INSTALLATION MANUAL

For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing
the air-conditioner unit.

MANUAL DE INSTALACIÓN

Para un uso correcto y seguro, lea detalladamente este manual y el manual de instalación de la unidad interior
antes de instalar la unidad de aire acondicionado.

Air-Conditioners

PUZ-A·NHA, PUZ-A·NHA-BS
PUY-A·NHA, PUY-A·NHA-BS

FOR INSTALLER

PARA EL INSTALADOR

 BG79U896H01_cover

05.11.10, 11:46 AM

1

Содержание Mr.Slim PUY-A NHA

Страница 1: ...indoor unit installation manual thoroughly before installing the air conditioner unit MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Air Conditioners PUZ A NHA PUZ A NHA BS PUY A NHA PUY A NHA BS FOR INSTALLER PARA EL INSTALADOR ...

Страница 2: ...ure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Consult a dealer for repairs If alterations or repairs are not performed correctly water leakage electric shock or fire m...

Страница 3: ...kylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessa...

Страница 4: ...an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for A42 models is 1000 mm 39 3 8 inch or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for upward airflow the clearance is 500 1000 mm 19 11 16 39 3 8 inch or m...

Страница 5: ...occur When bending the pipes be careful not to break them Bend radii of 100 mm 3 15 16 inch to 150 mm 5 27 32 inch are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result 1 Pipes must be connected starting from the indoor unit Flare nuts must be tightened with a torque wrench 2 Flare the liquid pipes and gas pipes and apply a thin layer of refrigerat...

Страница 6: ...ps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result I Double spanner section Do not apply a spanner other than to this sec tion Doing so would cause coolant leaks J Seal section Seal the end of the heat insulation material at the pipe connection section with whatever seal material you have on hand so that water does not infiltrate the heat insulati...

Страница 7: ... connection When drain piping is necessary use the drain socket or the drain pan option A12 A18 A24 A42 Drain socket PAC SG61DS E Drain pan PAC SG63DP E PAC SG64DP E A B C D E Fig 6 1 Fig 6 2 A24 A42 A12 A18 A Earth terminal B Terminal block C Clamp D Service panel E Wire the cables so that they do not contact the center of the service panel or the gas valve 6 1 Outdoor unit Fig 6 1 Fig 6 2 1 Remo...

Страница 8: ...8 A12 A18 CORD COVER CONDUIT COVER CABLE STRAP TERMINAL BED SERVICE PANEL CONDUIT PLATE accessory GR L2 L1 S1 S2 S3 A24 42 ...

Страница 9: ... for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit terminals Warning Do not use the air conditioner if the insulat...

Страница 10: ... timer or the contact input of an ON OFF switch is added to the CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation 8 2 Refrigerant collecting pump down Perform the following pr...

Страница 11: ... 13 16 39 3 8 59 1 16 39 3 8 59 1 16 11 13 16 19 11 16 19 11 16 39 3 8 15 3 4 23 5 8 39 3 8 78 23 32 3 15 16 5 29 32 39 3 8 59 1 16 19 11 16 31 1 2 5 29 32 39 3 8 59 1 16 15 3 4 23 5 8 78 23 32 118 3 32 11 13 16 19 11 16 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 5 29 32 9 27 32 5 29 32 9 27 32 39 3 8 59 1 16 11 13 16 19 11 16 M...

Страница 12: ...3400 Lawrenceville Suwanee Road Suwanee Georgia 30024 Toll Free 800 433 4822 Toll Free Fax 800 889 9904 www mrslim com Specifications are subject to change without notice ...