1.1 - 4.3)
4.3 (1.0 - 4.7)
Breaker capacity
A
15
Electrical
data
Power input (Total) *1, *2
W
1,050
910
Running current (Total) *1, *2
A
5.1 - 4.9 - 4.7 (220V - 230V - 240V) 4.8 - 4.6 - 4.4 (220V - 230V - 240V)
Power factor (Total) *1, *2
%
94
87
Starting current (Total) *1, *2
A
7.6
Coefficient of performance (C.O.P) (Total)
*1, *2
3.81
4.73
Compressor
Model
SVB130FBBMT
Output
W
1,100
Current *1, *2
A
4.15
Refrigeration oil (Model)
L
0.35 (FW68S)
Fan motor
Model
RC0J50-NA
Current *1, *2
A
0.35
Dimensions W x H x D
mm
800 x 550 x 285
Weight
kg
37
Special remarks
Air flow (Rated)
m
3
/h
1,704
2,010
Sound level (Rated)
dB(A)
44
50
Fan speed (Rated)
rpm
780
910
Pre-charged refrigerant quantity (R32)
kg
0.9
Max refrigerant quantity (R32)
kg
0.9
*1 Measured under rated operating frequency.
*2 When connected with indoor units below.
MSZ- MSZ-HR25VF
NOTE:
Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C