background image

3

2

SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R32

Servicing precautions for units using refrigerant R32

 

WARNING

This unit uses a flammable refrigerant.

If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire.

  Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.

  The appliance shall be stored in a room without continuously operating ignition sources (for example: open flames, an operating gas appliance or an operating  

 

electric heater.)

  Do not pierce or burn.

  Be aware that refrigerants may not contain an odor.

  Pipe-work shall be protected from physical damage.

  The installation of pipe-work shall be kept to a minimum.

  Compliance with national gas regulations shall be observed.

  Keep any required ventilation openings clear of obstruction.

  Servicing shall be performed only as recommended by the manufacturer.

  The appliance shall be stored so as to prevent mechanical damage from occurring.

Basic work procedures are the same as those for conventional units using refrigerant R410A.

However, pay careful attention to the following points.

1.  Information on servicing

  Checks on the Area

 

Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimized.

  Work Procedure

 

Work shall be undertaken under a controlled procedure so as to minimize the risk of a flammable gas or vapor being present while the work is being performed.

  General Work Area

 

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided.  

 

The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

  Checking for Presence of Refrigerant

 

The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially toxic or flammable  

 

atmospheres. Ensure that the leak detection equipment being used is suitable for use with all applicable refrigerants, i.e. non-sparking, adequately sealed or   

 

intrinsically safe.

  Presence of Fire Extinguisher

 

If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment shall be available to hand.   

 

Have a dry powder or CO2 fire extinguisher adjacent to the charging area.

  No Ignition Sources

 

No person carrying out work in relation to a refrigeration system which involves exposing any pipe work shall use any sources of ignition in such a manner that  

 

it may lead to the risk of fire or explosion. All possible ignition sources, including cigarette smoking, should be kept sufficiently far away from the site of installa- 

 

tion, repairing, removing and disposal, during which refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around  

 

the equipment is to be surveyed to make sure that there are no flammable hazards or ignition risks. "No Smoking" signs shall be displayed.

  Ventilated Area

 

Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. A degree of ventilation shall   

 

continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it externally into the  

 atmosphere.

  Checks on the Refrigeration Equipment

 

Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance  

 

and service guidelines shall be followed. If in doubt, consult the manufacturer's technical department for assistance.

 

The following checks shall be applied to installations using flammable refrigerants: 

 

  • The charge size is in accordance with the room size within which the refrigerant containing parts are installed.

 

  • The ventilation machinery and outlets are operating adequately and are not obstructed.

 

  • If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant.

 

  • Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected.

 

  • Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing  

 

    components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being cor- 

     roded.

  Checks on Electrical Devices

 

Repair and maintenance to electrical components shall include initial safety checks and component inspection procedures. If a fault exists that could compro-

 

mise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is nec-

 

essary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.

 

Initial safety checks shall include that: 

 

  • capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;

 

  • no live electrical components and wiring are exposed while charging, recovering or purging the system;

 

  • there is continuity of earth bonding

2.  Repairs to Sealed Components

  During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers,  

 

etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located  

 

at the most critical point to warn of a potentially hazardous situation.

  Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of 

 

protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, 

 

incorrect fitting of glands, etc.

 

Ensure that the apparatus is mounted securely.

 

Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres.  

 

Replacement parts shall be in accordance with the manufacturer's specifications.

3.  Repair to intrinsically Safe Components

 

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted  

 

for the equipment in use.

 

Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the  

 

correct rating.

 

Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak.

4. Cabling

 

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall 

 

also take into account the effects of aging or continual vibration from sources such as compressors or fans.

OBH823

Содержание MUZ-HR25

Страница 1: ...ATION 6 5 NOISE CRITERIA CURVES 7 6 OUTLINES AND DIMENSIONS 9 7 WIRING DIAGRAM 10 8 REFRIGERANT SYSTEM DIAGRAM 12 9 PERFORMANCE CURVES 14 10 ACTUATOR CONTROL 28 11 SERVICE FUNCTIONS 29 12 TROUBLESHOOTING 30 13 DISASSEMBLY INSTRUCTIONS 51 MUZ HR42VF MUZ HR50VF Models MUZ HR25VF E1 ER1 ET1 MUZ HR35VF E1 ER1 ET1 MUZ HR42VF E1 ER1 ET1 MUZ HR50VF E1 ER1 ET1 Indoor unit service manual MSZ HR VF Series O...

Страница 2: ...ater into the electric parts Do not touch the refrigerant Do not touch the hot or cold areas in the refrigeration cycle When the repair or the inspection of the circuit needs to be done without turning off the power exercise great caution not to touch the live parts Use the specified refrigerant only Never use any refrigerant other than that specified Doing so may cause a burst an explosion or fir...

Страница 3: ...ng changed they shall be fit for the purpose and to the correct specification At all times the manufacturer s maintenance and service guidelines shall be followed If in doubt consult the manufacturer s technical department for assistance The following checks shall be applied to installations using flammable refrigerants The charge size is in accordance with the room size within which the refrigera...

Страница 4: ...ely familiar with the equipment and all its detail It is recommended good practice that all refrigerants are recovered safely Prior to the task being carried out an oil and refrigerant sample shall be taken in case analysis is required prior to re use of reclaimed refrigerant It is essential that electrical power is available before the task is commenced a Become familiar with the equipment and it...

Страница 5: ...Air inlet Back and side MUZ HR25VF MUZ HR35VF PART NAMES AND FUNCTIONS 3 ACCESSORIES MODELS MUZ HR25VF MUZ HR35VF MUZ HR42VF MUZ HR50VF Drain socket 1 MUZ HR42VF MUZ HR50VF Air outlet Drain outlet Piping Drain hose Air inlet back and side OBH823 ...

Страница 6: ...oil Model L 0 27 FW68S 0 35 FW68S Fan motor Model RC0J55 DC Current 1 Cooling A 0 24 0 23 0 20 Heating 0 24 0 23 Dimensions W H D mm 699 538 249 800 550 285 Weight kg 23 24 34 35 Special remarks Dehumidification Cooling L h 0 8 1 1 1 6 2 0 Air flow 1 Cooling High m3 h 1 818 1 932 2 058 Low 990 1 050 906 Heating High 1 932 2 052 1 962 Med 1 680 1 788 1 686 Low 1 356 1 452 1 260 Sound level 1 Coolin...

Страница 7: ...transistor Q821 30 37 A 600 V Current limiting PTC thermistor PTC64 33 Ω PTC65 33 Ω Terminal block TB1 5 P Relay X63 3 A 250 V X64 20 A 250 V R V coil 21S4 220 240 V AC 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR BAND CENTER FREQUENCIES Hz COOLING FUNCTION SPL dB A LINE HEATING 50 50 NC 10...

Страница 8: ... 10 51 MUZ HR42VF 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 OCTAVE BAND SOUND PRESSURE LEVEL dB re 0 0002 MICRO BAR BAND CENTER FREQUENCIES Hz COOLING FUNCTION SPL dB A LINE HEATING 50 NC 10 51 MUZ HR50VF Test conditions Cooling Dry bulb temperature 35 C Wet bulb temperature 24 C Heating Dry bulb temperature 7 C Wet bulb temperature 6 C OUTDO...

Страница 9: ...9 Unit mm MUZ HR25VF MUZ HR35VF OUTLINES AND DIMENSIONS 6 MUZ HR35VF MUZ HR42VF MUZ HR50VF OBH823 ...

Страница 10: ...10 WIRING DIAGRAM 7 MUZ HR25VF E1 ER1 MUZ HR35VF E1 ER1 MUZ HR25VF ET1 MUZ HR35VF ET1 OBH823 ...

Страница 11: ...11 MUZ HR42VF E1 ER1 MUZ HR50VF E1 ER1 MUZ HR42VF ET1 MUZ HR50VF ET1 OBH823 ...

Страница 12: ...ermistor RT68 Stop valve with service port Muffler REFRIGERANT SYSTEM DIAGRAM 8 MUZ HR25VF MUZ HR35VF MUZ HR42VF MUZ HR50VF Outdoor heat exchanger Flared connection Defrost thermistor RT61 Discharge temperature thermistor RT62 Flared connection Stop valve With strainer Stop valve with service port Refrigerant flow in cooling Compressor 4 way valve Refrigerant flow in heating Refrigerant pipe ø9 52...

Страница 13: ...2 50VF 20 12 9 52 6 35 ADDITIONAL REFRIGERANT CHARGE R32 g Model Outdoor unit precharged Refrigerant piping length one way 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m MUZ HR25VF 400 0 20 40 60 80 100 120 140 160 260 MUZ HR35VF 450 MUZ HR42VF 700 MUZ HR50VF 800 Calculation X g 20 g m Refrigerant piping length m 7 NOTE Refrigerant piping exceeding 7 m requires additional refrigerant charge accord...

Страница 14: ...e indoor air intake as shown in the figure and at least 2 sets of wet and dry bulb thermometers to the indoor air outlet The thermometers must be attached to the position where air speed is high 2 Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake Cover the thermometers to prevent direct rays of the sun 3 Check that the air filter is cleaned 4 Open windows and doors ...

Страница 15: ...7 5 22 4 20 7 19 0 17 2 15 5 13 8 12 1 10 3 8 6 6 9 MUZ HR25VF MUZ HR50VF MUZ HR42VF MUZ HR35VF Outdoor intake air Wet bulb temperature C 20 15 10 5 0 5 10 15 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 Heating capacity at Rated frequency Capacity correction factor 15 20 26 Indoor intake air Dry bulb temperature Indoor air Dry bulb temperature difference C 20 4 18 8 17 3 15 7 14 1 12 6 11 0 9 4 7 8 6 ...

Страница 16: ...tion factors The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz The operational frequency of compressor Hz Correction of Cooling capacity The operatio...

Страница 17: ... RUN OPERATION Refer to 9 3 9 4 OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT Dry bulb temperature C Relative humidity 20 50 25 60 30 70 9 3 HOW TO OPERATE FIXED FREQUENCY OPERATION Test run operation 1 Press EMERGENCY OPERATION switch to start COOL or HEAT mode COOL Press once HEAT Press twice 2 Test run operation starts and continues to operate for 30 minutes 3 Compressor operates at rated frequ...

Страница 18: ...R25VF Outdoor unit current MUZ HR42VF MUZ HR50VF 0 5 10 15 20 25 1 5 2 0 2 5 3 0 0 5 10 15 20 25 4 5 5 0 5 5 6 0 0 5 10 15 20 25 2 0 2 5 3 0 3 5 4 0 0 5 10 15 20 25 2 0 2 5 3 0 3 5 4 0 Ambient temperature C Outdoor current A Ambient temperature C Outdoor current A Ambient temperature C Outdoor current A Ambient temperature C Outdoor current A MUZ HR35VF MUZ HR25VF Outdoor unit current MUZ HR42VF M...

Страница 19: ... 792 27 24 3 35 1 61 0 48 728 3 23 1 55 0 48 768 3 15 1 51 0 48 792 3 05 1 46 0 48 832 27 26 3 45 1 24 0 36 768 3 35 1 21 0 36 808 3 30 1 19 0 36 832 3 20 1 15 0 36 856 28 18 2 94 2 59 0 88 640 2 81 2 48 0 88 672 2 70 2 38 0 88 704 2 60 2 29 0 88 736 28 20 3 06 2 33 0 76 672 2 94 2 23 0 76 712 2 85 2 17 0 76 728 2 75 2 09 0 76 760 28 22 3 19 2 04 0 64 696 3 08 1 97 0 64 740 3 00 1 92 0 64 760 2 88...

Страница 20: ... 896 2 38 1 43 0 60 928 27 24 2 88 1 38 0 48 880 2 70 1 30 0 48 920 2 55 1 22 0 48 960 27 26 3 03 1 09 0 36 912 2 85 1 03 0 36 952 2 68 0 96 0 36 992 28 18 2 45 2 16 0 88 784 2 25 1 98 0 88 832 2 08 1 83 0 88 864 28 20 2 58 1 96 0 76 816 2 40 1 82 0 76 856 2 23 1 69 0 76 904 28 22 2 73 1 74 0 64 848 2 55 1 63 0 64 896 2 38 1 52 0 64 928 28 24 2 88 1 50 0 52 880 2 70 1 40 0 52 920 2 55 1 33 0 52 96...

Страница 21: ...7 24 4 56 2 19 0 48 1101 4 39 2 11 0 48 1162 4 28 2 06 0 48 1198 4 15 1 99 0 48 1258 27 26 4 69 1 69 0 36 1162 4 56 1 64 0 36 1222 4 49 1 62 0 36 1258 4 35 1 57 0 36 1295 28 18 4 00 3 52 0 88 968 3 83 3 37 0 88 1016 3 67 3 23 0 88 1065 3 54 3 11 0 88 1113 28 20 4 17 3 17 0 76 1016 4 00 3 04 0 76 1077 3 88 2 95 0 76 1101 3 74 2 84 0 76 1150 28 22 4 34 2 77 0 64 1053 4 18 2 68 0 64 1119 4 08 2 61 0 ...

Страница 22: ...3 23 1 94 0 60 1404 27 24 3 91 1 88 0 48 1331 3 67 1 76 0 48 1392 3 47 1 66 0 48 1452 27 26 4 11 1 48 0 36 1379 3 88 1 40 0 36 1440 3 64 1 31 0 36 1500 28 18 3 33 2 93 0 88 1186 3 06 2 69 0 88 1258 2 82 2 48 0 88 1307 28 20 3 50 2 66 0 76 1234 3 26 2 48 0 76 1295 3 03 2 30 0 76 1367 28 22 3 71 2 37 0 64 1283 3 47 2 22 0 64 1355 3 23 2 07 0 64 1404 28 24 3 91 2 03 0 52 1331 3 67 1 91 0 52 1392 3 47...

Страница 23: ...27 24 5 63 2 48 0 44 1219 5 42 2 38 0 44 1286 5 29 2 33 0 44 1327 5 12 2 25 0 44 1394 27 26 5 80 1 85 0 32 1286 5 63 1 80 0 32 1353 5 54 1 77 0 32 1394 5 38 1 72 0 32 1434 28 18 4 94 4 15 0 84 1072 4 73 3 97 0 84 1126 4 54 3 81 0 84 1179 4 37 3 67 0 84 1233 28 20 5 15 3 70 0 72 1126 4 94 3 55 0 72 1193 4 79 3 45 0 72 1219 4 62 3 33 0 72 1273 28 22 5 36 3 21 0 60 1166 5 17 3 10 0 60 1240 5 04 3 02 ...

Страница 24: ...3 99 2 23 0 56 1554 27 24 4 83 2 13 0 44 1474 4 54 2 00 0 44 1541 4 28 1 88 0 44 1608 27 26 5 08 1 63 0 32 1528 4 79 1 53 0 32 1595 4 49 1 44 0 32 1662 28 18 4 12 3 46 0 84 1313 3 78 3 18 0 84 1394 3 49 2 93 0 84 1447 28 20 4 33 3 11 0 72 1367 4 03 2 90 0 72 1434 3 74 2 69 0 72 1514 28 22 4 58 2 75 0 60 1420 4 28 2 57 0 60 1501 3 99 2 39 0 60 1554 28 24 4 83 2 32 0 48 1474 4 54 2 18 0 48 1541 4 28...

Страница 25: ...27 24 6 70 2 88 0 43 1866 6 45 2 77 0 43 1968 6 30 2 71 0 43 2030 6 10 2 62 0 43 2132 27 26 6 90 2 14 0 31 1968 6 70 2 08 0 31 2071 6 60 2 05 0 31 2132 6 40 1 98 0 31 2194 28 18 5 88 4 88 0 83 1640 5 63 4 67 0 83 1722 5 40 4 48 0 83 1804 5 20 4 32 0 83 1886 28 20 6 13 4 35 0 71 1722 5 88 4 17 0 71 1825 5 70 4 05 0 71 1866 5 50 3 91 0 71 1948 28 22 6 38 3 76 0 59 1784 6 15 3 63 0 59 1896 6 00 3 54 ...

Страница 26: ...4 75 2 61 0 55 2378 27 24 5 75 2 47 0 43 2255 5 40 2 32 0 43 2358 5 10 2 19 0 43 2460 27 26 6 05 1 88 0 31 2337 5 70 1 77 0 31 2440 5 35 1 66 0 31 2542 28 18 4 90 4 07 0 83 2009 4 50 3 74 0 83 2132 4 15 3 44 0 83 2214 28 20 5 15 3 66 0 71 2091 4 80 3 41 0 71 2194 4 45 3 16 0 71 2317 28 22 5 45 3 22 0 59 2173 5 10 3 01 0 59 2296 4 75 2 80 0 59 2378 28 24 5 75 2 70 0 47 2255 5 40 2 54 0 47 2358 5 10...

Страница 27: ...2 41 858 2 84 946 3 31 1014 3 78 1063 4 21 1092 4 68 1121 MUZ HR42VF CAPACITY 4 70 kW INPUT 1300 W INDOOR DB C OUTDOOR WB C 10 5 0 5 10 15 20 Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT 15 2 96 845 3 57 1014 4 18 1144 4 79 1235 5 41 1313 5 97 1352 6 58 1378 21 2 82 910 3 38 1079 4 00 1196 4 56 1287 5 17 1352 5 73 1391 6 32 1443 26 2 54 975 3 15 1144 3 71 1261 4 32 1352 4 94 1417 5 50 1...

Страница 28: ...er the compressor has stopped running 10 3 RELATION BETWEEN MAIN SENSOR AND ACTUATOR Sensor Purpose Actuator Compressor LEV Outdoor fan motor R V coil Indoor fan motor Defrost heater Discharge temperature thermistor Protection Indoor coil temperature thermistor Cooling Coil frost prevention Heating High pressure protec tion Defrost thermistor Heating Defrosting Fin temperature thermistor Protectio...

Страница 29: ... of the compressor at low outside temperature The pre heat control prevents this interference The pre heat control turns ON when the discharge temperature thermis tor is 20 C or below When the pre heat control turns ON the compressor is energized About 50 W Pre heat control setting JK ON To activate the pre heat control cut the JK wire of the inverter P C board OFF To deactivate the pre heat contr...

Страница 30: ...4 When removing the electronic control P C board hold the edge of the board with care NOT to apply stress on the components 5 When connecting or disconnecting the connectors hold the connector housing DO NOT pull the lead wires TROUBLESHOOTING 12 3 Troubleshooting procedure 1 Check if the OPERATION INDICATOR lamp on the indoor unit is blinking on and off to indicate an abnormality To make sure che...

Страница 31: ... Does the left lamp on the indoor unit stay ON for 3 seconds When it stays ON for 3 seconds without beep The outdoor unit is abnormal The indoor unit is abnormal Check the blinking pattern and identify the abnormal point by referring to the table of indoor unit failure mode recall function Refer to indoor unit service manual Make sure to check at least 2 consecutive blinking cycles 2 Releasing the...

Страница 32: ...he failure mode recall function Release the failure mode recall function by the following procedures Turn OFF the power supply and turn it ON again Press RESET button of the remote controller Repair the failure parts The outdoor unit is normal Release the failure mode recall function accord ing to the left mentioned procedure Deleting the memorized abnormal condition After repairing the unit recal...

Страница 33: ...ge current flows into power module IC700 Reconnect compressor connector Refer to 12 5 How to check inverter compressor Check stop valve Compressor synchronous abnormality Compressor start up failure protection 12 time blink 2 5 seconds OFF Waveform of compressor current is distorted Reconnect compressor connector Refer to 12 5 How to check inverter compressor 5 time blink 2 5 seconds OFF Discharge...

Страница 34: ... How to check inverter compressor Each phase current of compressor 9 time blink 2 5 seconds OFF Each phase current of compressor cannot be detected normally 14 time blink or more 2 5 seconds OFF Stop valve Closed valve 14 time blink 2 5 seconds OFF Closed valve is detected by compressor current Check stop valve 4 way valve Pipe temperature 16 time blink 2 5 seconds OFF The 4 way valve does not wor...

Страница 35: ... refrig erant amount Refer to 12 5 Check of LEV 11 4 time blink 2 5 seconds OFF Fin temperature P C board tem perature thermistor overheat protection Temperature of fin temperature thermistor on the heat sink exceeds 75 86 C or temperature of P C board temperature thermistor on the inverter P C board exceeds 72 85 C Check around outdoor unit Check outdoor unit air passage Refer to 12 5 Check of ou...

Страница 36: ...ction PAM pro tection will be activated in the fol lowing cases 1 Instantaneous power voltage drop Short time power failure 2 When the power supply voltage is high 23 9 time blink 2 5 seconds OFF Inverter check mode The connector of compressor is disconnected inverter check mode starts Check if the connector of the com pressor is correctly connected Refer to 12 5 How to check inverter compressor N...

Страница 37: ...nt diagram and voltage 1 Inverter P C board for the chart of thermistor Compressor Measure the resistance between terminals using a tester Temperature 10 40 C Normal Ω MUZ HR25 35VF MUZ HR42 50VF U V U W V W 1 59 2 16 0 82 1 11 W U V WHT RED BLK Outdoor fan motor Measure the resistance between lead wires using a tester Temperature 10 40 C Color of lead wire Normal Ω MUZ HR25 35VF MUZ HR42 50VF RED...

Страница 38: ...50 130 V The voltage may differ according to the tester Operation method Start cooling or heating operation by pressing EMERGENCY OPERATION switch on the indoor unit TEST RUN OPERA TION Refer to 9 3 Measurement point At 3 points BLK U WHT V BLK U RED W WHT V RED W NOTE 1 Output voltage varies according to power supply voltage 2 Measure the voltage by analog type tester 3 During this check LED of t...

Страница 39: ... TEST RUN OPERATION Refer to 9 3 Measurement Measure the time from the start of compressor to the stop of compressor due to overcurrent Compressor starts Abnormal IC700 failure Compressor winding short Abnormal Compressor lock out Starting defect Abnormal Poor contact Inverter P C board defect Disconnected connector Abnormal Refrigerant circuit defect Closed valve Normal 0 second 1 second 2 second...

Страница 40: ... minutes or more without showing thermistor abnormality OK Cause is poor contact Yes Yes Disconnect the connector of thermistor in the inverter P C board see below table and measure the resistance of thermistor Thermistor Symbol Connector Pin No Board Defrost RT61 Between CN641 pin1 and pin2 Inverter P C board Discharge temperature RT62 Between CN641 pin3 and pin4 Fin temperature RT64 Between CN64...

Страница 41: ...lace the inverter P C board Replace the 4 way valve Unit operates COOL mode even if it is set to HEAT mode Is there 230 V AC between CN721 and on the inverter P C board 3 minutes after the power supply is turned ON Yes No Replace the inverter P C board Replace the 4 way valve Unit operates HEAT mode even if it is set to COOL mode Disconnect connector between the compressor and the IGBT module IC70...

Страница 42: ...easure the voltage of CN931 Between 1 and 5 Between 2 and 5 Between 3 and 5 Does the voltage between each terminal become 5 and 0 V DC repeatedly Does the outdoor fan motor rotate smoothly Replace the outdoor fan motor Replace the inverter P C board Yes Yes No Fixed to either 5 or 0 V DC No No Yes Disconnect the connectors CN931 and CN932 from the inverter P C board Check the connection between th...

Страница 43: ...amp on the indoor unit light up Does LED on the inverter P C board light up or blink Refer to 12 6 1 No Replace the inverter P C board Is there bus bar voltage 260 370 V DC between DB61 and DB61 on the inverter P C board Refer to 12 6 1 No Check the electric parts in main circuit Yes Yes No Disconnect the connector between the compressor and the power module IC700 Turn ON power supply and press EM...

Страница 44: ...tage by an analog tester Properly fix the LEV coil to the expansion valve Replace the inverter P C board Replace the LEV coil Replace the expansion valve Is LEV coil properly fixed to the expansion valve Does the resistance of LEV coil have the characteristics Refer to 12 4 Do you hear the expansion valve click click Do you feel the expansion valve vibrate when touching it Turn ON the power supply...

Страница 45: ...door fan motor If the connection is poor make it correct Operate the outdoor unit by starting EMERGENCY OPERATION Check the LED indication on the in verter P C board Does the LED blink 10 times Replace the inverter P C board Check the corresponding parts following LED indication Refer to 12 3 Yes No Yes 10 time blink No L Check of inverter P C board OBH823 ...

Страница 46: ...t them No A Turn OFF the power supply Check once more if the indoor outdoor connecting wire is not miswiring Bridge the outdoor terminal block S2 and S3 1 B 1 Miswiring may damage indoor electronic control P C board during the operation Be sure to confirm the wiring is correct before the opera tion starts Turn ON the power supply Does the LED on the inverter P C board repeat 3 6 second OFF and 0 8...

Страница 47: ...air trapped in the refrigerant circuit Close the stop valve and disconnect the power plug or turn the breaker OFF The unit occasionally stops when the stop valve is opened or closed during operation Open the stop valve and start the cooling operation again Yes No The refrigerant gas amount may be 60 or less than the normal amount Identify where the gas is leaking from and fix the leak CAUTION Do n...

Страница 48: ...he installation condition combination of specific conditions such as antennas or wiring Check the following before asking for service 1 Devices affected by the electromagnetic noise TV sets radios FM AM broadcast shortwave 2 Channel frequency broadcast station affected by the electromagnetic noise 3 Channel frequency broadcast station unaffected by the electromagnetic noise 4 Layout of indoor outd...

Страница 49: ...rive outdoor fan motor CN932 R V coil 21S4 CN721 Smoothing capacitor C62 Fuse F701 T3 15AL250V Outdoor heat exchanger RT68 CN644 Ambient tem peraturer RT65 CN643 Fuse F901 T3 15AL250V 20 10 0 10 20 30 40 0 10 20 30 40 50 60 70 80 90 100 Temperature C Defrost thermistor RT61 Ambient temperature thermistor RT65 Outdoor heat exchanger temperature thermistor RT68 Temperature C Discharge temperature th...

Страница 50: ...4 CN642 Ambient temperature thermistor RT65 CN643 Discharge temperature thermistor RT62 CN641 Defrost thermistor RT61 CN641 DB61 260 370 V DC Front side of unit 230 V AC Output to drive compressor LDU LDV LDW Fuse F701 T3 15AL250V R V coil 21S4 CN721 230 V AC Jumper wire for changing defrost setting JS Signal of outdoor fan motor CN931 230 V AC Outdoor heat exchanger temperature thermistor RT68 CN...

Страница 51: ...inal with this connector shown below has the locking mechanism Slide the sleeve Pull the terminal while pushing the locking lever Hold the sleeve and pull out the terminal slowly Connector Sleeve Locking lever Detaching method of the terminal with locking mechanism The terminal which has the locking mechanism can be detached as shown below There are following 2 types of the terminal with locking m...

Страница 52: ... screws of the earth wire and the terminal block support 7 Remove the screw of the terminal block and remove the terminal block 8 Remove the heat sink support from the P C board support 9 Unhook the catch of the inverter P C board and remove the inverter P C board from the P C board support 3 Removing the R V coil 1 Remove the cabinet and the panels Refer to section 1 2 Disconnect the following co...

Страница 53: ...to 9 5 Pull out the outdoor heat exchanger temperature ther mistor from its holder 6 Pull out the ambient temperature thermistor from its holder 5 Removing the outdoor fan motor 1 Remove the cabinet and the panels Refer to section 1 2 Disconnect the following connectors Inverter P C board CN931 CN932 Fan motor 3 Remove the fan motor lead wire from where it is fas tened on the separator 4 Remove th...

Страница 54: ...move the terminal cover and the compressor lead wire 7 Recover gas from the refrigerant circuit NOTE Recover gas from the pipes until the pressure gauge shows 0 kg cm2 0 MPa 8 Detach the brazed part of the suction and the dis charge pipe connected with the compressor 9 Detach the brazed part of pipes connected with the 4 way valve 10 Remove the nuts of compressor legs 11 Remove the compressor 54 P...

Страница 55: ...ng wire 4 Remove the screws fixing the top panel 5 Remove the top panel 6 Remove the screws fixing the cabinet 7 Remove the cabinet 8 Remove the screws fixing the back panel 9 Remove the back panel Photo 1 Photo 2 55 Back panel Service panel Screws of the cabinet Screws of the top panel Screw of the cabinet Screws of the back panel Screws of the terminal block support and the back panel Screws of ...

Страница 56: ... panels Refer to section 1 2 Disconnect the following connectors Inverter P C board CN721 R V coil 3 Remove the R V coil 4 Removing the discharge temperature thermistor defrost thermistor outdoor heat exchanger tempera ture thermistor and ambient temperature thermistor 1 Remove the cabinet and panels Refer to section 1 2 Disconnect the lead wire to the reactor and the following con nectors Inverte...

Страница 57: ...tion 2 3 Recover gas from the refrigerant circuit NOTE Recover gas from the pipes until the pressure gauge shows 0 kg cm2 0 MPa 4 Detach the brazed part of the suction and the discharge pipe connected with compressor 5 Remove the nuts of compressor legs 6 Remove the compressor 7 Detach the brazed part of pipes connected with 4 way valve 7 Removing the LEV assembly 1 Detaching the brazed part of pi...

Страница 58: ...ICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Copyright 2018 MITSUBISHI ELECTRIC CORPORATION Published Oct 2018 No OBH823 Made in Japan Specifications are subject to change without notice ...

Отзывы: