34
NOTE:
Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).
The left
lamp of
OPERATION
INDICATOR
lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C. board)
Condition
Remedy
Indoor/outdoor
unit failure
mode recall
function
Outdoor unit
failure mode
recall function
10-time blink
2.5 seconds
OFF
Discharge temperature
—
Temperature of discharge temperature
thermistor has been 50°C or less for
20 minutes.
• Refer to 12-5. "Check
of LEV".
• Check refrigerant
circuit and refrigerant
amount.
—
○
11-time blink
2.5 seconds
OFF
Bus-bar voltage (DC)
8-time blink
2.5 seconds OFF
Bus-bar voltage of inverter cannot be
detected normally.
• Refer to 12-5. "How
to check inverter/
compressor".
—
○
Each phase current of
compressor
9-time blink
2.5 seconds OFF
Each phase current of compressor
cannot be detected normally.
14-time blink
or more
2.5 seconds
OFF
Stop valve (Closed valve)
14-time blink
2.5 seconds OFF
Closed valve is detected by
compressor current.
• Check stop valve.
○
○
4-way valve/
Pipe temperature
16-time blink
2.5 seconds OFF
The 4-way valve does not work
properly.
The indoor coil thermistor detects an
abnormal temperature.
• Check the 4-way
valve.
• Replace the inverter
P.C. board.
Outdoor refrigerant system
abnormality
1-time blink
2.5 seconds OFF
A closed valve and air trapped in the
refrigerant circuit are detected based
on the temperature sensed by the
indoor and outdoor thermistors and the
current of the compressor.
• Check for a gas leak
in a connecting piping
etc.
• Check the stop valve.
• Refer to 12-5.
“Check of outdoor
refrigerant circuit”.
○
○
OBH823
Содержание MUZ-HR25
Страница 9: ...9 Unit mm MUZ HR25VF MUZ HR35VF OUTLINES AND DIMENSIONS 6 MUZ HR35VF MUZ HR42VF MUZ HR50VF OBH823 ...
Страница 10: ...10 WIRING DIAGRAM 7 MUZ HR25VF E1 ER1 MUZ HR35VF E1 ER1 MUZ HR25VF ET1 MUZ HR35VF ET1 OBH823 ...
Страница 11: ...11 MUZ HR42VF E1 ER1 MUZ HR50VF E1 ER1 MUZ HR42VF ET1 MUZ HR50VF ET1 OBH823 ...