NOTE : Coil frost prevention during COOL mode of “I FEEL CONTROL”
There are two types of controls in coil frost prevention.
①
Temperature control
<MS-/0709/12> When the indoor coil thermistor RT12 reads 4°C or below for 5 minutes, the coil frost prevention mode
starts.
<MS-18/24> When the indoor coil thermistor RT12 reads -1°C or below, the coil frost prevention mode starts immediately.
However, the coil frost prevention only works after 5 minutes from the compressor starts.
The compressor stops and the indoor fan operates at the set speed for 5 minutes.
After that, if RT12still reads below 4°C (MS-07/09/12) or below -1°C (MS-18/24) this mode prolonged until the RT12 reads
over 4°C (MS-07/09/12) or -1°C (MS-18/24).
②
Time control
When the three conditions below have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.
a. Compressor has been continuously operating.
b. Indoor fan speed is Lo or Me.
c. Room temperature is below 26°C.
When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts
from the beginning.
Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds
26°C. However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.
●
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
Followings are the fan speed in AUTO.
Initial temperature difference
Room temperature minus set temperature : 2 degrees or more············································Hi
Room temperature minus set temperature : 1 degree or more and less than 2 degrees·····Me
Room temperature minus set temperature : less than 1 degree···········································Lo
—DRY mode of “I FEEL CONTROL”—
The system for dry operation uses the same refrigerant circuit as the cooling circuit.
The compressor and the indoor fan are controlled by the temperature and the microprocessor.
By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature
decrease.
The operation of the compressor and indoor fan is as follows.
1. When the room temperature is 23°C or over:
Compressor operates by temperature control and time control.
①
Set temperature is controlled to fall 2°C as initial set temperature.
②
When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
Indoor fan and outdoor fan operate in the same cycle as the compressor.
2. When the room temperature is under 23°C.
When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF.
When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.
1 deg. 1.66 deg.
2 deg. 4 deg.
— COOL mode of “I FEEL CONTROL” —
Compressor and
outdoor fan motor
OFF
ON
Run continuously in cooling mode
Indoor fan motor
ON
ON
OFF
Fan speed