background image

VG79A008H02

SPLIT-TYPE AIR CONDITIONERS
Models

MS12/15/17TN

Series

MSH12/15TN

[FLARE CONNECTION TYPE]

1. THE FOLLOWING SHOULD ALWAYS BE

OBSERVED FOR SAFETY

Please report to your supply authority or obtain their consent before connecting
this equipment to the power supply system.

Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR
SAFETY” before installing the air conditioner.

Be sure to observe the cautions specified here as they include important items
related to safety.

The indications and meanings are as follows.

 WARNING

Could lead to death, serious injury, etc.

 CAUTION

Could lead to serious injury in particular environments when operated incorrectly.

After reading this manual, be sure to keep it together with the OPERATING
INSTRUCTIONS in a handy place on the customer’s site.

 WARNING

Do not install the unit by yourself (customer).

Incomplete installation could cause injury due to fire, electric shock, the unit
falling or leakage of water. Consult the dealer from whom you purchased the
unit or special installer.

Install the unit securely in a place which can bear the weight of the unit.

When installed in an insufficient strong place, the unit could fall causing injury.

Use the indoor/outdoor unit connecting wire that meets the Standards to
connect the indoor and outdoor units and fix the wire to the terminal
block securely so that no external force is conveyed to the connecting
section of the terminal block.

Incomplete connection or fixing of the wire could result in a fire.

Do not use intermediate connection of the power cord or the extension
cord and do not connect many devices to one AC outlet.

It could cause a fire or an electric shock due to defective contact, defective
insulation, exceeding the permissible current, etc.

Check that the refrigerant gas do not leak after installation has com-
pleted.

Perform the installation securely referring to the installation manual.

Incomplete installation could cause a personal injury due to fire, electric
shock, the unit falling or leakage of water.

Perform electrical work according to the installation manual and be sure
to use an exclusive circuit.

If the capacity of the power circuit is insufficient or there is incomplete
electrical work, it could result in a fire or an electric shock.

Attach the electrical cover to the indoor unit and the service panel to the
outdoor unit securely.

If the electrical cover in the indoor unit and/or the service panel in the outdoor
unit are not attached securely, it could result in a fire or an electric shock due
to dust, water, etc.

Be sure to use the part provided or specified parts for the installation
work.

The use of defective parts could cause an injury due to a fire, an electric
shock, the unit falling, leakage of water, etc.

Be sure to cut off the main power in case of setting up the indoor
electronic control P.C. board or wiring works.

It could cause an electric shock.

 CAUTION

Ground the unit.

Do not connect the ground to a gas pipe, water pipe, lightning rod or
telephone ground. Defective grounding could cause an electric shock.

Do not install the unit in a place where an inflammable gas leaks.

If gas leak and accumulate in the area surrounding the unit, it could cause an
explosion.

Install a ground leakage breaker depending on the installation place
(Where it is humid).

If a ground leakage breaker is not installed, it could cause an electric shock.

Perform the drainage/piping work securely according to the installation
manual.

If there is a defect in the drainage/piping work, water could drop from the unit
and household goods could be wet and damaged.

2. SELECTING THE INSTALLATION LOCATION

2-1 INDOOR UNIT

Where airflow is not blocked.

Where cool air spreads over the entire room.

Maximum refrigerant piping length between indoor unit and outdoor unit is 49 ft.
and the difference of height of both units is 25 ft. maximum.

Rigid wall without vibration.

Where it is not exposed to direct sunshine.

Where easily drained.

At a distance 3 ft. or more away from your TV and radio (to prevent picture from
being distorted or noise from being generated).

In a place as far away as possible from fluorescent and incandescent lights (so
the infrared remote control can operate the air conditioner normally).

Where the air filter can be removed and replaced easily.

2-2 OUTDOOR UNIT

Where it is not exposed to strong wind.

Where airflow is good and dustless.

Where it is not exposed to rain and direct sunshine.

Where neighbours are not annoyed by operation sound or hot air.

Where rigid wall or support is available to prevent the increase of operation sound
or vibration.

Where there is no risk of combustible gas leakage.

When installing the unit at a high level, be sure to fix the unit legs.

Where it is at least 10 ft. away from the antenna of TV set or radio. (Otherwise,
images would be disturbed or noise would be generated.)

Install the unit horizontally.

 CAUTION

Avoid the following places for installation where air conditioner trouble is liable to
occur.

Where there is too much machine oil.

Salty environment as seaside areas.

Hot-spring areas.

Where sulfide gas exists.

Other special atmospheric areas.

2-3 WIRELESS REMOTE CONTROLLER MOUNTING

Place of mounting

Where it is easy to operate and easily visible.

Where children can not touch.

Mounting

Select a position about 4 ft. above the floor, check that signals from the remote
controller are surely received by the indoor unit from that position (‘beep’ or ‘beep-
beep’ receiving tone sounds). After that, attach remote controller mounting
hardware 

3

 to a pillar or wall and set the wireless remote controller 

6

.

In rooms where inverter type fluorescent lamps are used, the signal from the
wireless remote controller may not be received.

ADVANCED AND EVER ADVANCING

INSTALLATION MANUAL

Содержание MS12

Страница 1: ... main power in case of setting up the indoor electronic control P C board or wiring works It could cause an electric shock CAUTION Ground the unit Do not connect the ground to a gas pipe water pipe lightning rod or telephone ground Defective grounding could cause an electric shock Do not install the unit in a place where an inflammable gas leaks If gas leak and accumulate in the area surrounding t...

Страница 2: ...s on both indoor and outdoor sides Remove the valve cover of the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoor and outdoor units Limits Pipe length 49 ft max Height difference 25 ft max No of bends 10 max Refrigerant adjustment If pipe length exceeds 25 ft additional refrigerant R 22 charge is required The outdoor unit is charged with refrigerant for pipe leng...

Страница 3: ...te controller Wireless Indoor unit Outdoor unit DC12V Polar ELECTRICAL SPECIFICATIONS MODEL MSH12TN MSH15TN INDOOR UNIT Power supply V PHASE Hz 115 1 60 115 1 60 Min Circuit Ampacity 0 6 0 6 Fan motor F L A 0 43 0 43 OUTDOOR UNIT Power supply V PHASE Hz 208 230 1 60 208 230 1 60 Max Fuse size time delay A 15 20 Min Circuit Ampacity 14 14 Fan motor F L A 0 42 0 52 Compressor R L A 10 0 10 0 L R A 3...

Страница 4: ...rminal MU12TN and MUH12TN MU15 17TN and MUH15TN Conduit cover Connector Lock nut Service panel Grounding terminal Connect wires to the matching numbers of terminals Remark Indoor unit can also be powered from an independent power supply Max Fuse size time delay 15 A In this case these indoor outdoor connecting wires for indoor power supply are not necessary A disconnect switch may be required Chec...

Страница 5: ...at the same time that a power has restored If the unit has been off with the remote controller before power failure the auto restart function does not work as the power button of the remote controller is off To prevent breaker off due to the rush of starting current systematize other home appliances not to turn on at the same time 4 5 PIPE FORMING Place the drain hose below the refrigerant piping ...

Страница 6: ...the same method as the indoor unit For tightening use the same tightening torque applied for indoor unit and tighten the flare nut with torque wrench or spanner INSULATION AND TAPING 1 Cover piping joints with pipe cover 2 For outdoor unit side surely insulate every piping including valves 3 Using piping tape G apply taping starting from the entry of outdoor unit Fix the end of piping tape G with ...

Страница 7: ... to which the drain hose is to be attached at the rear right of the indoor unit Insert the drain hose fully into the drain pan Check if the hose is hooked securely to the projection of its inserting part at the drain pan INDOOR UNIT INSTALLATION Insert the drain hose into the wall hole sleeve C and hook the upper part of indoor unit on the installation plate 1 Then move the unit to the very edge o...

Страница 8: ...rated with the remote controller both the test run and the emergency operation are released by commands from the remote controller Once the compressor stops the restart preventive device operates so the compressor will not operate for three minutes to protect the air conditioner 6 5 EXPLANATION TO THE CUSTOMER Using the OPERATING INSTRUCTIONS explain the following to the customer how to control te...

Отзывы: