Mitsubishi Electric MXZ-2C20NAHZ Скачать руководство пользователя страница 2

En-

1-2. SPECIFICATIONS

1.  BEFORE INSTALLATION

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

•  Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.

•  Be sure to observe the warnings and cautions specified here as they include important items related to safety.

•  After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.

Required Tools for Installation

Phillips screwdriver

Level

Scale

Utility knife or scissors

Torque wrench

Wrench (or spanner)

5/32 in. (4 mm) hexagonal 

wrench

Flare tool for R40A

Gauge manifold for R40A

Vacuum pump for R40A

Charge hose for R40A

Pipe cutter with reamer

 ENGLISH

CONTENTS

. BEFORE INSTALLATION ............................................................

2. OUTDOOR UNIT INSTALLATION ...............................................3

3. FLARING WORK AND PIPE CONNECTION ...............................5

4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN ......... 5

5. PUMPING DOWN ........................................................................7

Model

Power supply

Pipe length and height difference *, *2, *3, *4, *5, *6

Rated Voltage

Frequency Max. pipe length per indoor 

unit / for multi-system

Max. height difference

Max. no. of bends per 

indoor unit / for multi system Refrigerant adjustment A *7

MXZ-2C20NAHZ

208/230 V

60 Hz

82 ft (25 m)/64 ft (50 m)

49 ft (5 m)

25/80

.08 oz each 5 ft (20 g/m)

MXZ-3C24NAHZ

MXZ-3C30NAHZ

82 ft (25 m)/230 ft (70 m)

MXZ-5C42NA

82 ft (25 m)/262 ft (80 m)

*1 Never  use  pipes  with  thickness  less  than  specified.  The  pressure  resist

-

ance will be insufficient.

*2 Use a copper pipe or a copper-alloy seamless pipe.

*3 Be careful not to crush or bend the pipe during pipe bending.

*4 Refrigerant pipe bending radius must be 4 in. (00 mm) or more.

*5 Insulation material : Heat resisting foam plastic 0.045 specific gravity

*6 Be sure to use the insulation of specified thickness. Excessive thickness 

may cause incorrect installation of the indoor unit and insufficient thickness 

may cause dew drippage.

*7 If pipe length exceeds 98 ft (30 m), additional refrigerant (R40A) charge 

is  required.  (No  additional  charge  is  required  for  pipe  length  less  than  

98 ft (30 m).)

  Additional refrigerant (ft) = A ×  (pipe length (ft) - 98)

5

  Additional refrigerant (m) = A × (pipe length (m) - 30)

n

  Do not install the unit by yourself (user).

  Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water. Consult the dealer from whom you purchased the 

unit or a qualified installer.

n

  Follow the instructions detailed in the installation manual.

  Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water. 

n

  When installing the unit, use appropriate protective equipment and tools 

for safety.

  Failure to do so could cause injury.

n

  Install the unit securely in a place that can bear the weight of the unit.

  If the installation location cannot bear the weight of the unit, the unit could fall 

causing injury.

Perform electrical work according to the installation manual and be sure 

to use an exclusive circuit. Do not connect other electrical appliances to 

the circuit.

  If the capacity of the power circuit is insufficient or there is incomplete electrical 

work, it could result in a fire or an electric shock.

n

  Ground the unit correctly.

  Do not connect the ground wire to a gas pipe, water pipe, lightning rod or 

telephone ground. Defective grounding could cause electric shock.

Do not damage the wires.

  Damaged wires could cause fire.

Be sure to shut off the main power when setting up the indoor P.C. board 

or wiring.

  Failure to do so could cause electric shock.

n

  Use the specified wires to securely connect the indoor and outdoor units. 

Attach the wires firmly to avoid applying stress to the terminal block.

  Improper connection could cause fire.

Do not install the unit in a place where flammable gas may leak.

  If gas leaks and accumulates around the unit, it could cause an explosion.

n

  Do not use intermediate connection of the power cord or the extension 

cord.Do not connect many devices to one AC outlet.

  It could cause a fire or an electric shock.

Use the parts provided or specified parts for the installation work.

  The use of defective parts could cause an injury or leakage of water due to a 

fire, an electric shock, the unit falling, etc.

When plugging the power supply plug into the outlet, make sure that there 

is no dust, blockage, or loose parts both in the outlet and on the plug. 

Verify that the power supply plug is completely in the outlet. 

  If there is dust, blockage, or loose parts on the power supply plug or the outlet, 

it could cause electric shock or fire. If loose parts are found on the power supply 

plug, replace it.

Securely attach the electrical cover to the indoor unit and the service 

panel to the outdoor unit.

  If the electrical cover of the indoor unit and/or the service panel of the outdoor 

unit are not attached securely, dust, water, etc. could collect in the unit and 

could cause a fire or an electric shock.

When installing, relocating, or servicing the unit, make sure that no substance 

other than the specified refrigerant (R410A) enters the refrigerant circuit.

  Any presence of foreign substance such as air can cause abnormal pressure 

rise and may result in explosion or injury. The use of any refrigerant other than 

that specified for the system will cause mechanical failure, system malfunction, 

or unit breakdown. In the worst case, this could lead to a serious impediment 

to securing product safety.

Do  not  discharge  the  refrigerant  into  the  atmosphere.  Check  that  the 

refrigerant gas does not leak after installation has been completed. If 

refrigerant leaks during installation, ventilate the room.

  If refrigerant comes in contact with a fire, harmful gas could be generated. 

  If refrigerant gas leaks indoors, and comes into contact with the flame of a fan 

heater, space heater, stove, etc., harmful gases will be generated.

Use appropriate tools and piping materials for installation. 

  The pressure of R40A is .6 times higher than R22. Not using the appropri-

ate tools and materials, or improper installation could cause the pipes to burst 

causing an injury. 

When pumping down the refrigerant, stop the compressor before discon-

necting the refrigerant pipes.

  If the refrigerant pipes are disconnected while the compressor is running and 

the stop valve is open, air could be drawn in and the pressure in the refrigera

-

tion cycle could become abnormally high, causing the pipes to burst. 

When installing the unit, securely connect the refrigerant pipes before 

starting the compressor.

  If the compressor is started before the refrigerant pipes are connected and the 

stop valve is open, air could be drawn in and the pressure in the refrigeration 

cycle could become abnormally high, causing the pipes to burst.

Fasten a flare nut with a torque wrench as specified in this manual.

  If fastened too tight, a flare nut could break and cause refrigerant leakage.

Install the unit  according to national wiring regulations.

n

  Be sure to install a Ground Fault Interrupt (GFI) circuit breaker.

  Failure to install a Ground Fault Interrupt (GFI) circuit breaker may result in 

electric shock or fire.

n

  Perform the drainage/piping work securely according to the installation 

manual.

  If there is defect in the drainage/piping work, water could drip from the unit, 

and damage household items.

n

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

  This could cause injury. 

n

  Do not install the outdoor unit where small animals may live.

  If small animals enter the unit and damage its electrical parts, it could cause a 

malfunction, smoke emission, or fire. Keep the area around the unit clean. 

 

CAUTION

(Could lead to serious injury when operated incorrectly.)

 

WARNING

(Could lead to death or serious injury, etc.)

BH79A088H01_en.indd   1

2014/08/05   13:34:46

Содержание MXZ-2C20NAHZ

Страница 1: ...tion de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual de instalación de dicha unidad Cualquier...

Страница 2: ...e unit it could cause an explosion n Do not use intermediate connection of the power cord or the extension cord Do not connect many devices to one AC outlet It could cause a fire or an electric shock n Use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an electric shock the unit falling etc n When p...

Страница 3: ... Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed with walls such as a verandah be sure to have enough space as shown below In this case the air con...

Страница 4: ...er indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm if there are obstacles to both sides Open as a rule More than 19 11 16 in 500 mm if the back both sides and top are open More than 13 25 32 in 350 mm Outdoor unit installation Air inlet Air outlet 2 U shape notched holes B...

Страница 5: ... only Follow local electrical code POWER SUPPLY CABLE Use solid or stranded conductor Min AWG8 Use copper conductors only Follow local electrical code GROUND WIRE Use solid or stranded conductor Min AWG8 Use copper conductors only Follow local electrical code WARNING Use the indoor outdoor unit connecting wire that meets the Standards to connect the indoor and outdoor units and fix the wire to the...

Страница 6: ... completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the tool selected 5 Check Compare the flared work with Fig 6 If flare is noted to be defective cut off the flared sec tion and do flaring work again 4 1 PURGING PROCEDURES AND LEAK TEST 4 PURGING PROCE...

Страница 7: ...during cold season But never use naked fire or steam Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Procedure Press the pipin...

Страница 8: ...nit installation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of the refrigerant in the ...

Страница 9: ... peut provoquer un incendie n N installez pas l unité dans un endroit exposé à des fuites de gaz inflam mable La fuite ou l accumulation de gaz autour de l unité peut entraîner une explo sion n N utilisez pas de raccord intermédiaire ou de rallonge pour brancher le cordon d alimentation Ne branchez pas plusieurs appareils à une prise secteur Cela peut provoquer un incendie ou un choc électrique n ...

Страница 10: ...st basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit face au mur Pour éviter toute exposition au vent il est recommandé d installer un écran de protection du côté de la ...

Страница 11: ...mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose de l ancien climatiseur Reformer l écrou évasé en respec tant les dimensions des nouveaux tuyaux de réfrigérant 23 5 8 600 14 9 16...

Страница 12: ...ncomplet ou une fixation incorrecte risqueraient de provoquer un incendie Raccorder les fils aux bornes associées aux numéros correspondants Lors du raccordement du cordon et ou du fil au bloc de sortie veiller à fixer chaque vis à la borne correspondante APPAREIL INTÉRIEUR Prévoir une longueur de câble de raccordement supplémentaire en vue des entretiens ultérieurs Remarque Un sectionneur devrait...

Страница 13: ...de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G sur les embouts évasés des tuyaux ainsi que sur les raccords de tuyau de l appareil extérieur 2 Alignez la partie médiane du tuyau sur les raccords de tuyau de l appareil extérieur et serrez les écrous évasés à la main de 3 à 4 tours 3 Serre...

Страница 14: ...ible appuyer de nouveau sur le commutateur de correc tion de câblage tuyauterie SW871 pour annuler cette fonction Vérifier ensuite les raccordements de câblage et tuyauterie de manière conventionnelle en faisant fonctionner les appareils intérieurs l un après l autre Pour utiliser cette fonction l appareil doit être alimenté Veiller à ne pas toucher des éléments autres que le commutateur notamment...

Страница 15: ...llation de l appareil intérieur pour la méthode d arrêt du système Si trop de réfrigérant a été ajouté au système de climatisation il se peut que la pression ne parvienne pas à baisser jusqu à 0 1 à 0 psi jauge 0 05 à 0 MPa ou la fonction de protection pourrait se déclencher en raison de la montée de pression dans le circuit de réfrigérant à haute pression Dans ce cas utilisez un dispositif de col...

Страница 16: ...cumula alrededor de la unidad podría producirse una explosión n No emplee conexiones intermedias del cable de alimentación ni tampoco un cable de extensión Evite también conectar demasiados aparatos a una sola toma de CA Esto podría provocar un incendio o una descarga eléctrica n Utilice las piezas suministradas o indicadas para efectuar la instalación El empleo de piezas defectuosas podría provoc...

Страница 17: ...sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposición al viento se recomienda instalar una placa de flectora en el lado de salida de aire de l...

Страница 18: ... madera tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo Para utilizar tuberías ya existentes active el modo COOL REFRIGERA CIÓN durante 30 minutos y realice el bombeo de vaciado antes de retirar el acondicionador de aire antiguo Adapte el abocardado a las dimensiones para el nuevo refrigerante 2 ...

Страница 19: ...sas podrían provocar un incendio Conecte los cables al número correspondiente de terminales Asegúrese de conectar cada tornillo con su terminal correspon diente cuando fije los cables al panel de terminales Con vistas a un futuro mantenimiento prolongue los cables de conexión 2 2 CABLES DE CONEXIÓN PARA LA UNIDAD EXTERIOR ESPECIFICACIONES ELÉCTRICAS UNIDAD EXTERIOR MXZ 2C20NAHZ MXZ 3C24NAHZ MXZ 3C...

Страница 20: ...ervicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cerradas y cubiertas con sus tapas 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vac...

Страница 21: ...erías inco rrecta y resulte difícil confirmarla use esta función para detectarla y corregirla siguiendo estos procedimientos Asegúrese de lo siguiente La unidad recibe corriente Las válvulas de retención están abiertas 4 4 EXPLICACIÓN PARA EL USUARIO Basándose en el MANUAL DE INSTRUCCIONES explique al usuario cómo utilizar el equipo de aire acondicionado cómo utilizar el controlador remoto cómo re...

Страница 22: ...lte el manual de instalación de la unidad interior para más detalles acerca del método de detención de la operación Si se ha añadido demasiado refrigerante al sistema con acondicionador de aire puede que la presión no baje de 0 1 a 0 psi manómetro de 0 05 a 0 MPa o que la función de protección se ponga en funcionamiento debido a la subida de presión en el circuito de refrigeración de presión eleva...

Страница 23: ...A4 tombo blank indd 1 12 18 2006 9 45 16 AM ...

Страница 24: ...BH79A088H01 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BH79A088H01_cover4 indd 2 2014 08 05 13 34 25 ...

Отзывы: